5.2 PRODUCT SETUP
c) TRIP AND ALARM LEDS
!
PATH: SETTINGS
PRODUCT SETUP
# TRIP & ALARM LEDS
#
The Trip and Alarm LEDs are on LED Panel 1. Each indicator can be programmed to become illuminated when the
selected FlexLogic™ operand is in the Logic 1 state.
d) USER-PROGRAMMABLE LED 1(48)
!
PATH: SETTINGS
PRODUCT SETUP
# USER-PROGRAMMABLE
# LED 1
There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-
nate when the selected FlexLogic™ operand is in the Logic 1 state.
LEDs 1 through 24 inclusive are on LED Panel 2; LEDs 25 through 48 inclusive are on LED Panel 3.
Refer to the LED Indicators section in Chapter 4 for the locations of these indexed LEDs. This menu selects the operands
5
to control these LEDs. Support for applying user-customized labels to these LEDs is provided. If the
"Self-Reset" (default setting), the LED illumination will track the state of the selected LED operand. If the
is 'Latched', the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a communi-
cations channel, or from any programmed operand, even if the LED operand state de-asserts.
Table 5–2: RECOMMENDED SETTINGS FOR LED PANEL 2 LABELS
SETTING
LED 1 Operand
LED 2 Operand
LED 3 Operand
LED 4 Operand
LED 5 Operand
LED 6 Operand
LED 7 Operand
LED 8 Operand
LED 9 Operand
LED 10 Operand
LED 11 Operand
LED 12 Operand
Refer to the Control of Setting Groups example in the Control Elements section of this chapter for group activation.
5-26
!"
USER-PROGRAMMABLE LEDS
TRIP LED INPUT:
Off
ALARM LED INPUT:
MESSAGE
Off
!"
USER-PROGRAMMABLE LEDS
LED 1 OPERAND:
Off
LED 1 TYPE:
MESSAGE
Self-Reset
PARAMETER
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Off
Off
BREAKER 1 OPEN
BREAKER 1 CLOSED
BREAKER 1 TROUBLE
Off
D60 Line Distance Relay
!"
TRIP & ALARM LEDS
Range: FlexLogic™ operand
Range: FlexLogic™ operand
!"
USER-PROGRAMMABLE LED 1(48)
Range: FlexLogic™ operand
Range: Self-Reset, Latched
SETTING
PARAMETER
LED 13 Operand
Off
LED 14 Operand
BREAKER 2 OPEN
LED 15 Operand
BREAKER 2 CLOSED
LED 16 Operand
BREAKER 2 TROUBLE
LED 17 Operand
SYNC 1 SYNC OP
LED 18 Operand
SYNC 2 SYNC OP
LED 19 Operand
Off
LED 20 Operand
Off
LED 21 Operand
AR ENABLED
LED 22 Operand
AR DISABLED
LED 23 Operand
AR RIP
LED 24 Operand
AR LO