Remote Inputs - GE G60 Instruction Manual

Generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

5 SETTINGS
Sixteen remote devices, numbered from 1 to 16, can be selected for setting purposes. A receiving relay must be pro-
grammed to capture messages from only those originating remote devices of interest. This setting is used to select specific
remote devices by entering (bottom row) the exact identification (ID) assigned to those devices.
The
REMOTE DEVICE 1(16) VLAN ID
they are not applicable to GSSE messages. The
remote device is sending the GOOSE message. The
cation identification in the GOOSE message. These settings should match the corresponding settings on the sending
device.
!"
PATH: SETTINGS
INPUTS/OUTPUTS
# REMOTE INPUT 1
#
MESSAGE
MESSAGE
MESSAGE
Remote Inputs which create FlexLogic™ operands at the receiving relay, are extracted from GSSE/GOOSE messages
originating in remote devices. The relay provides 32 remote inputs, each of which can be selected from a list consisting of
64 selections: DNA-1 through DNA-32 and UserSt-1 through UserSt-32. The function of DNA inputs is defined in the IEC
61850 specification and is presented in the IEC 61850 DNA Assignments table in the Remote Outputs section. The function
of UserSt inputs is defined by the user selection of the FlexLogic™ operand whose state is represented in the GSSE/
GOOSE message. A user must program a DNA point from the appropriate FlexLogic™ operand.
Remote Input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
selects the number (1 to 16) of the remote device which originates the required signal, as previously
REMOTE IN 1 DEVICE
assigned to the remote device via the setting
selects the specific bits of the GSSE/GOOSE message required.
The
REMOTE IN 1 DEFAULT STATE
the remote device sending the point is declared to be non-communicating. The following choices are available:
Setting
REMOTE IN 1 DEFAULT STATE
Setting
REMOTE IN 1 DEFAULT STATE
Setting
REMOTE IN 1 DEFAULT STATE
not known, such as after relay power-up but before the first communication exchange, the input will default to Logic 1.
When communication resumes, the input becomes fully operational.
Setting
REMOTE IN 1 DEFAULT STATE
not known, such as after relay power-up but before the first communication exchange, the input will default to Logic 0.
When communication resumes, the input becomes fully operational.
For additional information on GSSE/GOOOSE messaging, refer to the Remote Devices section in this chap-
ter.
NOTE
GE Multilin
and
REMOTE DEVICE 1(16) ETYPE APPID
REMOTE DEVICE 1(16) VLAN ID
REMOTE DEVICE 1(16) ETYPE APPID
!"
!

REMOTE INPUTS

REMOTE INPUT 1(32)
REMOTE IN
1 DEVICE:
Remote Device
1
REMOTE IN
1 BIT
PAIR: None
REMOTE IN
1 DEFAULT
STATE: Off
REMOTE IN
1
EVENTS: Disabled
REMOTE DEVICE NN ID
setting selects the logic state for this point if the local relay has just completed startup or
to "On" value defaults the input to Logic 1.
to "Off" value defaults the input to Logic 0.
to "Latest/On" freezes the input in case of lost communications. If the latest state is
to "Latest/Off" freezes the input in case of lost communications. If the latest state is
G60 Generator Management Relay
settings are only used with GOOSE messages;
setting identifies the virtual LAN on which the
setting identifies the Ethernet appli-
Range: 1 to 16 inclusive
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32
Range: On, Off, Latest/On, Latest/Off
Range: Disabled, Enabled
(see the Remote Devices section).
5.7 INPUTS/OUTPUTS
5.7.6 REMOTE INPUTS
REMOTE IN 1 BIT PAIR
5-171
5