Chapter 21
21.4.3

Input Method of STO Signal

・Input voltage for the STO signal can be chosen from the
internal power supply of inverter (P24S terminal) or an
external DC24V power supply.
Wiring example
Internal power supply+Sink logic
ST2
P24S STC
CMS
Short-circuit line
External power supply+Sink logic
ST2
Remove
short-circuit line
P24S STC
CMS
DC24V external power supply (SELV or PELV)
STC
ST1
Switch
: Direction of current
STC
ST1
Switch
: Direction of current
・Also, by changing the connecting point of short-circuit
line, you can choose input logic from sink and source.
・By turning off the external switch (contact point) for
STO input shown in the wiring example below, STO
function is enabled, and output to the motor is shuts off.
Internal power supply+Source logic
P24S STC
CMS
Short-circuit line
External power supply+Source logic
Remove
short-circuit line
P24S STC
CMS
DC24V external power supply (SELV or PELV)