Download Print this page

User Configuration - Omega DPG1000DAR-30V100 Instruction Sheet

Dpg1000dar series dpg1000dar series digital pressure gauges with alarms and 4-20 ma output

Advertisement

Pass Code Entry
A pass code is required to calibrate and configure the gauge.
Additional levels of security may be enabled by defining separate
pass codes for calibration, user configuration, and output test and
set point adjust modes. See Changing the User-Defined Pass Code
at the end of this manual to change pass codes.
Functions in user configuration mode
Restore original factory configuration
Enable/disable zero tare function
Fixed 1% deadband or adjustable hysteresis mode of operation
Operation for blinking alarm LEDs
Set point modes (high alarm/low alarm or state at power-up)
Relay action mode (normal/reverse)
DAR model retransmission output upper and lower limits
Enable/disable a pass code for output test and set point adjust
When the gauge enters a mode requiring a pass code, the display
indicates _ _ _ _ with the first underscore blinking, and either
TSTPC, CFGPC, CALPC on the lower display. All three pass codes
are initially set to the factory default of 3510.
Note: During pass code entry the LEDs will be off and the gauge will
not respond to changes in applied pressure. The relays will maintain
their prior state. The gauge will automatically revert to the normal
operation if no buttons are operated for approximately 15 seconds.
Use the s and t buttons to set the left-most digit to 3.
Press and release the SEL button to index to the next position. The
3 will remain, and the second position will be blinking.
Use the s and t buttons to select 5.
Press and release the SEL button to index to the next position. 3 5
will remain, and the third position will be blinking.
Use the s and t buttons to select 1.
Press and release the SEL button to index to the next position. 3 5
1 will remain, and the fourth position will be blinking.
Use the s and t buttons to select 0.
Press and release the SEL button to proceed.
If an incorrect pass code was entered, the gauge will to exit to the
normal operating mode. Upon successful pass code entry, follow
the steps in the appropriate section of this manual.
Note: To exit a mode at any time, press and hold the SEL button
until the display indicates – – – – .
Zero Tare Mode
If the gauge is not indicating zero with zero pressure applied but is
within approximately 3% of full scale pressure of zero, you may tare
the gauge to zero. This feature may be enabled or disabled. Absolute
ranges are configured with this feature turned off.
From the normal operating mode with the gauge port open to
atmosphere, press and hold both the s and t buttons and press
the SEL button. The relay outputs and the retransmission output will
hold the last value, and the visual indicators will be deactivated.
Release all buttons when the display indicates o o o o.
The display will indicate a newly calculated zero tare value with
Z OFF on the lower display. Note: If not within approximately 3%
of zero, Err0 will be displayed. Press the SEL button to cancel the
operation and return to normal operating mode without affecting
any existing zero tare value.
To cancel and remove any existing zero tare value, press and
release the t button. The display will indicate zero. To restore the
newly calculated zero tare value, press and release the s button.
To exit the Zero/Tare mode, press and release the SEL button. The
gauge will return to normal operation.
Output Test Mode
From the normal operating mode, press and hold the TEST button
and press the SEL button. Release both buttons when the display
indicates – – – – or _ _ _ _.
If pass code protection is enabled, the display indicates _ _ _ _
with the left-most underscore blinking, and TSTPC.
Enter the pass code as described in the Pass Code Entry section.
While in the Test mode with no buttons pressed, the display will indi-
cate the pressure with the engineering units blinking at a slow rate.
When the TEST button is pressed, the LED indicators and the relays
will toggle to their opposite states. The display will indicate the
preset test value with TEST on the lower display, and the retrans-
mission output on DAR models will correspond to the test value.
Pressing the s or the t button while holding the TEST button will
raise or lower the test value. Note that the gauge will not respond to
changes in applied pressure while the TEST button is held.
When the TEST button is released, the display, the LED indicators,
and the relay outputs will correspond to the applied pressure.
Press and release the SEL button to exit the Output Test mode and return
to normal operation.
DPG1000DAR Series Digital Pressure Gauges Alarms and 4-20 mA Output
Adjust Setpoint, Fixed Deadband Mode
"Set Point" is defined as the pressure value that will result in a
change of state only from a normal to an alarm condition.
"Trip Point" is defined as the pressure value that will result in a
change of state of alarm condition, and includes the effect of dead-
band when returning from an alarm to a normal condition.
Set Point 1
From the normal operating mode press the SEL button to display
Trip Point 1.
Press and hold the TEST button and press the SEL button. Release
both buttons when the display indicates – – – – .
If pass code protection is enabled, before the unit enters the Set
Point 1 Adjust Mode, the display initially indicates _ _ _ _ with
the left-most underscore blinking, and with TSTPC on the display.
Enter the pass code as described in the Pass Code Entry section.
While in the Set Point 1 Adjust mode with no buttons pressed, the
display will indicate Trip Point 1 with TRIP1 blinking at a slow rate
on the lower display, and the alarm indicators and the retransmis-
sion output will correspond to the applied pressure.
To adjust the Set Point 1 value, press and hold the TEST button.
The display will indicate Set Point 1 with SP1 on the lower display.
Operate the s and t buttons to adjust Set Point 1 to the desired
value. Release the TEST button to store the Set Point 1 value.
Note: The gauge will not respond to changes in applied pressure
while the TEST button is pressed. The alarm relays, LEDs, LCD
alarm icons, and the DAR output will maintain their prior states until
the TEST button is released.
To exit the Set Point 1 Adjust mode and return to the normal operat-
ing mode, press and release the SEL button.
Set Point 2
From the normal operating mode press the SEL button twice to
display Trip Point 2.
Press and hold the TEST button and press the SEL button. Release
both buttons when the display indicates – – – – .
If pass code protection is enabled, before the unit enters the Set
Point 2 Adjust Mode, the display initially indicates _ _ _ _ with
the left-most underscore blinking, and with TSTPC on the display.
Enter the pass code as described in the Pass Code Entry section.
While in the Set Point 2 Adjust mode with no buttons pressed, the
display will indicate Trip Point 2 with TRIP2 blinking at a slow rate
on the lower display, and the alarm indicators and the retransmis-
sion output will correspond to the applied pressure.
To adjust the Set Point 2 value, press and hold the TEST button.
The display will indicate Set Point 2 with SP2 on the lower display.
Operate the s and t buttons to adjust Set Point 2 to the desired
value. Release the TEST button to store the Set Point 2 value.
Note: The gauge will not respond to changes in applied pressure
while the TEST button is pressed. The alarm relays, LEDs, LCD
alarm icons, and the DAR output will maintain their prior states until
the TEST button is released.
To exit the Set Point 2 Adjust mode and return to normal operation,
press and release the SEL button.
Adjust Trip Point, Adjustable Hysteresis Mode
From the normal operating mode press the SEL button to display the
desired trip point (SET_1, RST_1, SET_2, or RST_2).
Press and hold the TEST button and press the SEL button. Release
both buttons when the display indicates – – – – .
If pass code protection is enabled, before the unit enters the Set
Point Adjust Mode, the display initially indicates _ _ _ _ with the
left-most underscore blinking, and with TSTPC on the lower display.
Enter the pass code as described in the Pass Code Entry section.
While in the Trip Point Adjust mode with no buttons pressed, the
display will indicate the trip point value with its designator (SET_1,
RST_1, SET_2, or RST_2) blinking at a slow rate.
To adjust the displayed trip point value, press and hold the TEST
button. The display will continue to indicate the trip point value.
Operate the s and t buttons to adjust the trip point to the desired
value. The trip point value is stored when the TEST button is
released. Note: The relays and indicators will not correspond to the
applied pressure value until the TEST button is released.
To exit the Trip Point Adjust mode and return to the normal operat-
ing mode, press and release the SEL button.

User Configuration

From the normal operating mode, press and hold the TEST and
the s buttons.
Then press the SEL button.
Release all buttons when the display indicates CFG.
Before the gauge enters the Configuration mode, the display initially
User Configuration—cont.
indicates _ _ _ _ with the first underscore blinking, and with
CFGPC on the lower display.
Enter the pass code as described in the Pass Code Entry section.
Restore Factory Configuration
The upper display will be blank, and the lower display will display
either USER_ or FCTRY.
If USER_ is selected, the existing user configuration will be retained
and will be accessible for modification in the following steps. To
select USER_, press and release the t button. The lower display
will indicate USER_.
If FCTRY is selected, the existing user configuration will be replaced
by the configuration as it left the factory and will be accessible for
modification in the following steps. To select FCTRY, press and
release the s button. The lower display will indicate FCTRY.
Press and release the SEL button to move on to the next parameter.
Zero Tare Configuration
The upper display will be blank, and the lower display will indicate
either ZTARE or NOZTR.
If ZTARE is selected, the user will be able to manually zero the
gauge from the normal operating mode.
To select ZTARE, press and release the s button. The lower display
will indicate ZTARE.
If NOZTR is selected the user will be prevented from zeroing the
gauge from the normal operating mode. This is default setting for
absolute reference ranges.
To select NOZTR, press and release the t button. The lower display
will indicate NOZTR.
Press and release the SEL button to move on to the next parameter.
Setpoint Type Configuration
The lower display will either indicate DBAND or ADJ_H.
If DBAND is selected, each output relay will operate with a 1% of
full-scale deadband between set and reset.
To select DBAND, press and release the s button. The lower
display will indicate DBAND.
If ADJ_H is selected, each output relay will have an adjustable SET
point and an adjustable RESET point.
To select ADJ_H, press and release the t button. The lower display
will indicate ADJ_H.
Press and release the SEL button to move on to the next parameter.
Alarm Annunciator Function Selection
The lower display will indicate either A_ACK, M_ACK or NO_AN.
If A_ACK is selected, an alarm condition will be automatically
acknowledged when the alarm condition clears. When an alarm
condition occurs, the LED for that alarm will begin to blink red and will
continue to blink red until it has been manually acknowledged or until
the alarm condition clears. If an alarm is manually acknowledged, the
LED will be steadily red while the alarm condition continues to exist.
The LED will be steadily green whenever no alarm condition exists.
If M_ACK is selected, an alarm condition must be manually
acknowledged. When an alarm condition occurs, the LED for that
alarm will blink red if the alarm condition exists or green if the alarm
condition no longer exists. The LED will continue to blink until it has
been manually acknowledged by a pressing the TEST button. Once
an alarm has been acknowledged, the LED will be steadily red while
the alarm condition exists or green when the alarm no longer exists.
If NO_AN is selected, the LEDs will not blink. When an alarm condi-
tion occurs, the LED associated with that alarm will be illuminated
steadily red if the alarm condition exists or green if the alarm condi-
tion no longer exists. In addition, the LCD display for ALARM1 and
ALARM2 will not be displayed during alarm conditions.
Use the s or t buttons to cycle through the three choices. When
the lower display indicates the desired annunciator action, press
and release the SEL button to move on to the next parameter.
Alarm Action Selection (Fixed Deadband Configuration)
The lower display will display either SP1_L or SP1_H.
If SP1_L is selected Alarm 1 will be a low alarm. Alarm 1 will be SET
when the pressure falls below Setpoint 1. Alarm 1 will be RESET
when the pressure rises above Setpoint 1 plus the preset deadband.
To select SP1_L, press and release the t button. The lower display
will indicate SP1_L.
If SP1_H is selected Alarm 1 will be a high alarm. Alarm 1 will be
SET when the pressure rises above Setpoint 1. Alarm 1 will be
RESET when the pressure falls below Setpoint 1 minus the preset
deadband. To select SP1_H, press and release the s button. The
lower display will indicate SP1_H.
Press and release the SEL button to move to Alarm 2.
The upper display will be blank, and the lower display will display
either SP2_L or SP2_H.
If SP2_L is selected Alarm 2 will be a low alarm. Alarm 2 will be SET
3

Advertisement

loading

This manual is also suitable for:

Dpg1000dar-30inhgvacDpg1000dar-05gDpg1000dar-15aDpg1000dar-15gDpg1000dar-30aDpg1000dar-60g ... Show all