The Installation Of Lndoor And Outdoor Unit - Model Rak-35Ppb/Rac-35Wpb - Hitachi RAC-25WPB Service Manual

Hide thumbs Also See for RAC-25WPB:
Table of Contents

Advertisement

Figure showing the installation of lndoor and Outdoor unit
MODEL RAK-35PP /RAC-35WP
above 50 mm when
installed on the
ceiling of balcony
above 100mm
above 300mm
B
B
Be sure to
completely
seal any gap
with putty.
above 200mm
above 50mm
above 50mm
give clearance
as wide as
possible
above
200mm
8
above
50mm
2,300 mm or more
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the insulator is
insufficient, please use commercial
products.)
The refrigerating machine oil is
easily affected by moisture. Use
caution to prevent water from
entering the cycle.
The difference in height between
the indoor and outdoor unit
should be kept below 10m.
The connecting pipe, no matter
big or small, should all be
insulated with insulation pipe and
then wrapped with vinyl tape.
(The insulator will deteriorate if
it is not wrapped with tape).
The connection of insulated drain
hose.
Inner diameter 16mm
Please use insulated drain hose for
the indoor piping (commercial
product)
above 50mm
Plug