Specification 2-1. Table of Specifications 2-1-1. Cassette Type Specifications 2-1-2. Duct Type Specifications 2-2. Dimensions 2-2-1. Cassette Type Indoor Unit 2-2-2. Cassette Type Outdoor Unit 2-2-3. Duct Type Indoor Unit 2-2-4. Duct Type Outdoor Unit...
Page 13
G ICH1800E/ICH2400E/CH18ZA/CH24ZA/CH18CA/CH24CA) Unit : mm Liquid refrigerant port Water Supply Intake Gas refrigerant port Drain tube outlet Fixing bracket 950 (Dimensions of Front Panel) 880 (Cutting Dimensions of Ceiling) 766 (Space of Suspension Bolts) 840 (Outer Dimensions) 12 | SAMSUNG...
Page 14
G ICH3600G/ICH4400G/CH36ZA/CH44ZA/CH36CA/CH44CA) Unit : mm Liquid refrigerant port Water Supply Intake Gas refrigerant port Drain tube outlet Fixing bracket 950 (Dimensions of Front Panel) 880 (Cutting Dimensions of Ceiling) 766 (Space of Suspension Bolts) 840 (Outer Dimensions) SAMSUNG | 13...
Page 15
SPECIFICATION Dimensions (Cont.) Cassette Type √√ Outdoor Unit G UBH1800E/CH18ZAX/CH18CAX Unit : mm (Front View) (Rear View) G UBH2400E/CH24ZAX/CH24CAX Unit : mm (Front View) (Rear View) 14 | SAMSUNG...
Page 16
SPECIFICATION Dimensions (Cont.) G UCH3600G/CH36ZAX/UCH4400G/CH44ZAX/CH36CAX/CH44CAX) Unit : mm Input bolt fixing dimension 840mm 415mm SAMSUNG | 15...
Page 17
SPECIFICATION Dimensions (Cont.) Duct Type √√ Indoor Unit G IDH1800E/2400E/3200E DH18ZA1(A2)/DH24ZA1(A2)/DH32ZA1(A2) Unit : mm 16 | SAMSUNG...
Page 18
1023 1042(Space of suspension bolts) 936 x 321(Dimension of outlet duct flange) Inspection area 1200mm Pipe connection port (Liquid pipe:ø9.52mm, Gas pipe:ø19.05mm) Drain pipe connection port (Out diameter:ø27.2mm) 936 x 321(Dimension of inlet duct flange) 1110(Outer Dimensions) SAMSUNG | 17...
Page 19
SPECIFICATION Dimensions (Cont.) Duct Type √√ Outdoor Unit G UBH1800E/DH18ZAX Unit : mm (Front View) (Rear View) G UBH2400E/DH24ZAX Unit : mm (Front View) (Rear View) 18 | SAMSUNG...
Page 20
SPECIFICATION Dimensions (Cont.) G UDH3200E/DH32ZAX Unit : mm (Front View) (Rear View) G UDH4400G/DH44ZAX Unit : mm SAMSUNG | 19...
Installation 3-1. Operation of the Remote Controller 3-2. Control of the Remote Controller 3-3. Centralized Controller 3-4. Drain Hose Installation 3-5. Air-Purge Procedure 3-6. Refrigerant Refill Procedure 3-7. “Pump down” procedure 3-8. Performing Leak Tests 3-9. Installation the Front Panel 3-10.
Page 24
• The wind mode to rotate in the order of wind select button, Breeze → Weak → Strong → Fan Speed Wind auto → Breeze. • The blades are moving between up and down. Flow Direction SAMSUNG | 23...
Page 25
2. At the state of simultaneous pressing of On Timer key and Off Timer key, insert the batteries in the wireless remote controller. 3. When the wireless remote controller is on the TEST MODE, press On/Off key to make the SET for the Test operation. 24 | SAMSUNG...
Indoor unit ↔ wired remote controller Operation LED and reservation communication defect LED alternating flickering (1Hz period) Abnormal on outdoor pipe temperature sensor Restored when outdoor pipe Filter LED flickering (1Hz period) (4.9[V] and higher, 0.5[V] and lower temperature sensor is normal SAMSUNG | 25...
Page 27
Filter Reset pressing the key after cleaning the filter resets the filter sign. • The wind mode to rotate in the order of wind select button, Breeze → Weak → Strong → Fan Speed → Wind auto Breeze. 26 | SAMSUNG...
Page 28
2. At the state of simultaneous pressing of On Timer key and Off Timer key, insert the batteries in the wireless remote controller. tion. 3. When the wireless remote controller is on the TEST MODE, press On/Off key to make the SET for the Test opera SAMSUNG | 27...
Page 29
Indoor unit ↔ wired remote controller Operation LED and reservation communication defect LED alternating flickering (1Hz period) Filter LED flickering (1Hz period) Restored when outdoor pipe Abnormal on outdoor pipe temperature sensor temperature sensor is normal (4.9[V] and higher, 0.5[V] and lower 28 | SAMSUNG...
Page 30
Indoor unit control Group control Indoor unit 1 chamber control Basic specification Fixed to OFF Able to operate of wired Disable to operate the Combined use of remote controller wireless remote controller wireless remote controller (SLAVE MODE) (MASTER MODE) SAMSUNG | 29...
Page 31
OPTION ITEM SW ON SW OFF DEFAULT VENTILATOR FAN Not installed Not installed DRAIN PUMP Installed Installed FLOAT SWITCH Installed Not installed FILTER CLEANING PERIOD 1000 Hr 2000 Hr INDOOR FAN MOTOR SPEED NORMAL SPEED HIGH SPEED 30 | SAMSUNG...
Page 32
Adjust the address of digital switch of indoor unit PCB in “A” chamber to “0”. Adjust the address of digital switch of indoor unit PCB in “B” chamber to “1”. In such a way, adjust the address of digital switch up to chamber “F”. SAMSUNG | 31...
Page 33
Put on the set power where the wired remote controller is installed. CAUTION • The option can be applied when the power is put again after resetting the option of wired remote controller. Be sure to keep the set power on/off after option setting. 32 | SAMSUNG...
Page 34
• The power of each chamber shall be used with the one having the same frequency during the group operation by use of wired remote controller. • The communicating line between the wired remote controller and indoor unit shall be of 100m at maximum. SAMSUNG | 33...
Page 35
If the SET is operating for 3 minutes through forced cooling operation, the SET is off after 2 minutes. ❑ The Error occurring in the TEST operation displays in the wired remote controller display window and is referred to the following table. 34 | SAMSUNG...
The connection by non-polarity method is easy. BUTTON NAME FUNCTION ALL 1 To put on all 16 chamber’s set. ALL 0 To put off all 16 chambers’ set. “01” ~ ”16” To put on/off set assigned with the number. SAMSUNG | 35...
+ centralized controller) System 3-3-3. Chambers Centralized Control System Connection Diagram "A" chamber "B" chamber "P" chamber "C" ~ "O" chamber Indoor unit Indoor unit Indoor unit Transmitter Transmitter Transmitter 01 02 01 02 01 02 01 02 36 | SAMSUNG...
Page 38
• Must fit tightly against body without any gap. When connecting the drain hose without the flexible hose, you Note should attach it to the drain tube outlet with adhesives and tapes to prevent water leaks. No gap ´ SAMSUNG | 37...
Page 39
Cover drain pump ˇ Confirm that the water flows out through the drain hose. You can check the drainage only when the air conditioner is Note turned on. ¨ Reassemble the cover drain pump and the screws. ´ 38 | SAMSUNG...
Page 40
The hose should not be allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other support as close to the unit as possible. Support pieces Ceiling SAMSUNG | 39...
Page 41
1 The base pan must be level with the ceiling. 2 Wrap the drain tube outlet on the right and left side of the indoor unit with an insulating materials. Drain pump Bottom of the drain pan ´ 40 | SAMSUNG...
Page 42
Half union the indoor unit. Liquid Suction(gas) pipe side pipe side Check the leakage on the connections. (A, B, C, D) Liquid Suction(gas) valve valve Outdoor Unit Check each valve for leakage. SAMSUNG | 41...
Stop operation of the air conditioner. Close the suction valve, disconnect the pressure gauge, and open the suction valve again. CAUTION • You must not add the R407C refrigerant without purging and vacuum procedure. Close the cap of each valve. 42 | SAMSUNG...
Page 44
Stop operation of the air conditioner. 7. Move the indoor and outdoor units to a new location. 8. Remove the mounting plate for the indoor unit and move it to a new location. Close the cap of each valve. SAMSUNG | 43...
Thus, when refrigerant leakage occurs in use, you must purge and make vacuous with a vacuum pump before adding the refrigerant. Then put the optimal quantity of refrigerant newly. In addition, the refrigerant must be added in liquid phase. 44 | SAMSUNG...
Page 46
- After removing the cushion Blocking that is installed in the air outlet of ACH3600G/4400G and CH36ZA/44ZA to install the air blocking. ˆ SAMSUNG | 45...
Indoor Fan Motor Speed Normal High speed CAUTION • If you do not adjust the switch when not installing the drain pump, "\9" error will occurs. If this happens, adjust the No.2 and No.3 switches to the "OFF" position. 46 | SAMSUNG...
Page 48
You must not adjust the switch 1 and 3. They should be in “OFF” position at all times. Switch Position Switch Option Item Group One indoor unit Number of air conditioner(s) controlled controlling controlling by the wired remote controller Using wireless remote controller Can be used Cannot be used SAMSUNG | 47...
Page 49
Rotary Digital Switch(DS01) - Before setting up the options, always make sure that you have switched off the main power. Note - After adjusting the options, you should supply the power. Otherwise, the options will not be applied. 48 | SAMSUNG...
Page 50
0). Ø Adjust the DIP switch No. 2 in the wired remote controller to “ON” position. You cannot install the centralized controller when the wired remote Note controller for a group has already been installed. SAMSUNG | 49...
Page 51
Adjust the rotary switch on the transmitter to the desired position referring to the table on page 48. You cannot install the centralized controller when the wired remote Note controller for a group has already been installed. Centralized Controller Unit A Unit B Unit C Centralized controller 50 | SAMSUNG...
Specification of Control Module 4-1. Anti-freezing Control 4-2. High Load Prevention Control(During Heating) 4-3. Dehumidifying Control 4-4. Cold Wind Prevention Control(During Heating) 4-5. Defrost Operation (During Heating)
Page 54
→ 2nd anti-freezing control release : Indoor heat exchanger temperature ≥ 6°C ¨ To operate based on the first detected one among the indoor heat exchanger temperature and outdoor heat exchanger temperature ˆ T1 Temperature specification : 35°C +(20°C – outdoor temperature)/2 T1 Temperature specification : (48°C≥T1≥35°C) SAMSUNG | 53...
Page 55
: COMPor ON, Outdoor fan ON, Indoor fan set wind. ➔ Anti-freezing OFF ˇ Applicable pattern of anti-freezing during the indoor pipe temperature sensor open/short (higher than 4.9V/lower than 0.5V) Release the room temperature anti-freezing when the indoor pipe temperature sensor is normal. 54 | SAMSUNG...
Page 56
→ breeze is set at wind volume → weak, weak → weak, strong → strong – → In model 23Z, strong wind at outdoor temperature ≥ 14˚C, the temperature of indoor heat exchanger ≤ 55˚C – Indoor fan control at the 2nd high temperature prevention : breeze SAMSUNG | 55...
Page 57
On/Off time as per the dehumidifying mode Operation cycle (minutes) COMPor and Indoor fan I-Mode II-Mode III-Mode IV-Mode ON time 6 minutes 5 minutes 3 minutes COMPor OFF time 4 minutes 5 minutes 6 minutes ´ COMPor and indoor fan operation cycle 56 | SAMSUNG...
Page 58
# It operates in COMPor=ON/OFF(MODE I, II, III, IV) from dehumidifying operation ”1st CYCLE” Indoor fan = breeze ˇ Wind control → based on the setting of remote controller. ¨ Default after reset → desired temperature (Ts)=24[˚C] SAMSUNG | 57...
Page 59
Indoor heat exchanger temperature = lower than 24˚C indoor fan speed off ˇ However, if COMPor is operating, the indoor fan is operating “breeze” not off even though the temperature of indoor exchanger is lower than 24˚C. 58 | SAMSUNG...
Page 60
4-5-5. When the mode is changed to cooling operation during defrost operation Œ After the completion of defrost, the cooling operation starts. ´ DISPLAY is changed from heating to cooling and the defrost lamp is on <Table →> SAMSUNG | 59...
Page 63
DIAGRAMS 5. Diagrams 5-1. Refrigerating Cycle Block Diagram Cassette Type G ACH1800E, ACH2400E, CH18ZA, CH24ZA *Allowable pipe length : Max. 30m Indoor Unit Outdoor Unit *Allowable drop distance : Max. 15m Check Valve 3-Way Valve Capallary Tube Capillary Check Tube...
Page 64
1m. : CH44CA When extending the pipe length by more than 5m, 45gr(40gr: Outdoor Unit is higher than Indoor Unit) of R407C refrigerant should be refilled per extension length of 1m. : CH36CA SAMSUNG | 63...
Page 65
High Pressure switch *Amount of refilling per extension length of 1m; When extending the pipe length by more than 5m, 40gr(50gr: Outdoor Unit is higher than Indoor Unit) of R-22 refrigerant should be refilled per extension length of 1m. 64 | SAMSUNG...
Page 66
*Allowable drop distance : Max. 25m 3-Way Valve Check Valve Liquid Side Capillary Tube Capillary Tube Heat Exchanger Heat (Condenser) Exchanger (Evaporator) Reservior Gas Side 3-Way Valve 4-Way Valve Cooling Heating Muffler Accumulator Gas leak check point Compressor High Pressure switch SAMSUNG | 65...
Page 67
DIAGRAMS Wiring Diagrams 5-2. Wiring Diagrams Cassette Type √√ Indoor Unit G 18K / 24K 66 | SAMSUNG...
Performance 6-1. Air velocity distribution (Cassette Type) 6-2. The distribution of temperature each space section 6-3. The Graph of Air-flow (Cassette Type) 6-4. Graph of Air-flow rate vs external static pressure 6-5. Cooling Capacity 6-6. Heating Capacity 6-7. Cooling Ampere 6-8.
Page 106
6-1. Air velocity distribution (Cassette Type) G 18K BTU (UNIT : m/s) 0.25 0.25 0.25 0.25 (UNIT : m/s) 0.25 0.25 CONDITION ❏ Fan speed : High ❏ Horizontal Blade : 30˚ Discharge ❏ Operation mode : Blowing ❏ Voltage : 240V SAMSUNG | 105...
Page 110
The distribution of temperature each space section 6-2. The distribution of temperature each space section Environment 4-Way Cassette Indoor Unit Outlet : 12˚C, 16CMM Indoor : 27˚C Room size : Window : 35˚C 5m x 5m x 2.5m SAMSUNG | 109...
Page 111
PERFORMANCE The Graph of Air-flow (Cassette Type) 6-3. The Graph of Air-flow (Cassette Type) 110 | SAMSUNG...
Page 112
HH : DIP Switch OFF position(High speed) The characteristic curves for ‘HH’, ‘H’, ‘Med’, and ‘Low’ fan H : At shipment(Normal speed) speed controller are shown. ˇ The nameplate values are shown based on the ‘H’ air flow. SAMSUNG | 111...
Page 113
PERFORMANCE Cooling Capacity 6-5. Cooling Capacity G ACH1800E / CH18ZA G ACH2400E / CH24ZA 112 | SAMSUNG...
Page 114
PERFORMANCE Cooling Capacity (Cont.) G ACH3600G / CH36ZA G ACH4400G / CH44ZA SAMSUNG | 113...
Page 115
PERFORMANCE Cooling Capacity (Cont.) G ADH1800E / DH18ZA1(A2) G ADH2400E / DH24ZA1(A2) 114 | SAMSUNG...
Trouble shooting & Error Mode 7-1. Trouble shooting by Outdoor unit Error code 7-2. Trouble shooting by Wireless Remote Controller receiver & Display unit 7-3. Trouble shooting by Wired Remote controller 7-4. Error Code & Check 7-5. Fault Diagnosis by Symptom...
Page 148
Float switch open error EC04 Communication error between indoor unit and outdoor unit EC05 Communication error between wired remote controller and indoor unit EC06 Outdoor unit pipe thermistor error EC07 Three phase power incorrect connecting error EC08 SAMSUNG | 147...
Page 149
✽ The asterisk mark “ * ” + “ERROR” CODE of wired remote controller stands for the set number. ex) ERROR CODE “39” is the FLOAT SWITCH OPEN ERROR of SET no.3. ✽ Indicators means wireless Remote controller Receiver & display. 148 | SAMSUNG...
Page 150
- Indoor unit pipe thermistor defect Is the indoor unit pipe thermistor installed at CN8? Install the indoor unit pipe thermistor at CN8 Is the voltage across thermistor 4.9V and higher Replace the indoor unit PCB or 0.5V lower? Replace the thermistor SAMSUNG | 149...
Page 151
Is the outdoor unit thermistor installed at CN41? Install the outdoor unit thermistor at CN41. Is the voltage across the thermistor 4.9V and Replace the outdoor unit PCB higher or 0.5V and lower? Replace the thermistor ✽ “*” stands for the indoor unit address. 150 | SAMSUNG...
Page 152
SW2 ON? SW3 ON? Replace pump? indoor unit Install float SW SW2 ON? Replace PCB SET SW2 OFF SET SW2 OFF SET SW3 OFF SET SW3 OFF Power RESET ✽ “*” stands for the indoor unit address. SAMSUNG | 151...
Page 153
The Micom of outdoor unit is operating normally, Is the LED of PCB flickering with 16Hz? check and replace the communication circuit of outdoor unit and indoor unit. Replace the PCB ✽ “*” stands for the indoor unit address. 152 | SAMSUNG...
Page 154
Is the jump wire inserted into CN20 of indoor unit PCB? Is the address of PCB digital switch Set address to "0" of indoor unit to "0"? Replace the indoor unit PCB Replace the wired remote controller ✽ “0” stands for the indoor unit address. SAMSUNG | 153...
Page 155
Is indoor pipe thermistor installed at CN41? Connect correctly and check. Is the voltage across the thermistor 4.9V and Replace the outdoor PCB higher or 0.5V and lower? Replace the thermistor ✽ “*” stands for the indoor unit address. 154 | SAMSUNG...
Page 156
IC correct Replace wire Replace IC that does not Take two connected lines to change the string of make round type signal L1, L2, L3 because of the reverse of power. SAMSUNG | 155...
Page 157
Mis-insertion of CN9? Wire shorted? LED direct/reverse direction check? LED direct/reverse direction check? Check pin no.1 of CN9 while pressing Replace the wireless receiving board SW91 : DC 0V? Replace after check of indoor unit main PCB 156 | SAMSUNG...
Page 158
R1, R2, unit PCB R3 of indoor unit terminal boards? Does the error code display? Connect correctly the R1, R2, R3 Error correction and recheck Check the main PCB of indoor unit and replace it. SAMSUNG | 157...
Page 159
Check IC06 and micom, are the pin 14 and 15 of indoor replace unit PCB IC06 low? Is the voltage across the indoor unit fan Replace PCB AC220 ~ 240V? Check the indoor unit fan motor and replace 158 | SAMSUNG...
Page 160
Are the pins 11 and 12 of IC07 of outdoor Check and replace unit PCB low when each wind control mode IC07 micom is operation? Is the voltage across the outdoor unit Replace PCB fan motor AC220~240V? Check outdoor unit fan motor and replace SAMSUNG | 159...
Page 161
Is the output of NO. 10 of IC05 of outdoor Check and replace unit low then the compressor is on? IC05 Is the voltage AC220V across the terminal Replace the magnet of outdoor unit when the compressor is on? replay Replace the compressor 160 | SAMSUNG...
Page 162
Are the voltage of pin no. 1 and 6 of indoor unit PCB DC 12V? Is the output of pin no. 2, 3, 4, and 5 of CN 12 and 13 of indoor unit PCB spherical? Replace up and down swing motor Replace indoor unit PCB SAMSUNG | 161...
Page 163
Is “HIGH” the No.11 pin output of IC06? micom Is DC12V the relay both voltage of RY72? Relace the RY72 Is AC220V~AC240V of the No.1, No3 pin Replace the indoor PCB. both voltage of CN5. Check the drain pump and replace. 162 | SAMSUNG...
Page 164
Put on and then reset the power indoor unit on? Normal ERROR CODE = “09” ERROR DISPLAY = FLICKERING Replace indoor unit PCB Is the level of micon pin no.55 “HIGH” Are no.2 and 3 of option switch of indoor unit on? SAMSUNG | 163...
Page 165
Is IC06 pin no. 10 “LOW”? Check and replace IC06 Is the voltage across RY77 normal? Check and replace RY77 Is the voltage of CN6 no.1 and 3 of Replace indoor unit PCB indoor unit AC220V~AC240V? Check and replace ventilator 164 | SAMSUNG...
Page 166
No trouble on F101, F102, F701? Replace fuse DC12V output? DC5V output? Check and replace IC02 Check and replace power No trouble on power transformer transformer AC output? Check and replace IC101 No trouble on the power system and finish the test SAMSUNG | 165...
Page 167
Replace fuse DC12V output? DC5V output? Check and replace IC02 Check and replace power No check on power transformer transformer AC? Check and replace IC01 No trouble on the outdoor unit power system and finish the test 166 | SAMSUNG...
Page 168
Is the LED1 on after centralized controller on and Replace the PCB of relay equipment off after centralized controller off? Is the LED2 of relay equipment PCB flickering with Replace the relay equipment PCB the consistent interval? Replace the PCB of centralized controller SAMSUNG | 167...