7 PARAMETERS

Simple variable-speed operation can be performed with the inverter in the initial settings. Set the required parameters
according to the load and operating conditions. Use the operation panel to set or change a parameter.
7.1
Parameter list
REMARKS
 When the Ethernet board is removed, the parameters for Ethernet communication cannot be read or written.
  indicates simple mode parameters. (initially set to extended mode)
 The parameters surrounded by a black border in the table allow its setting to be changed during operation even if "0" (initial
value) is set in Pr. 77 Parameter write selection.
 Refer to the Ethernet Function Manual for details of the FR-E700-NE Ethernet communication parameters, and refer to Chapter
4 of the FR-E700 Instruction Manual (Applied) for details of the other parameters.
Parameter
Name
 0
Torque boost
 1
Maximum frequency
 2
Minimum frequency
 3
Base frequency
Multi-speed setting (high
 4
speed)
Multi-speed setting (middle
 5
speed)
Multi-speed setting (low
 6
speed)
 7
Acceleration time
 8
Deceleration time
 9
Electronic thermal O/L relay
DC injection brake operation
10
frequency
DC injection brake operation
11
time
DC injection brake operation
12
voltage
13
Starting frequency
14
Load pattern selection
15
Jog frequency
Jog acceleration/deceleration
16
time
17
MRS input selection
High speed maximum
18
frequency
19
Base frequency voltage
Acceleration/deceleration
20
reference frequency
Acceleration/deceleration time
21
increments
22
Stall prevention operation level 0 to 200%
Stall prevention operation level
23
compensation factor at double
speed
24
Multi-speed setting (speed 4)
25
Multi-speed setting (speed 5)
Setting
Initial
Parameter
Range
Value
6/4/3/2%
0 to 30%

0 to 120Hz
120Hz
0 to 120Hz
0Hz
0 to 400Hz
60Hz
0 to 400Hz
60Hz
0 to 400Hz
30Hz
0 to 400Hz
10Hz
0 to 3600/
5/10/15s
360s

0 to 3600/
5/10/15s
360s

Inverter
0 to 500A
rated
current
0 to 120Hz
3Hz
0 to 10s
0.5s
0 to 30%
6/4/2%

0 to 60Hz
0.5Hz
0 to 3
0
0 to 400Hz
5Hz
0 to 3600/
0.5s
360s
0, 2, 4
0
120 to 400Hz
120Hz
0 to 1000V,
9999
8888, 9999
1 to 400Hz
60Hz
0, 1
0
150%
0 to 200%,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
Name
26
Multi-speed setting (speed 6)
27
Multi-speed setting (speed 7)
Acceleration/deceleration
29
pattern selection
Regenerative function
30
selection
31
Frequency jump 1A
32
Frequency jump 1B
33
Frequency jump 2A
34
Frequency jump 2B
35
Frequency jump 3A
36
Frequency jump 3B
37
Speed display
RUN key rotation direction
40
selection
41
Up-to-frequency sensitivity
42
Output frequency detection
Output frequency detection for
43
reverse rotation
Second acceleration/
44
deceleration time
45
Second deceleration time
46
Second torque boost
47
Second V/F (base frequency)
Second stall prevention
48
operation current
Second electronic thermal O/L
51
relay
DU/PU main display data
52
selection
Parameter list
Setting
Initial
Range
Value
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0, 1, 2
0
0, 1, 2
0
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0 to 400Hz,
9999
9999
0, 0.01 to
0
9998
0, 1
0
0 to 100%
10%
0 to 400Hz
6Hz
0 to 400Hz,
9999
9999
0 to 3600/
5/10/15s
360s

0 to 3600/
9999
360s, 9999
0 to 30%,
9999
9999
0 to 400Hz,
9999
9999
0 to 200%,
9999
9999
0 to 500A,
9999
9999
0, 5, 7 to 12,
14, 20,
23 to 25,
0
52 to 57, 61,
62, 100
36
6
7

Hide quick links: