Serial Communication Connections - ABB REU 523 Technical Reference Manual

Combined overvoltage and undervoltage relay
Hide thumbs Also See for REU 523:
Table of Contents

Advertisement

1MRS 750942-MUM
4.2.2.
Combined Overvoltage and Undervoltage Relay
Technical Reference Manual
Table 4.2.1-3
Output contacts
Terminal
Function
X2.1-3
PO1, closing contact
X2.1-4
X2.1-5
PO2, closing contact
X2.1-6
X2.1-7
SO1, common
X2.1-8
SO1, NC
X2.1-9
SO1, NO
X2.1-10
SO2, common
X2.1-11
SO2, NC
X2.1-12
SO2, NO
Table 4.2.1-4
IRF contact
Terminal
Function
X2.1-13
Internal relay fault, common
X2.1-14
Closed; IRF, or U
X2.1-15
Closed; no IRF, and U
Table 4.2.1-5
Binary input
Terminal
Function
X2.1-17
Input+
X2.1-18
Input-

Serial communication connections

The REU 523 is interfaced with a fibre-optic bus by means of the bus connection
module RER 103 via the D9S-type connector X2 located on the rear panel of the
device. The terminals of the fibre-optic cables are connected to the counter terminals
Rx (Receiver) and Tx (Transmitter) of the bus connection module. The fibre-optic
cables are linked from one protection relay to another and to the substation level
communication unit, e.g. SRIO 1000M and the RER 125.
The optical PC-connection on the front panel of the relay is used to connect the relay
to a fibre-optic SPA bus via opto-cable 1MKC950001-1.
Table 4.2.2-1
RS-485 connector X2 for the RER 103
Terminal
Function
X.2.2-1
Data A (data signal +)
X.2.2-2
Data B (data signal -)
X.2.2-3
RTS A (request to send +)
X.2.2-4
RTS B (request to send -)
X.2.2-5
COL A (2.8 V on relay)
X.2.2-6
COL B (2.2 V on relay)
X.2.2-7
GND
X.2.2-8
NC
X.2.2-9
+5 Vdc, auxiliary voltage (max. 200 mA)
disconnected
aux
connected
aux
REU 523
49