The Others - Samsung AF55JV1MAEE Service Manual

Floor stand type air conditioner
Hide thumbs Also See for AF55JV1MAEE:
Table of Contents

Advertisement

4-3-16 The others

1. E465 : Compressor over load error
If a compressor is normal, check the assembly between Heatsink-Inverter PBA. If it is fine, change Inverter PBA.
2. E468 : Current sensor error
Check EEPROM data.
Check PCB operates properly.
3. E471 : Oudoor EEPROM error
Upload EEPROM on Outdoor unit Main PBA.
4. E474 : IPM(IGBT Module) or PFCM Temperature sensor Error
E500 : IPM is over heated
Check IPM is well assembled to heatsink
Check whether inlet port is clogged.
Change IPM if it is defective one
5. E554 : Gas leak error
Check refrigerant charge
Check Indoor EVA sensor
Check Service valve is open.
Check the pipes and wires correctly connected.
6. E556 : Capacity miss match between indoor and outdoor
Check the model name of indoor and outdoor unit and set option code on indoor unit again.
7. Outdoor overload protection control (at the stop of the compressor.) : E404
Check whether the fan and the motor operate normally.
Check the operation of EEV.
Check the temperature sensor of the indoor unit heat Exchanger.
Check the indoor unit inlet blocking.