Check Compressor Resistances - Bosch AHUW036A2 Service Manual

Split outdoor unit 230 v 1 n-/400 v 3 n-
Table of Contents

Advertisement

Check compressor resistances

3
Check compressor resistances
WARNING: Electric shock!
▶ Even if the ODU is disconnected from power supply,
it takes some time to discharge the remaining
electricity of the electrolytic capacitor. Before
conducting a service or repairing job, switch off the
main power supply and make sure that all LED on the
circuit boards are off.
To check the resistance of the compressor:
▶ Disconnect the compressor motor plug
▶ Measure the resistance between each coil and ground
▶ The resistance should be more than 2M (at 20 °C)
To check the resistance between the coils:
▶ Disconnect the compressor motor plug
▶ Measure the resistance between the coils
▶ The resistance should be equal
1
1
Fig. 32 Check compressor resistances
[1]
Compressor
[2]
Copper pipe
34
2
6 720 817 722-33.1I
Split ODU – 6 720 817 722 (2015/06)