Samsung MR-DH00 Technical Data Book
Samsung MR-DH00 Technical Data Book

Samsung MR-DH00 Technical Data Book

Dvm control system
Hide thumbs Also See for MR-DH00:
Table of Contents

Advertisement

Control Systems
2014.04
DBEU-14042B(A)
SAMSUNG ELECTRONICS Co., LTD.
416 Maetan-3Dong, Yeongtong-Gu, Suwon City Gyeonggi-Do, Korea 443-742
Internet Website : www.dvmsystem.com
Email : Airconditioner@samsung.com
Specifications may be subject to change without prior notice for product improvement.

Advertisement

Table of Contents
loading

Summary of Contents for Samsung MR-DH00

  • Page 1 Control Systems 2014.04 DBEU-14042B(A) SAMSUNG ELECTRONICS Co., LTD. 416 Maetan-3Dong, Yeongtong-Gu, Suwon City Gyeonggi-Do, Korea 443-742 Internet Website : www.dvmsystem.com Email : Airconditioner@samsung.com Specifications may be subject to change without prior notice for product improvement.
  • Page 2: Table Of Contents

    5) Connection....47 MR-DH00 5) Display ..... . 48 1) Features .
  • Page 3 Power distribution system Operation mode selection switch Electricity meter interface module MCM-C200 MIM-B16N 1) Features ..... 73 1) Features ....128 2) Installation .
  • Page 4 VII. Building management systems Test run tool for system air conditioner installation DMS L-net(Lonworks GW) S-checker MIM-B18N 1) Features ....146 MIM-C10N 2) Product specification .
  • Page 5 Overview of DVM S New communication system diargram DMS B-net DMS L-net (MIM-B17N) (MIM-B18N) S-NET3 (MST-P3P) DMS-Bnet DMS-Lnet Ethernet DMS2 (MIM-D00AN) Control layer Set layer Max.16 outdoor units Max. 80 units Max.15 Contollers Max.16 Controllers Max. 128 indoor units (Includes ERV, MCU) (Max.
  • Page 6 Compatibility table (New Conventional) Conventional communication Conventional communication Controller Product DMS2 Interface OnOff Outdoor unit Indoor unit (BACnet GW/ S-NET mini module Controller LonWorks GW) Wired remote controller (MWR-WE10N) Interface module I (MIM-N00) Interface module II (MIM-N01) Interface module III (MIM-N10) OnOff Controller (MCM-A202DN) DMS2 (MIM-D00AN) BACnet GW (MIM-B17N)
  • Page 7 Conventional communication Conventional communication Controller Product DMS2 Interface OnOff Outdoor unit Indoor unit (BACnet GW/ S-NET mini module Controller LonWorks GW) Wired remote controller (MWR-WE10) Interface module (MIM-B13D,E) OnOff controller (MCM-A202D) Function controller (MCM-A100) DMS2 (MIM-D00A) BACnet GW (MIM-B17) LonWorks GW (MIM-B18) PIM (MIM-B16) S-NET 3 (MST-S3P,D3P,P3P) S-NET mini (MST-S3W)
  • Page 8 DVM CONTROL SYSTEMS...
  • Page 9 Individual Control Systems Receiver & Display unit ....Wireless remote controller ... . Wired remote controller ....ERV wired remote controller.
  • Page 10: Receiver & Display Unit

    Connector : 13Pin Receiver & Display unit PCB Note Wire length: 10m Receiver & Display unit is only available for a duct type indoor unit. 2. Wireless remote controller MR-DH00 1) Features (Unit : mm) Easy and convenient operation control...
  • Page 11 2) Description of parts ⑰ ① ⑱ ② ⑨ ③ ⑲ ⑪ ⑩ ④ ⑫ ⑳ ⑤ ⑭ ⑥ ⑬ ⑥ ⑦ ⑬ ⑧ ⑮ ⑯ ②, ⑥ , ⑥ , ⑧, ⑬ , ⑳, is only supported and available in certain indoor units. Description Name ①...
  • Page 12: Additional Function

    Control Systems Individual control systems 2. Wireless remote controller MR-DH00 3) Additional function ❶ Remove the batteries from the remote controller. ❷ ❸ Set the 2 digits of option code. ❹ Input 20 digits in total. ❺ Press the button more than twice to set the indoor unit option code.
  • Page 13: Wired Remote Controller

    3. Wired remote controller MWR-WE10N 1) Features (Unit : mm) 120.0 19.5 (1) Air conditioner / ERV control (Function is available when indoor units support any of above functions) (4) User convenience function - Indoor unit cycle data monitoring - Indoor unit option code setting and monitoring - Indoor unit address and option setting and monitoring 2) Product specification Power Supply...
  • Page 14: Description Of Parts

    Control Systems Individual control systems 3. Wired remote controller MWR-WE10N 3) Description of parts ④ ⑤⑨⑩⑪ ⑫ ⑬ (1) Display ① ⑭ ② ⑮ ⑯ ③ ⑥ ⑰ ⑱ ⑦ ⑧ ⑳ ⑲ Classification Function Indication ① Displays air conditioner operation ②...
  • Page 15 (2) Buttons ⑫ ⑨ ⑱ ⑧ ⑬ ② ① ⑮ ③ ⑳ ⑤ ⑥ ⑦ ④⑪ ⑩⑯⑲ ⑭ ⑰ Classification Function Button ① ② Selects the desired air conditioner operation ③ Sets the desired temperature ④ Changes the air conditioner’s fan speed ⑤...
  • Page 16 Control Systems Individual control systems 3. Wired remote controller MWR-WE10N 3) Description of parts (3) PCB Name Description ① It is used to upgrade the software Communication and power ② ① MWR-WE10N uses 2-wire power line communication. ② 4) Option function Main Function Default...
  • Page 17 How to set the user mode (2) Refer to the Wired Remote Controller’s User Set list on the next [∧]/[∨] buttons, select a main menu number and press the [>] button to enter the sub-menu setting screen. [∧]/[∨] buttons, select a sub-menu number and press the [>] button to enter the data setting screen.
  • Page 18 Control Systems Individual control systems 3. Wired remote controller MWR-WE10N 4) Option function ervice mode Main Function Default Unit menu menu Used Wired remote Use of wireless remote controller 0-No use, 1-Use controller Option 0-MAIN, 1-SUB 0–Indoor unit, 1–Wired remote controller Use of average temperature 0-No use, 1-Use Wired remote...
  • Page 19 Main Function Default Unit menu menu Used 1, 2 0~30 3, 4 0~25 1RPM 0- Pre, checking Filter performance 1-Medium performance, 2-High performance 0-30, 1-40, 2-50 Use of discharge temperature Indoor unit, 0-No use, 1-Use control AHU discharge Cooling discharge temperature 3, 4 temperature Heating discharge temperature...
  • Page 20 Control Systems Individual control systems 3. Wired remote controller MWR-WE10N 4) Option function ervice mode How to set the service mode (1) If you want to use the various additional functions for your Wired time for more than three seconds. (2) Refer to the list of additional functions for your Wired Remote Controller Using the [∧]/[∨] buttons, select a main menu number and press the [>] button to enter the sub-menu setting screen.
  • Page 21 uilt-in temperature sensor of wired remote controller (However, indoor unit is limited to DVM S series ) Check the setting of the wired remote controller built-in sensor from the service menu. Main Used Factory Function Description Unit menu menu Wireless remote Use of wireless remote 0-No use, 1-Use controller...
  • Page 22 Control Systems Individual control systems 3. Wired remote controller MWR-WE10N 4) Option function uilt-in temperature sensor of wired remote controller (1) When communication error occurs over 3 minutes, Indoor unit ignores the built-in temperature sensor and use indoor unit temperature sensor. Ignores the temperature compensation setting on the wired remote controller and use the compensation value set on indoor unit instead.
  • Page 23 5) Display rror display displayed in the LCD display. LCD Display When an Error Occurs in Your Indoor/Outdoor Units (Product Group Display : A20) Example : Error 121 occurred in indoor unit with main address no. 18 (decimal numbers). Refers to the indoor unit Outdoor unit address Indoor unit Main address Error code...
  • Page 24 Control Systems Individual control systems 3. Wired remote controller MWR-WE10N 5) Display ired remote controller error codes Display Description Remarks after successful communication No communication between Master (Main) and Slave(Sub) wired remote controllers When using Master remote controller Slave wired remote controller When external interlocking control is in No indoor unit installed for interlocking function Detection available in Master wired...
  • Page 25 Individual control (1) Control 1 indoor unit with 1 wired remote controller F1/F2 Indoor unit Outdoor unit F3/F4 Wired remote controller Control All connected indoor units Display Operation status of the connected indoor unit Group control (1) Control multiple indoor units with 1 wired remote controller Indoor unit Outdoor unit Wired remote controller...
  • Page 26 Control Systems Individual control systems 3. Wired remote controller MWR-WE10N Group control (3) Control 1 or multiple indoor units with 2 wired remote controllers F1/F2 Indoor unit Outdoor unit F3/F4 Wired remote controller Master Slave Master Slave Maximum 16 indoor units can be connected Control All connected indoor units Priority 2.
  • Page 27: Features

    MWR-SH00N 1) Features (Unit : mm) 2) Product specification Power supply Power consumption 1.5 W 30 % RH~90 % RH Communication 100 m 16 indoor units Indoor unit Model...
  • Page 28: Description Of Parts

    Control Systems Individual control systems 3. Wired remote controller MWR-SH00N ⑪ ⑩ 3) Description of parts ⑨ ① ② ③ ⑧ ④ ⑦ ⑤ ⑥ ⑫ ⑱ ⑬ ⑭ ⑰ ⑮ ⑯ Name Description Indicator will be on when remote controller usage restriction is set. ①...
  • Page 29 Description Name Power/communication ① connection terminal ① 4) Option function SEG in use How to set Sub Menu Main Menu Down Left Exit Save Press for more than 3 seconds simultaneously Main Function Default Save menu Reset User mode to default value 0 - Disabled, 1 - Reset none Partially lock...
  • Page 30 Control Systems Individual control systems 3. Wired remote controller MWR-SH00N 4) Option function SEG in use Service mode Sub Menu How to set Main Menu Down Left Exit Save Press for more than 3 seconds simultaneously Auto Cool Heat Auto Cool Heat Main...
  • Page 31: System Reset

    Main Function Default value menu menu in use 0- Cooling and heating, 1-Cooling 'cooling only' only Setting wireless remote controller usage 0 - Disable, 1 - Enable Set option restriction function of 0-Master, 1-Slave the wired Setting auto operation usage 0 - Disable, 1 - Enable remote controller...
  • Page 32: Display

    Control Systems Individual control systems 3. Wired remote controller MWR-SH00N 5) Display Error display Address of the product with error and the error code will be displayed alternately. Error 121 occurs for indoor unit No. 10 (Decimal digits) Outdoor unit address Indoor unit Main address Error code Refers to the indoor unit...
  • Page 33 Individual control (1) Control 1 indoor unit with 1 wired remote controller F1/F2 Indoor unit Outdoor unit F3/F4 Wired remote controller Control All connected indoor units Display Operation status of the connected indoor unit Group control (1) Control multiple indoor units with 1 wired remote controller Indoor unit Outdoor unit Wired remote controller...
  • Page 34 Control Systems Individual control systems 3. Wired remote controller MWR-SH00N Group control (3) Control 1 or multiple indoor units with 2 wired remote controllers F1/F2 Indoor unit Outdoor unit F3/F4 Wired remote controller Master Slave Master Slave Maximum 16 indoor units can be connected Control All connected indoor units Priority 1.
  • Page 35: Erv Wired Remote Controller

    4. ERV wired remote controller MWR-VH12N 1) Features (Unit : mm) 122.0 75.0 16.6 2) Product specification Power supply Power consumption 1.5 W 30 % RH~90 % RH Communication 100 m...
  • Page 36: Description Of Parts

    Control Systems Individual control systems 4. ERV wired remote controller MWR-VH12N 3) Description of parts ⑧ ⑨ ⑦ ⑥ ① ⑤ ② ④ ③ ⑩ ⑭ ⑮ ⑪ ⑫ ⑯ ⑬ Name Description ① Operation mode indicator Indicates when On timer is set. Indicates when Off timer is set.
  • Page 37: Option Function

    Name Description ① ① connection terminal 4) Option function How to set SEG used Sub menu Main menu Press the buttons at the same time for over Set, Cancel 3 seconds PAGE 1 PAGE 2 PAGE 3 PAGE 4 PAGE 5 PAGE 6 PAGE 7 PAGE 8...
  • Page 38 Control Systems Individual control systems 4. ERV wired remote controller MWR-VH12N 4) Option function ervice mode How to set SEG used Sub menu Main menu Press the buttons at the same time for over 3 seconds Set, Cancel Main Function Default value Remarks menu menu...
  • Page 39 Main Function Default value Remarks menu menu in use Indoor unit Page Address of registered device master view Master Hexadecimal number function master Page Address of registered device master Hexadecimal number 0 - Master, 1 - Slave wired remote controller option function Setting external 0 - No use, 1 - Use...
  • Page 40: Display

    Control Systems Individual control systems 4. ERV wired remote controller MWR-VH12N 5) Display rror display Address of the product with error and the error code will be displayed alternately. Example : Error 101 occurs for indoor unit No. 10 (Decimal digits) Indoor unit address Refers to the indoor unit (Displayed in hexadecimal)
  • Page 41 Individual control 1 ERV, 1 wired remote controller COM2(F3, F4) COM2(F3, F4) COM2(F3, F4) Control All connected ERVs Display Group control (1) COM2(F3, F4) COM2(F3, F4) Control All connected ERVs Display Group control (2) remote controller COM1(F1, F2) COM2(F3, F4) COM1(F1, F2) COM2(F3, F4) Control...
  • Page 42 Control Systems Individual control systems 4. ERV wired remote controller MWR-VH12N Mixed installation Outdoor unit COM1(F1, F2) COM1(F1, F2) COM1(F1, F2) Indoor unit Indoor unit Indoor unit COM2(F3, F4) COM2(F3, F4) COM2(F3, F4) Control All connected ERVs Display Caution 100m controller : 100m...
  • Page 43 Centralized control systems Interface module ....ERV interface module ....OnOff controlle .
  • Page 44: Centralized Control Systems

    Control Systems Centralized control systems 1. Interface module MIM-N01 1) Features Communication interface module between new communication ERV and controller Connect 1 ERV interface module to Max. 16 ERVs Individual control – Maximum 16 ERVs Group control – Maximum 16 groups Supported communication type ↔...
  • Page 45: Description Of Parts

    ompatible Models (1) New communication outdoor unit Conventional communication upper level controller Outdoor unit ① OnOff controller : MCM-A202D ② DMS2 : MIM-D00A Upper level controller ③ BACnet Gateway : MIM-B17 ④ Lonworks Gateway : MM-B18 ⑤ S-NET mini : MST-S3W Function controller and S-NET 2 Plus are not supported.
  • Page 46: Connection Diagram

    Control Systems Centralized control systems 1. Interface module MIM-N01 4) Connection diagram ew communication outdoor unit Conventional communication upper level controller C1/C2 C1/C2 Conventional communication R1/R2 R1/R2 R1/R2 New communication MIM-N01 MIM-N01 MIM-N01 MIM-N01 Conventional communication outdoor unit New communication upper level controller R1/R2 New communication Conventional communication...
  • Page 47: Connection

    5) Connection onnecting with OnOff controller Conventional communication outdoor unit New communication OnOff controller (MCM-A202DN) New communication outdoor unit Conventional communication OnOff controller (MCM-A202D) OnOff controller Connecting to Touch centralized controller Conventional communication outdoor unit New communication Touch centralized controller (ACM-A300N) Touch centralized controller Connecting to DMS 2 / BACnet GW / Lonwoks GW Conventional communication outdoor unit...
  • Page 48: Display

    Control Systems Centralized control systems 1. Interface module MIM-N01 6) Display Checking the operation Software version is Display the set value Display the address of Outdoor unit detected Tracking completed displayed after power of the rotary switch the interface module during tracking Displays the Main address of the communicating is supplied...
  • Page 49: Erv Interface Module

    2. ERV interface module MIM-N10 1) Features Communication interface module between new communication ERV and controller Connect 1 ERV interface module to Max. 16 ERVs Individual control – Maximum 16 ERVs Group control – Maximum 16 groups Supported communication type ↔...
  • Page 50 Control Systems Centralized control systems 2. ERV interface module MIM-N10 2) Product specification Compatible Models (1) New communication ERV Conventional communication upper level controller New communication ERV ① OnOff controller : MCM-A202D ② DMS2 : MIM-D00A Upper level controller ③ BACnet GW : MIM-B17 ④...
  • Page 51: Description Of Parts

    3) Description of parts ⑧ Name Description Communication terminal that connects to outdoor unit / ① communication ⑥ connector ② Power connector DC12V Communication indicator LED ③ (Left LED 3 : No function Communication ③ Middle RED : Blinks during it communicates with upper level controller ⑤...
  • Page 52: Connection Diagram

    Control Systems Centralized control systems 2. ERV interface module MIM-N10 4) Connection diagram New communication ERV ↔ Conventional communication upper level controller C1/C2 C1/C2 Conventional communication R1/R2 R1/R2 R1/R2 communication MIM-N10 MIM-N10 MIM-N10 MIM-N10 Conventional/new communication ERV ↔ New communication upper level controller R1/R2 communication MIM-N10...
  • Page 53: Connection

    5) Connection Connecting with OnOff controller ▶ Conventional communication ERV ↔ New communication OnOff controller (MCM-A202DN) ▶ New communication ERV ↔ Conventional communication OnOff controller (MCM-A202D) OnOff controller Note must be used.
  • Page 54: Checking The Operation

    Control Systems Centralized control systems 2. ERV Interface module MIM-N10 5) Connection Connecting with Touch centralized controller ▶ Conventional communication ERV ↔ New communication Touch centralized controller (MCM-A300N) ▶ New communication ERV ↔ Conventional communication Touch centralized controller (MCM-A300N) Touch centralized controller Connecting with DMS2 / BACnet GW / Lonwoks GW ▶...
  • Page 55: Features

    3. OnOff controller MCM-A202DN 1) Features 2) Product specification Power supply Power consumption Operating Temperature range ° °C Operating Humidity range Communication Max. Communication length Set layer Max. connectable number of device Control layer Compatible product Conventional communication outdoor unit requires interface module (MIM-N01) to establish connection MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected.
  • Page 56: Description Of Parts

    Control Systems Centralized control systems 3. OnOff controller MCM-A202DN 3) Description of parts ① ⑥ ② ③ ⑥ COOL AUTO HEAT ④ ⑧ ⑤ ⑦ Name Description It lights on when more than one indoor unit operates. ① Indoor unit operation LED It flickers during indoor unit tracking process after power reset.
  • Page 57: Optional Function

    ddress & option switch DIP SW Description SW02 Restriction setting on wired/wireless remote control use SW01 Cool Wired/Wireless remote control use is allowed all the time. Level 0 Auto Option switch Wired/Wireless remote control use is allowed only if indoor unit is ON Heat by the OnOff controller.
  • Page 58: Connection Diagram

    Control Systems Centralized control systems 3. OnOff controller MCM-A202DN 4) Optional function peration mode selection switch Indoor unit 1 Indoor unit 2 Indoor unit 3 ndoor unit operation Cooling mode set Heating mode set Auto mode set 5) Connection diagram Set layer connection (F1/F2) Max.
  • Page 59 Control layer connection (R1/R2) Connectable controller : - Touch centralized controller (MCM-A300N). - OnOff controller (MCM-A202DN). (1) Connection with outdoor unit F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2 Control layer...
  • Page 60 Control Systems Centralized control systems 3. OnOff controller MCM-A202DN 5) Connection diagram Control layer connection (R1/R2) (2) Connection with DMS2/BACnet GW/Lonworks GW Case2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 R1 R2 F1 F2 R1 R2 Ex.) DMS2 (MIM-D00AN) Control layer Caution Set layer...
  • Page 61: Display

    6) Display arious LED display Main : 0 Main : 1 Main : 2 Address : 1 RMC(1) : 1 RMC(1) : 1 RMC(1) : 1 RMC(2) : 0 RMC(2) : 1 RMC(2) : 2 R1/R2 Main : 0 Main : 1 Main : 2 RMC(1) : 1 RMC(1) : 1...
  • Page 62: Touch Centralized Controller

    Control Systems Centralized control systems 4. Touch centralized controller MCM-A300N 1) Features Unit : mm View indoor unit error history 2) Product specification Power supply Power consumption 110W Operating temperature range 0°C~40°C Operating humidity range 30%RH~90%RH Communication External Digital Output communication Digital Input port...
  • Page 63: Description Of Parts

    Compatible product Outdoor unit OnOff controller (MCM-A202DN) Touch centralized controller (MCM-A300N) Controller DMS2 (MIM-D00AN) BACnet gateway (MIM-B17N) Lonworks gateway (MIM-B18N) Conventional communication outdoor unit requires interface module (MIM-N01) to establish connection MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected. To connect ERV, MIM-N10 interface module is required. 3) Description of parts ②...
  • Page 64: Connection Diagram

    Control Systems Centralized control systems 4. Touch centralized controller MCM-A300N 4) Connection diagram S-NET 3 TCP/IP Control layer Touch centralized OnOff controller OnOff controller controller DMS2 RS485 Touch centralized controller Outdoor unit Maximum 128 indoor units (DVM series) Set layer...
  • Page 65: Connection

    5) Connection Set layer connection (F1/F2) Max. 16 Controllers can be connected to same communication line. Connectable controller: - OnOff controller (MCM-A202DN) - Touch centralized controller (MCM-A300N) Set layer F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2 Set layer F1 F2 R1 R2...
  • Page 66 Control Systems Centralized control systems 4. Touch centralized controller MCM-A300N 5) Connection Control layer connection (R1/R2) (2) Connection with DMS2 / BACnet GW / Lonworks GW Case1 F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 R1 R2 Ex.) DMS2(MIM-D00AN) Control layer...
  • Page 67: Main Function

    Caution LonWorks GW cannot be connected to same communication line. Set layer F1 F2 R1 R2 F1 F2 F1 F2 F1 F2 F1 F2 DMS2 / BACnet GW / LonWorks GW should be connected to control layer. 6) Main function one control You can create a zone by grouping multiple indoor units Maximum 12 zones can be created (Total up to 128 indoor units)
  • Page 68 Control Systems Centralized control systems 4. Touch centralized controller MCM-A300N 6) Main function Grouping indoor units Displays number of indoor units in a group Displays number of indoor units in a group Schedule control Maximum 10 schedules can be created Excluded day setting is possible...
  • Page 69 Setting indoor unit usage restriction (1) Cool lower limit/ Heat upper limit It can set the lower temperature limit in Cool mode and the upper temperature limit in Heat mode. This setting can be changed by other touch centralized controller and DMS2. (2) Operation mode limit This setting can be changed by other touch centralized controller and DMS2.
  • Page 70 Control Systems Centralized control systems 4. Touch centralized controller MCM-A300N 6) Main function ock function You can lock the functions of Touch centralized controller. (1) Screen lock You can lock the screen. (2) Operating panel lock You can set the access lock of each item of operating panel. The locked item will be deactivated.
  • Page 71 Remote controller usage restriction (1) Indoor unit operating panel You can set the controller restriction. You can set the type of controller which will be restricted when "Disable RC" is applied from operating panel. [Settings] [Device settings] [Control level] (2) Device settings You can set the type of controller which will be restricted when "Disable RC"...
  • Page 72 Control Systems Centralized control systems 4. Touch centralized controller MCM-A300N 6) Main function Tracking Detects all the indoor and outdoor units that are connected to communication line of Touch centralized controller indoor units that will be controlled from each Touch centralized controller. Hiding indoor unit...
  • Page 73: Operation Mode Selection Switch

    5. Operation mode selection switch MCM-C200 1) Features Operation mode selection switch Mixed operation mode protection (Unit : mm) 2) Installation Max. distance between the outdoor unit PCB and the MCM-200: 100m...
  • Page 74: Control Example

    Control Systems Centralized control systems 5. Operation mode selection switch MCM-C200 3) Control example Initial condition Cool/Heat Selector : Heating position Compressor ON Sequence 1 Set the Cool/Heat selector to the Cooling position ① Change Cool/Heat Selector to Cooling ② Result ③...
  • Page 75: Iii. Integrated Management

    III. Integrated management systems DMS2 ......S-NET3......
  • Page 76: Product Specification

    Control Systems Integrated management systems 1. DMS2 MIM-D00AN 1) Features 2) Product specification Source Power Input Output Operating temperature ℃ ℃ range Operating humidity range Communication method External Digital Output connection Digital Input port RS485 Maximum Digital Output length of Digital Input connection Ethernet...
  • Page 77: Description Of Parts

    Compatible product Conventional communication outdoor unit requires interface module(MIM-N01). MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected. To connect ERV, MIM-N10 interface module is required. PIM connection is different depending on software version. - Before 2.6.0.3 : MIM-B16 only - 2.6.0.3 : MIM-B16N only - After 2.6.1.
  • Page 78 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 3) Description of parts ottom DI Terminal2 DO Terminal1 DI Terminal1 DO Terminal 2 Power Terminal RS485 Communication terminal Reset Button Cable tie groove Serial Terminal LAN Terminal SD Card Socket enu and display DMS2 IP Current time Detail description...
  • Page 79: Connection Diagram

    4) Connection diagram MIM-B16(PIM) should be connected separately with outdoor unit or controllers. MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2. 5) Wiring F1 F2 R1 R2 F1 F2 R1 R2 (1) Connecting outdoor unit directly (2) Connecting OnOff controller / Touch centralized controller Note...
  • Page 80 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 5) Wiring onnecting with outdoor unit DMS2 Outdoor unit Outdoor unit Outdoor unit Outdoor unit Maximum 16 Outdoor unit connections Outdoor unit Outdoor unit onnecting with OnOff controller / Touch centralized controller DMS2 ex) OnOff controller Maximum 15...
  • Page 81 onnecting with outdoor unit and OnOff controller / Touch centralized controller DMS2 ex) OnOff controller Maximum 16 outdoor units Outdoor unit Outdoor unit Outdoor unit iring distance ⓐ ⓑ ⓒ ⓓ ⓔ Distance between DMS2 and OnOff controller / Touch centralized controller /outdoor unit ⓒ...
  • Page 82 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Tracking DMS2...
  • Page 83 Control & monitoring Monitoring Control Multiple language support Set silent contol...
  • Page 84 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function OnOff controller restriction Contact point control You can select emergency operation pattern (1) Pattern 2 Patter 2 Short external contact : Emergency stop Open external contact : Resume operation (2) Pattern 3 Pattern 3 External contact input to DI-1 External contact input to DI-2...
  • Page 85 General external contact point control DI : Voltage free contact signal input (Open / Short) DO : Contact signal output (DC 12V) Note Indoor unit usage restriction ❹ ❸ ❷ ❶ ❶ Check the indoor unit address. ❷ Select the Limit mode Control mode will be set automatically depends on the seleceted restricted mode ❸...
  • Page 86 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Logic control What is logic control? Examples of utilizing the logic control Input Output Compound Comparison Edit factor Command factor operator => Single =< factor > < Arithmetic factor Function factor...
  • Page 87 (1) Editing input factor ④ ② ③ ⑤ ⑥ ⑧ ⑨ ⑦ ① ① ② ③ Click “Select a factor”. Select type of the factor Click “Select a device” ⑥ ⑤ ④ Click “Apply”. Select a detail item Select the device from the list. ⑦...
  • Page 88 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Logic control (1) Editing input factor Item Comparison operator Standard value (2) Editing output factor ③ ② ④ ⑤ ① ⑥ ⑦ ① ② ③ Click “Select a factor”. Click “Select a device”. Select the device from the list.
  • Page 89 (3) Control example – Setting Ex) Set the ERV to turn off together when the indoor unit turns off ❶ ❷ ❸ Create input condition : Click [Select a factor] from the ‘Input’ window.
  • Page 90 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Logic control (3) Control example – Setting ❹ Click [Select a device], then [Device selection] window will pop up. Select a indoor unit to apply the new control logic. ❺ Create input condition : When the device is selected, click [Power] and click [Apply].
  • Page 91 ❼ Create output : From the output window, select the device to apply the control when input condition is satisfied. Click [Apply] when selection is completed. ❽ Create output : Select “Power” as a factor of the selected device and click [Apply]. ❾...
  • Page 92 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Logic control (4) Control example – Control logic Ex) Control logic 1 : Turn on 4 indoor units when outdoor temperature is 30°C or higher. Control logic 2 : Turn off 4 indoor units when outdoor temperature is 26°C. Control logic 1 ❶...
  • Page 93 Register control logic ➊ ➋ Control logic applied...
  • Page 94 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Power distribution System power consumption includes: 1. Main power - 2. Fan power 3. Stand-by power (1) DMS2 power distribution theory Operation information 1. Outdoor/Indoor unit operation 2. Indoor unit fan operation 3.
  • Page 95 (2) Main capacity (3) Fan capacity (4) Stand-by capacity (5) What if the room temperature begins to reach the set temperature? (6) Capacity accumulation and power distribution (7) Undesirable situation protection (8) Not equal stand-by power distribution (In case all the indoor units are stopped)
  • Page 96 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Power distribution Power distribution equation When configuring the DMS2 and the whole system, mapping of watt-hour meters for indoor/outdoor units must be precisely assigned for correct power distribution.
  • Page 97 Example...
  • Page 98 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Power distribution Installation example (Allowed) Mapping watt-hour meters to indoor/outdoor units Note...
  • Page 99 Installation example (Not allowed) All indoor units in one outdoor unit must have the same power source.
  • Page 100 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Power distribution (10) Setting the inspection section (11) Setting the power distribution environment...
  • Page 101 Example of watt hour meter installation ❶ Installing watt-hour meter to outdoor/ indoor unit Address 0 A/ B 1 phase power F1/F2 F1/F2 3 phase power...
  • Page 102 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Power distribution Example of watt hour meter installation ❷ Installing 1 watt-hour meter to all indoor units Address 0 1 phase power F1/F2 F1/F2 3 phase power...
  • Page 103 Example of watt hour meter installation ❸ Using CT watt-hour meter to and outdoor unit R S T N Address 0 R1/R2 3 phase 4 wire voltage 1 phase power F1/F2 F1/F2 3 phase power Note...
  • Page 104 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Power distribution Checking the watt-hour meter connection...
  • Page 105 Setting virtual watt-hour meter Maximum 128 virtual channel can be used. Address of the virtual channel will be displayed as following. (24~31).(1~16) Note...
  • Page 106 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Power distribution Caution...
  • Page 107 User authorization management Admin (Administrator) : Manager : Regular user : Editing user authorization...
  • Page 108 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function User management You can add or delete the user who access DMS2 through web. Authorization of the added user can be set from [Admin], [Manager], [Regular user].
  • Page 109 Zone management Zone edit Initial setting Zone edit : Add, delete zone Change name Move indoor unit...
  • Page 110 Control Systems Integrated management systems 1. DMS2 MIM-D00AN 6) Function Setting the user authorization Authorization to control and monitor a zone of indoor units can be assigned according to User ID ❶ Select the zone and select a user ID who can access the zone. ❷...
  • Page 111: Features

    2. S-NET3 MST-P3P 1) Features PC program designed to manage system air conditioners in a large site. 2) PC specifications Item Model Details Note Model Number of connection 3) System connection...
  • Page 112 Control Systems Integrated management systems 2. S-NET3 MST-P3P 4) Function (1) S-NET3 function description Control & Monitoring Schedule Usage time and power Statistics and analysis System management...
  • Page 113: Detail Function Description

    (2) User functions User Administrator Installer 5) Detail function description (1) S-NET3 display Log-in...
  • Page 114 Control Systems Integrated management systems 2. S-NET3 MST-P3P 5) Detail function description (1) S-NET3 display Control and monitoring Installation structure window Selecting management structure Selecting installation structure When DMS2 & OnOff controller are selected.
  • Page 115 Installation structure window When outdoor unit is selected When indoor unit is selected...
  • Page 116 Control Systems Integrated management systems 2. S-NET3 MST-P3P 5) Detail function description (1) S-NET3 display Installation structure window When DI is selected When DO is selected...
  • Page 117 Control Deselect device Selecting indoor unit and ERV together Selecting indoor unit Selecting ERV...
  • Page 118 Control Systems Integrated management systems 2. S-NET3 MST-P3P 5) Detail function description (1) S-NET3 display Schedule control ❶ Schedule setting The 1st step (select a schedule mode) The 2nd step (select the indoor units to apply a schedule to)
  • Page 119 Schedule control The 3rd step (schedule operation setting) The 4th step (Schedule period and exception date setting) Schedule setting completion...
  • Page 120 Control Systems Integrated management systems 2. S-NET3 MST-P3P 5) Detail function description (1) S-NET3 display Schedule control ❷ Schedule modification Usage time and power consumption ❶ Usage time and power ❷ Power consumption report...
  • Page 121 Usage time and power consumption ❸ Power management structure editing ❹ Power section setting...
  • Page 122 Control Systems Integrated management systems 2. S-NET3 MST-P3P 5) Detail function description (1) S-NET3 display Statistics and analysis ❶ Indoor unit status ❷ Power consumption of indoor units...
  • Page 123 System management ❶ Environment setting ❷ DMS2 setting Note...
  • Page 124 Control Systems Integrated management systems 2. S-NET3 MST-P3P 5) Detail function description (1) S-NET3 display System management ❸ View event log ❹ Information update of the installed device...
  • Page 125 System management ❺ DMS2 backup and restoration ❻ S-NET3 backup and restoration...
  • Page 126 Control Systems Integrated management systems 2. S-NET3 MST-P3P 5) Detail function description (2) S-NET3 log information Contents E9000 E9001 E9002 E9010 E9011 E9012 E9100 E9150 E9151 E9200 E9250 E9300 E9400 E9401 E9999 I101 I102 I103 I104 I105 I201 I202 I301 I801 I802 I803...
  • Page 127 IV . Power distribution system...
  • Page 128: Features

    Control Systems Power distribution system 1. Electricity meter interface module MIM-B16N 1) Features (Unit : mm) 64.80 Front view Side view Input : 100~240V AC, 50/60Hz, 1.0A (max. 8 meters) Power supply (adapter) Output : 12V DC, 3.0A Operating temperature range -10ºC ~ 50ºC Operating humidity range 10%RH~90%RH...
  • Page 129: Connectors

    3) Connectors ① ② ③ ④ ⑤ Description Name 8 terminals are allocated to interface pulse-type electricity meters. Each terminal is seen ① Pulse input terminals with a dedicated address on DMS2. ② Power input ③ Reset button ④ COM1 Connection terminal for RS485 communication with DMS2.
  • Page 130: Specifications On Electricity Meter

    Control Systems Power distribution system 1. Electricity meter interface module MIM-B16N 5) Specifications on electricity meter Current flow on output : Current-sinking Pulse rate : /pulse Pulse width : Time interval between pulses : min. 3ms Allowable current sinking : min. 15mA Withstanding voltage : min.
  • Page 131: Installation

    6) Installation MIM-B16N must not be installed in a way that power to MIM-B16N is off when one of the over-current circuit breakers is switched off. Power supply to MIM-B16N must be off only when all the power supplies to refrigerant systems whose power consumptions are monitored by the MIM-B16N are cut off.
  • Page 132: Wiring

    Control Systems Power distribution system 1. Electricity meter interface module MIM-B16N 7) Wiring Wiring to electricity meter Attention must be paid to make polarized connection between an electricity meter and MIM-B16N with correct specifications on wires. MIM-B16N Typical interface circuitry Cable : VCTF or equivalent Length :...
  • Page 133: Address Assignment

    8) Address assignment Each of the electricity meters is assigned with the dedicated address depending on MIM-B16N address setting and the position of the pulse input terminals. CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 Electricity meter address assignment table Pulse input terminal 8~15 Not recognized...
  • Page 134 Control Systems Power distribution system 1. Electricity meter interface module MIM-B16N 9) MIM-B16N menu structure Main menu Sub menu Description LCD window. SW2 setting 1.Monitoring 1.1 Address … … 1.1 Address 58 30 FF Address Fixed Option switch setting to ON is displayed with the position number at the corresponding positions while setting to OFF is shown with the mark ‘X’.
  • Page 135 Main menu Sub menu Description When pulse input is detected during the test period, the channel numbers are displayed. Otherwise, the character ‘X’ is displayed on the corresponding channel position. Make a loopback connection between COM1 and COM2 to check if the DMS2 communication channel is working or not.
  • Page 136: Setting Parameters On Dms2 (Mim-D00An )

    Control Systems Power distribution system 1. Electricity meter interface module MIM-B16N 10) Setting parameters on DMS2 (MIM-D00AN) The following parameters for MIM-B16N can be also set and monitored on DMS2 (MIM-D00AN) ❋ DMS2 setting for MIM-B16N parameters 11) Error code Error code Description E613...
  • Page 137: External Control System

    External control systems External contact interface module ..Multi tenant function controller (MTFC). . .
  • Page 138: Features

    Control Systems External control systems 1. External contact interface module MIM-B14 1) Features (Unit : mm) Interlock DVM air-conditioner with external controller 2) Description of parts Contact Input/Output Operation rating ④ ① Error state Normal:Close, Error:Open ⑤ Indoor unit Thermo On/Off [Output signal] or Operation State output ②...
  • Page 139: Control

    4) Control iming diagram for external contact control Ex1) Note IDU stands for Indoor Unit. No prioritized operation between the R/C and the external contact I/M. Ex2) Note IDU stands for Indoor Unit. After power reset, indoor unit operates as previous state. (IDU has power recovery function)
  • Page 140 Control Systems External control systems 1. External contact interface module MIM-B14 4) Control Ex3) Note IDU stands for Indoor Unit. After power reset, if IDU is turn ON by external contact, it starts as Auto mode, 24ºC, Auto fan speed. Ex4) Note IDU stands for Indoor Unit.
  • Page 141 Operation input It is possible to set the method of indoor unit control by external contact signal. Method 1. Turn On/Off the indoor units by external contact signal Method 2. Set standby/Turn Off the indoor unit by external contact signal Method 3.
  • Page 142: Features

    Control Systems External control systems 2. Multi tenant function controller (MTFC) MCM-C210N 1) Features (Unit: mm) Multi tenant function controller is an auxiliary power supply device which allows indoor unit to turn off (close EEV) normally and maintain communication when main power supply is cut. It is used in site such as hotel where individual power is supplied to the indoor unit be purchased separately at the installation site.
  • Page 143: Connection Diagram

    4) Connection diagram ELCB ELCB ELCB ELCB ELCB AC single phase AC single phase AC single phase AC single phase AC single phase power power power power power ELCB AC 24 V transformer MTFC MTFC MTFC MTFC DC 5V DC 5V DC 5V DC 5V DC 12V...
  • Page 144 Control Systems External control system 2. Multi tenant function controller MCM-C210N 6) Main fucntion Multi tenant function controller operation When AC power (that is supplied to indoor unit) is cut-off, it supplies auxiliary power (DC 12 V, DC 5 V) to the indoor unit. When AC power (that is supplied to indoor unit) is supplied normally, it cuts-off the auxiliary power (DC 12 V, DC 5 V) to the indoor unit.
  • Page 145 Building management systems DMS L-net (Lonworks GW) ... DMS B-net (BACnet GW)... . .
  • Page 146: Mim-B18N

    Control Systems Building management system 1. DMS L-net (Lonworks GW) MIM-B18N 1) Features (Unit : mm) DMS-Lnet For LonWork protocol system. Support DMS2 control function at the same time. 2) Product specification Source DC Adaptor Power Input 100~240VAC (±10%), 50/60Hz supply Output 12V 3A...
  • Page 147: Description Of Parts

    Compatible product Outdoor unit Controller Conventional communication outdoor unit requires compatible interface module (MIM-N01) to establish connection MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected. To connect ERV, MIM-N10 interface module is required. PIM connection is different depending on software version. - Before 2.6.0.3 : MIM-B16 only - 2.6.0.3 : MIM-B16N only - After 2.6.1.
  • Page 148 Control Systems Building management system 1. DMS L-net (Lonworks GW) MIM-B18N 3) Description of parts ottom DI terminal 1 DI terminal 2 DO terminal 3 DO terminal 4 Lon terminal RS485 Communication terminal Serial terminal Ethernet terminal Reset button SD card socket Cable tie groove Name Description...
  • Page 149: Connection Diagram

    4) Connection diagram MIM-B16(PIM) should be connected separately with outdoor units or controllers. MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2. LonWorks communication BMS DMS-Lnet Samsung RS485 communication For power distribution OnOff LonWorks GW controller...
  • Page 150 Control Systems Building management system 1. DMS L-net (Lonworks GW) MIM-B18N 5) Wiring onnecting with outdoor unit LonWorks GW Outdoor unit Outdoor unit Outdoor unit Outdoor unit Maximum 16 Outdoor unit connections Outdoor unit Outdoor unit Outdoor unit's address is defined automatically. The address can be changed manually also.
  • Page 151 onnecting with outdoor unit and OnOff controller LonWorks GW Maximum 16 outdoor units Outdoor unit Outdoor unit Outdoor unit iring distance DMS-Lnet ⓐ ⓑ ⓒ ⓓ Network radius ⓔ Distance between LonWorks GW and OnOff controller/outdoor unit ⓒ ⓓ ⓔ 1000m Distance between LonWorks GW and upper level controller ⓐ...
  • Page 152: Commission

    6) Commission for more than 3 seconds. the front panel will be lit up for a second. 7) Standard program identifier (SPID) Manufacturers : Samsung Electronics Co., Ltd. MID: 191 Usage (Device Subclass) : Utility {11} Object Types Description SFPT Name SCC –...
  • Page 153: Network Variable

    9) Network variable (1) Indoor unit/ ERV/ AHU kit object Name Type Description nviONOff SNVT_switch ON/OFF command NviApplicMode SNVT_hvac_mode Setting operating mode nviSetpoint SNVT_temp_p Setting desire temperature nviFanStatus SNVT_switch Setting fan speed nviERVMode SNVT_count Setting ERV operation mode nviFilterReset SNVT_switch Filter reset command nviUserLockout SNVT_switch...
  • Page 154: Network Parameter Chart

    Control Systems Building management system 1. DMS L-net (Lonworks GW) MIM-B18N 10) Network parameter chart (1) Indoor unit/ ERV/ AHU kit object SSACIndoor[nn](objectid=1-128) nvoSpaceTemp SNVT_temp_p nviOnOff SNVT_switch nvoApplicMode SNVT_hvac_mode nviApplicMode SNVT_hvac_mode nvoSetPoint SNVT_temp_p nviSetPoint SNVT_temp_p nvoOnOff SNVT_switch nviFanStatus SNVT_switch nvoFanStatus SNVT_switch nviERVMode SNVT_count nvoERVMode SNVT_count nviFilterReset SNVT_switch...
  • Page 155 11) Network variable list Supported NV (Network Variable) is different depending on the connected devices. NV Name Description Indoor AHU Kit nviOnOff ON/OFF command nviApplicMode Setting operating mode nviSetpoint Setting desirable temperature nviFanStatus Setting fan swing and speed nviERVMode Setting ERV operation mode nviFilterReset Filter reset command nviUserLockout...
  • Page 156: Detail Description Of Network Variable

    Control Systems Building management system 1. DMS L-net (Lonworks GW) MIM-B18N 12) Detail description of network variable (1) Indoor unit/ ERV/ AHU kit object 1-1. nvoSpaceTemp(11) 1-5. nvoFanStatus(15), nviFanStatus(4) Description Fan Speed and direction Description Indoor temperature SNVT_switch: Unsigned/signed Short SNVT_temp_p: Signed Long, 2 bytes SNVT Type SNVT Type...
  • Page 157 1-8. nvoDeviceAlarm(18) 1-13. nvoEnergyCon(24) 1. Remote control restriction status Electric consumption value after Description 2. Filter alert status baselin Description 3. Thermo On/Off status SNVT_elec_kwh_I: Signed Quad, SNVT Type 4. Error alert Status 4bytes SNVT_state: 16 Unsigned Bitfields SNVT Type Value and operation Byte Bit9 Bit8 Operation Remark Unlock...
  • Page 158 Control Systems Building management system 1. DMS L-net (Lonworks GW) MIM-B18N 12) Detail description of network variable (1) Indoor unit/ ERV/ AHU kit object 2-17. Expansion of nvoDevListDesc desription character value Alphabet or digit Alphabet or digit Alphabet or digit Model information Alphabet or digit Alphabet or digit...
  • Page 159 (2) DMS System object 2-1. nvoDigitalOut(3), nviDigitalOut(1) Description Digital output status on DMS SNVT_switch: Unsigned/singed Short SNVT Type Value State Value and operation 2-2. nvoDigitalIn(4) Description Digital Input status on DMS SNVT_switch: Unsigned/singed Short SNVT Type Value State Value and operation 2-3.
  • Page 160: Features

    Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 1) Features DMS-Bnet (Unit : mm) 2) Product specification Source DC Adaptor Power Input 100~240VAC (±10%), 50/60Hz supply Output 12V 3A Operating temperature -10ºC ~ 50º C range Operating humidity range 10%RH ~ 90%RH Communication Lower layer : RS485 x 5...
  • Page 161: Description Of Parts

    Compatible product Outdoor unit Controller Conventional communication outdoor unit requires compatible interface module (MIM-N01) to establish connection MIM-B13D, MIM-B13E, MIM-B04A Interface modules cannot be connected. To connect ERV, MIM-N10 interface module is required. PIM connection is different depending on software version. - Before 2.6.0.3 : MIM-B16 only - 2.6.0.3 : MIM-B16N only - After 2.6.1.
  • Page 162 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 3) Description of parts (3) Bottom DI terminal 1 DI terminal 2 DO terminal 3 DO terminal 4 RS485 Communication terminal Serial terminal Ethernet terminal Reset button SD card socket Cable tie groove Name Description...
  • Page 163: Connection Diagram

    4) Connection diagram MIM-B16(PIM) should be connected separately with outdoor units or controllers. MIM-B16N(PIM) can be connected with outdoor units or controllers to same channel of DMS2. BACnet communication BMS Samsung RS485 communication For power distribution OnOff BACnet GW controller...
  • Page 164 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 5) Wiring onnecting with outdoor unit BACnet GW Outdoor unit Outdoor unit Outdoor unit Outdoor unit Maximum 16 Outdoor unit connections Outdoor unit Outdoor unit Outdoor unit's address is defined automatically. The address can be changed manually also.
  • Page 165 onnecting with outdoor unit and OnOff controller BACnet GW Maximum 16 outdoor units Outdoor unit Outdoor unit Outdoor unit iring distance DMS-Bnet ⓐ ⓑ ⓒ ⓓ Network radius ⓔ Distance between BACnet GW and OnOff controller/outdoor unit ⓒ ⓓ ⓔ 1000m Distance between BACnet GW and upper level controller ⓐ...
  • Page 166: Description Of Device Id

    Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 6) Description of device ID DNET – Range CPP – Range INDOOR – Range Item [Digit 2] [Digit 3] [Digit 2] OnOff Controller DMS DI/DO Interface Module (16 x 16) Indoor Unit, ERV AHU kit, EHS Gateway...
  • Page 167: Object List

    Only Only Enable Disable Conditional Remote controller limit status AC_Remocon_Limit_xx_xxxxxx Integrated error code of both AC_Error_Code_xx_xxxxxx Refer to Samsung integrated error code list indoor unit and outdoor unit SPI setting False True HumanSensor setting AC_MDS_xx_xxxxxx False True When the error occurred, send event to list of...
  • Page 168 Only Only Enable Disable Conditional Remote controller limit status AHU_Remocon_Limit_xx_xxxxxx Integrated error code of both AHU_Error_Code_xx_xxxxxx Refer to Samsung integrated error code list indoor unit and outdoor unit Discharge cooling set AHU_DisCoolSetTemp_xx_xxxxxx °C temperature Discharge heating set AHU_DisHeatSetTemp_xx_xxxxxx °C temperature...
  • Page 169 (3) ERV Single ERV unit has following point list. Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Text-5 Power On/Off operation Filter sign status ERV_FilterSign_xx_xxxxxx False True Filter sign reset ERV_FilterSign_Reset_xx_xxxxxx False True Operation mode status ERV_Operation_Mode_xx_xxxxxx...
  • Page 170 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 7) Object list (4) EHS Unit Status value Instance Object Object Object Name Inactive Active Number Type Text-1 Text-2 Text-3 Text-4 Room temperature EHS_RoomTemp_xx_xxxxxx °C Use when displayed temperature type is set Set temperature EHS_Temp_Set_xx_xxxxxx °C...
  • Page 171 Instance Object Object Object Name Status value Number Type SIM (PIM) error code SIM_Error_Code_xx_xx Refer to list of error code When the error occurred, send event SIM (PIM) Notify SIM_Notify_xx_xx to list of destination in the recipient_list. (Max : 8) (6) OnOff Controller Single OnOff Controller has following point list.
  • Page 172 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 7) Object list (8) BACnet Gateway BACnet Gateway has following point list. Instance Control and Object Object Name Status value Number Monitoring Type All device OFF ALL_OFF_xx Inactive : All devices Off DMS2 Status DMS2_Status_xx BACnet...
  • Page 173: Through Wireshark

    8) Checking BACnet communication through Wireshark (1) Who-is (I-Am) replied by i-am from the devices. (2) ReadPropertyMultiple ReadPropertyMultiple Request ReadPropertyMultiple Response Continuum CyberStation...
  • Page 174 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 8) Checking BACnet communication through Wireshark (3) ReadPropertyMultiple Request Response (4) WriteProperty ‘Low’) 2. Response - SimpleACK WriteProperty ReadPropertyMultiple...
  • Page 175 (5) Subscribe COV Request Response (6) COV Notification Notification Response...
  • Page 176: Standard Object Type

    Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 9) Standard object type Object Type Support Description [Indoor temperature], [The power value after the basic date], [The number of hours usage of an indoor unit after the basic date], Analog Input period], [Indoor unit error code], [AHU error code], [ERV error code], [AHU error code], [ERV error code], [Centralized controller error code], [Interface module error code],...
  • Page 177: Property Support Specification

    10) Property support specification (1) Device property Check Property identifier Property data Support DMS2 code Individual identifier SAMSUNG DVM CharaterString Gateway DEVICE During communication: System status BACnetDeviceStatus Error with DMS2: Samsung Electronics Vendor name CharacterString CO., Ltd. Vendor identifier Unsigned16...
  • Page 178 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 10) Property support specification (2) Analog Input Property Check Property identifier Property data Support DMS2 code CharaterString REAL R(1) AI_Instance_device Description CharacterString address Device type CharacterString Communication Status_Flags FAULT flag Status Flags BACnetStatusFlags True OUT_OF_SERVICE...
  • Page 179 (3) Analog output property Check Property identifier Property data Support DMS2 code CharaterString DEVICE REAL AI_Instance_device Description CharacterString address Device type CharacterString Communication Status_Flags FAULT flag Status Flags BACnetStatusFlags True OUT_OF_SERVICE TRUE General Error Event state BACnetEventState Status_Flags FAULT flag TRUE FAULT if Reliability is not NO_FALUT_DETECTED...
  • Page 180 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 10) Property support specification (4) Binary input property Check Property identifier Property data Support DMS2 code CharaterString AI_Instance_device Description CharacterString address Device type CharacterString Communication Status_Flags FAULT flag Status Flags BACnetStatusFlags True OUT_OF_SERVICE TRUE...
  • Page 181 (5) Binary output property Check Property identifier Property data Support DMS2 code CharaterString AI_Instance_device Description CharacterString address Device type CharacterString Communication Status_Flags FAULT flag Status Flags BACnetStatusFlags True OUT_OF_SERVICE TRUE Event state BACnetEventState General Error Status_Flags FAULT flag TRUE FAULT if Reliability is not NO_FALUT_DETECTED Reliability BACnetReliability...
  • Page 182 Control Systems Building management system 2. DMS B-net (BACnet GW) MIM-B17N 10) Property support specification (6) Multi-state input property Check Property identifier Property data Support DMS2 code CharaterString Unsigned R(1) M_Instance_device Description CharacterString address Device type CharacterString Communication Status_Flags FAULT flag Status Flags BACnetStatusFlags True OUT_OF_SERVICE...
  • Page 183 (7) Multi-state output property Check Property identifier Property data Support DMS2 code CharaterString Unsigned R(1) M_Instance_device Description CharacterString address Device type CharacterString Communication Status_Flags FAULT flag Status Flags BACnetStatusFlags True OUT_OF_SERVICE TRUE General Error Event state BACnetEventState Status_Flags FAULT flag TRUE FAULT if Reliability is not NO_FALUT_DETECTED...
  • Page 184 DVM CONTROL SYSTEMS...
  • Page 185 VII. Test run tool for system air contioner installation S-checker......S converter ......
  • Page 186: Features

    Test run tool for system air conditioner installation 1. S-Checker MIM-C10N 1) Features Execute test run for Samsung system air conditioner and inspects the parts (EEV, Sensor). It can be linked with mobile application to allow saving and monitoring data of the test run.
  • Page 187: Description Of Parts

    3) Description of parts ⑬ ⑯ ⑭ ⑮ ⑧ ⑨ ⑦ ⑩ ① Live Wi-Fi Error ⑰ ② ⑪ ③ ④ ⑱ ⑤ ⑫ ⑲ ⑥ DC JACK DC 12 V RS-485 ⑳ Description Name ① Reset button Use to reset S-checker ②...
  • Page 188: Connection Diagram

    Control Systems Test run tool for system air conditioner installation 1. S-Checker MIM-C10N 4) Connection diagram F1/F2 Outdoor unit (New communication) SD Card S-checker micro SD Indoor unit Indoor unit USB cable 5) Connecting Connecting with outdoor unit Outdoor unit F1 F2 R1 R2 S-checker...
  • Page 189 Connecting with mobile device F1/F2 Outdoor unit (New communication) S-checker Indoor unit Indoor unit Method 1- Search for S-Checker Method 2- Scan from mobile application...
  • Page 190: Main Function

    Control Systems Test run tool for system air conditioner installation 1. S-Checker MIM-C10N 6) Main function Test run report Test run report menu will inspect the system in real time and notify the result. Section Function During outdoor unit test run, test run Inspection step for prgress will be displayed in the test run...
  • Page 191 Install monitoring It displays the installation information of the outdoor unit and indoor unit. Install monitor: Outdoor unit Install monitor: Indoor unit Checking the status of device to the terminal on the S-checker and check the status of the device. Type of sensor Displayed contents Resistence value, displays...
  • Page 192 Control Systems Test run tool for system air conditioner installation 1. S-Checker MIM-C10N 6) Main function Checking the communication Through Comm. Check menu, communication status between indoor/outdoor unit can be checked. Indoor unit can be connected to S-checker alone without outdoor unit, to check the communication status of indoor unit. Setting the indoor unit option You can check the option code of indoor unit from the S-checker.
  • Page 193 Other functions A/C S/W Upgrade: Firmware for indoor and outdoor unit of system air conditioner can be upgraded. Unit control: This function restricts general operation if auto trial operation is incompleted. Refrigerant check: This is a detect function according to piping option which calculates the amount of refrigerant to see if it's adequate.
  • Page 194: Features

    Control Systems Test run tool for system air conditioner installation 2. S-Converter MIM-C02N 1) Features Main purpose for use - To coonect with test run program [Test run program] · S-NET Pro : Conventional communication · S-NET Pro 2 : New communication (Unit:mm) 28.00 66.50...
  • Page 195: Description Of Parts

    3) Description of parts ③ ⑤ ② ④ ① ⑨ ⑩ ⑦ ⑤ ⑥ ⑧ Description Name ① Display power status 485 communication / 2 line ② Displays communication status when outdoor uint 2 line remote controller is connected communication LED ③...
  • Page 196: Connection

    Control Systems Test run tool for system air conditioner installation 2. S-Converter MIM-C02N 5) Connecting Connecting with outdoor unit F1 F2 R1 R2 Connecting with PC 6) Display (1) POWER LED When connected to Conventional communication outdoor unit - LED blinks When connected to new communication outdoor unit - LED is on (2) 232 LED LED blinks every time control signal is transmitted from the Test run program...
  • Page 197 MEMO...

Table of Contents