Omega DPG1000DAR-30V100 Instruction Sheet

Dpg1000dar series dpg1000dar series digital pressure gauges with alarms and 4-20 ma output

Advertisement

Quick Links

Digital Pressure Gauges with Alarms
DPG1000DAR Series
M3363/0818
INSTRUCTION
SHEET
Shop online at omega.com e-mail: info@omega.com
For latest product manuals: www.omegamanual.info
Ranges and Resolution
See table below. Resolution is fixed as indicated in table.
Dual Alarms, 4-20 mA Output
DPG1000DAR-30V100
–30.0 inHg to 100.0 psig
DPG1000DAR-30INHGVAC
0.00-30.00 InHg Vac
DPG1000DAR-05G
0.00-5.000 psig
DPG1000DAR-15A
0.00-15.00 psia
DPG1000DAR-15G
0.00-15.00 psig
DPG1000DAR-30A
0.0-30.00 psia
DPG1000DAR-30G
0.0-30.00 psig
DPG1000DAR-60G
0.0-60.00 psig
DPG1000DAR-100A
0.0-100.0 psia
DPG1000DAR-100G
0.0-100.0 psig
DPG1000DAR-300G
DPG1000DAR-500G
DPG1000DAR-1KG
DPG1000DAR-2KG
DPG1000DAR-3KG
DPG1000DAR-5KG
Alarm Setting
(All are field configurable)
-1N (default if not specified)
HI/LO Normal action
-2N
HI/HI Normal action
-3N
LO/LO Normal action
-1R
HI/LO Reverse action
-2R
HI/HI Reverse action
-3R
LO/LO Reverse action
Numeric
display
Alarm1
88888
X X X X X
2
ALARM 1
ALARM 2
Select
Test
s
t
SEL TEST
Alarm 1
status
LED
¼" NPT
3.38" Standard
3.5" NEMA 4X
TM
Accuracy
Accuracy includes linearity, hysteresis, repeatability
±0.25% of full scale ±1 least significant digit
Sensor hysteresis:
Sensor repeatability:
Range
Display
4 readings per second nominal display update rate
4 digit LCD, 0.5" H and 5 character 0.25" H alphanumeric
Alarm 1 and Alarm 2 LCD indicators and bi-color (red/green)
LEDs
Controls & Functions
SEL Select and display alarm trip points
TEST Alarm acknowledge, or toggle alarms when in test mode
Increase alarm setpoint when in setpoint adjust mode
s
Decrease alarm setpoint when in setpoint adjust mode
t
Multi-level pass code protection for set-up and calibration
Alarm Relay Outputs
Programmable dual form C (SPDT) relay contacts for HI/LO,
HI/HI, LO/LO, normal or reverse acting with 1% deadband, or
0-300.0 psig
adjustable trip and reset points for each relay, manual or auto
0-500.0 psig
acknowledge.
0-1000 psig
1A/24VDC, 0.5A/115VAC, non-inductive
0-2000 psig
120 milliseconds typical response time
0-3000 psig
4-20 mA Retransmission Output
Updated approximately 16 times per second
0-5000 psig
Current output, 4-20 mA DC
Output drive (compliance) determined by power source
Alarm Type
6,553 counts over sensor range
Calibration
Non-interactive, ±10% of range
All pressure and absolute models: zero, midpoint, span
All vacuum models: –span, –midpoint, zero
Vacuum/pressure models: –span, zero, +midpoint, +span
±15 psi models: –span, –midpoint, zero, +midpoint, +span
Alpha-
2.88"
numeric
display
Alarm 2
Up
Down
Alarm 2
status
LED
0.75"
1.65"
WARNING: This product can expose you to chemicals including
lead, nickel and chromium, which are known to the State of
California to cause cancer or birth defects or other reproductive
harm. For more information go to www.P65Warnings.ca.gov
and 4-20 mA Output
±0.015% FS, included in accuracy
±0.01% FS, included in accuracy
3 ft long, 22 AWG cables
with stripped and tinned
wire ends
4 conductor and
6 conductor
Allow 1" wire clearance
Turn at hex
fitting only
Power
8 to 24 VAC 50/60 Hz or 9 to 32 VDC
Gauge is on when power is on
Designed for continuous operation
1.0 watt maximum power consumption
Weight
9.5 ounces (approx.), shipping wt. 1 pound (approx.)
Housing
Extruded aluminum case, epoxy powder coated, ABS/ polycar-
bonate bezel, front and rear gaskets, polycarbonate label
Connection, Material, Media Compatibility
1/4" NPT male fitting
All wetted parts are 316L stainless steel
Overpressure, Burst, Vacuum
Ranges using 3000 psig sensor: 5000 psig overpressure
Ranges using 5000 psig sensor: 7500 psig overpressure
All others:
2 X pressure range
3000 psi, 5000 psi, and 4 digit ranges 112.5% full scale out-
of-range display: 1– – – or I –.–.–.–
Under-range display (non-vacuum sensors): –Err
4 X sensor burst pressure rating, or 10,000 psi, whichever is
less
Vacuum service: 15 psia, ±15 psig, 15 psig, 30 psia,
100 psig, 100 psia, 200 psig sensors
Environmental
Storage temperature:
–40 to 203°F (–40 to 95°C)
Operating temperature:
–4 to 185°F (–20 to 85°C)
Compensated temperature:
32 to 158°F (0 to 70°C)

Advertisement

loading

Summary of Contents for Omega DPG1000DAR-30V100

  • Page 1 Digital Pressure Gauges with Alarms and 4-20 mA Output DPG1000DAR Series M3363/0818 INSTRUCTION SHEET Shop online at omega.com e-mail: info@omega.com For latest product manuals: www.omegamanual.info Ranges and Resolution Accuracy Power See table below. Resolution is fixed as indicated in table.
  • Page 2: Installation Precautions

    DPG1000DAR Series Digital Pressure Gauges with Alarms and 4-20 mA Output Installation Precautions Power Operation with Adjustable Hysteresis Alarms 4 Read these instructions before using the gauge. Configuration may The gauge is powered on whenever a supply voltage is applied. In the adjustable hysteresis mode, two independent set and reset be easier before installation.
  • Page 3: User Configuration

    DPG1000DAR Series Digital Pressure Gauges Alarms and 4-20 mA Output Pass Code Entry Adjust Setpoint, Fixed Deadband Mode User Configuration—cont. A pass code is required to calibrate and configure the gauge. “Set Point” is defined as the pressure value that will result in a indicates _ _ _ _ with the first underscore blinking, and with Additional levels of security may be enabled by defining separate change of state only from a normal to an alarm condition.
  • Page 4: Calibration Preparation

    DPG1000DAR Series Digital Pressure Gauges Alarms and 4-20 mA Output User Configuration—cont. User Configuration—cont. Calibration—cont. when the pressure falls below Setpoint 2. Alarm 2 will be RESET Output Test and Set Point Adjust Modes Pass Code Protection Note: If the SEL button is held depressed for longer than 2 seconds, when the pressure rises above Setpoint 2 plus the preset deadband.
  • Page 5 Fax: (203) 359-7700 e-mail: info@omega.com For Other Locations Visit omega.com/worldwide The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice. WARRANTY/DISCLAIMER OMEGA ENGINEERING, INC.
  • Page 6 Where Do I Find Everything I Need for Process Measurement and Control? OMEGA…Of Course! Shop online at omega.com TEMPERATURE M U Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies M U Wire: Thermocouple, RTD & Thermistor M U Calibrators & Ice Point References M U Recorders, Controllers &...

This manual is also suitable for:

Dpg1000dar-30inhgvacDpg1000dar-05gDpg1000dar-15aDpg1000dar-15gDpg1000dar-30aDpg1000dar-60g ... Show all