Step
1
2
3
delete space
4
5
Rev. 1
September 2010

Table 5 Battery replacement procedure

ATTENTION
Use only the following 3.6V lithium thionyl chloride (Li-SOCl2) batteries (non-rechargeable),
size D. No other batteries are approved for use in OWA 100 Adapter.
Xeno Energy XL-205F
Eagle Picher PT-2300H
Tadiran TL-5930/s
Loosen (4) M4 screws and remove the cover.
Remove the old battery from the battery holder. If needed, pry out the battery by using a
slotted screwdriver as a lever.
Install battery as follows to avoid snagging the battery terminal on the clip and damaging the
battery.
Align the new battery with the clips and angle the positive (+) end of the battery
into the positive (+) battery terminal clip. Using a thumb and forefinger pull the negative
terminal clip outward and push down on the battery until fully seated in both clips. Do not
apply excessive force when pushing the battery down.
Replace the cover and tighten the (4) M4 screws.
Dispose the used battery promptly per local regulations or the battery manufacturer's
recommendations. Keep away from children. Do not disassemble and do not dispose of in
fire.