MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units
Chapter 2. Setup Mode
power-reversal protection. The Trip Unit display is
shown in Figure 38.
Figure 38. Trip Unit display for power-reversal relay delay.
Rating Plug Current Setting
The Trip Unit display for rating plug setting is
shown in Figure 39. Enter the current setting of the
rating plug by scrolling through the list with
and pressing
ENTER
reached. Table 16 lists the available rating plugs for
the various Trip Units.
C C C C A A A A U U U U T T T T I I I I O O O O N N N N : : : : Incorrect storage of this set point will
result in incorrect metering values.
A A A A T T T T T T T T E E E E N N N N T T T T I I I I O O O O N N N N : : : : Si une valeur incorrecte est
enregistrée pour ce réglage, les mesures seront
fausses.
Figure 39. Trip Unit display for rating plug current set point.
B B B B r r r r e e e e a a a a k k k k e e e e r r r r
F F F F r r r r a a a a m m m m e e e e
S S S S i i i i z z z z e e e e
R R R R a a a a t t t t i i i i n n n n g g g g P P P P l l l l u u u u g g g g O O O O p p p p t t t t i i i i o o o o n n n n s s s s , , , , A A A A m m m m p p p p s s s s
60, 80, 100, 125, 150, 200, 225, 250, 300, 400,
800–2000
450, 500, 600, 630, 700, 750, 800, 900, 1000,
A
1100, 1200, 1250, 1500, 1600, 2000
2500–320
1200, 1500, 1600, 2000, 2400, 2500, 3000,
0 A
3200
1600, 2000, 2400, 2500, 3000, 3200, 3600,
4000 A
4000
5000 A
3200, 4000, 5000
Table 16. Trip Unit rating plug options.
when the correct value is
Potential Transformer Primary Voltage
Enter the primary voltage rating of the potential
transformer, as illustrated in Figure 40. The range of
values is 120 to 600 volts, with an increment of 1 volt.
C C C C A A A A U U U U T T T T I I I I O O O O N N N N : : : : Incorrect storage of this set point will
result in incorrect metering values. Even if this set-
ting is entered remotely, it must be entered again
locally.
A A A A T T T T T T T T E E E E N N N N T T T T I I I I O O O O N N N N : : : : Si une valeur incorrecte est
enregistrée pour ce réglage, les mesures seront
fausses. Cette valeur doit être enregistrée locallement
même dans le cas d'une utilisation à distance avec
commnet.
VALUE
Figure 40. Trip Unit display for potential transformer primary
Potential Transformer Connection
Note that this step applies only to MicroVersaTrip
PM Trip Units.
Select the appropriate potential transformer connec-
tion, either line-to-line (
(
), as illustrated in Figure 41.
Ph-N
C C C C A A A A U U U U T T T T I I I I O O O O N N N N : : : : Incorrect storage of this set point will
result in incorrect metering values.
A A A A T T T T T T T T E E E E N N N N T T T T I I I I O O O O N N N N : : : : Si une valeur incorrecte est
enregistrée pour ce réglage, les mesures seront
fausses.
22
voltage set point.
) or line-to-neutral
Ph-Ph