Advertisement

CHAPTER 5: SETTINGS
Settings for
Transmission
ASDU
4
ASDU at T-3 (previous values) + ASDU at T-2 (previous values) + ASDU at T-1 (previous values) + ASDU at T0 (current values)
5.5.7.14 Control blocks
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  90–5 R-SV CB 1 CONFIGURATION
 90-5 R-SV CB 1
 CONFIGURATION
— The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client write, to
R-SV CB1 SVENA
start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is provided to the
client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that reflects the state of
the SvEna control where "1"= Enabled and "0"=Disabled. The figure shows the logic for setting the SvEna control bit.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
R-SV CB1 SVENA:
Off
R-SV CB1 CLIENT CTRL:
Off
R-SV CB1 SVENA DFLT:
Off
R-SV CB1 CONFREV:
1
R-SV CB1 PRIORITY:
4
R-SV CB1 CSCP CLASS:
Expedited Forwarding
R-SV CB1 VLAN ID:
0
R-SV CB1 APPID:
0
R-SV CB1 DEST IP:
224.0.0.0
R-SV CB1 SECURITY:
0
Figure 5-98: Logic for setting SvEna control bit
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1 to 4294967295
Range: 0 to 7
Range: None, Expedited Forwarding
Range: 0 to 4095
Range: 0 to 16383
Range: 0 to 255.255.255.255
Range: 0 to 2
SYSTEM SETUP
5
5-185