Fire Alarm Systems | FPC-7034 IDC expander, 4-point
FPC-7034 IDC expander, 4-point
www.boschsecurity.com
The FPC‑7034 Four-point Expander doubles the
number of alarm initiating device circuits on the
FPD‑7024 Fire Alarm Control Panel (FACP). These
circuits are identical to the circuits on the FACP.
This plug‑in module is automatically recognized by the
control panel's firmware when power is restored to
the system.
Certifications and approvals
Region
Regulatory compliance/quality marks
USA
UL
UL 864, Control Units and Accessories
for Fire Alarm Systems
FM
FPC-7034
CSFM
see www.boschsecurity.com (the Bosch
website)
FDNY-
6173
CoA
Installation/configuration notes
Compatible Products
The FPC‑7034 is compatible with the FPD‑7024 FACPs.
For a list of compatible smoke detectors, see the FPD
7024 Smoke Detector Compatibility List Technogram.
Adds four Class B or two Class A initiating circuits
u
to the FPD‑7024 FACP
For use with normally‑open (NO) or normally‑closed
u
(NC) alarm contacts
Compatible with two‑wire or four‑wire smoke
u
detectors
Up to 20 two‑wire smoke detectors per circuit
u
Easy installation due to plug‑in design and screw
u
terminal circuit connections
Notice
When four‑wire smoke detectors are used, power
must be supplied to the detectors from either the
control panel or an external power source.
Mounting Considerations
The FPC‑7034 mounts on the FPD‑7024 control board,
just to the right of the keypad. Use the four nylon
stand‑offs supplied with the expander.
Initiating Circuit Wiring
Circuit connection for the expansion initiating circuits
is identical to the on‑board circuit configuration. For
wiring details, see the FPD‑7024 Installation Guide.
Install a supplied EOL resistor at the end of each
wiring run.
Parts included
Quantity
Component
1
Four-loop expander board
4
2.21 kΩ End‑of‑Line (EOL) resistors (P/
N: 25899)

Advertisement

loading

Summary of Contents for Bosch FPC 7034

  • Page 1 Fire Alarm Systems is identical to the on‑board circuit configuration. For wiring details, see the FPD‑7024 Installation Guide. FPC-7034 Install a supplied EOL resistor at the end of each CSFM see www.boschsecurity.com (the Bosch wiring run. website) Parts included FDNY- 6173...
  • Page 2: Power Requirements

    Phone: +1 800 289 0096 Phone: +65 6571 2808 emea.securitysystems@bosch.com www.boschsecurity.com Fax: +1 585 223 9180 Fax: +65 6571 2699 emea.boschsecurity.com onlinehelp@us.bosch.com apr.securitysystems@bosch.com www.boschsecurity.us www.boschsecurity.asia © Bosch Security Systems 2018 | Data subject to change without notice 2692182923 | en, V10, 05. Dec 2018...