Refrigeration Cycle - Sharp AH-N45DP2 Service Manual

Split system room air conditioners, indoor / outdoor units
Table of Contents

Advertisement

AH-N45DP2
AU-N45DP2
AH-N56DP2
AU-N56DP2
Cycle temperature and service port pressure
Based on 'ISO 5151 : 1994(E), condition T1' (at 220V refrigerant pipes length 7.5m)
Model
AH-N45DP2
NO. Condition
1
2
3
4
Service port pressure
ISO condition
Temperature (˚C)
Cooling
27
Dimension of Capillary tube
AH-N45DP2
O.D.
Capillary tube
ø 3.2

REFRIGERATION CYCLE

Indoor unit
Flare coupling
3-way
valve
Outdoor unit
Compressor
4
Accumulator
Figure R-1. Refrigeration Cycle for AH-N45DP2 / AH-N56DP2
AH-N56DP2
Cooling
Cooling
83˚C
81˚C
40˚C
37˚C
11˚C
11˚C
7˚C
4˚C
0.46MPa
0.46MPa
Indoor side
Relative humididity (%)
47
I.D.
L
ø 2.0
400
Evaporator
3
Flare coupling
2-way
valve
Capillary tube
Condenser
1
2
Temperature (˚C)
35
AH-N56DP2
O.D.
Capillary tube
ø 3.5
20
Outdoor side
Relative humididity (%)
40
I.D.
L
ø 2.2
800