Installation - Honeywell F58G Product Data

Commercial duct mounted electronic air cleaner
Hide thumbs Also See for F58G:
Table of Contents

Advertisement

AIR HANDLER DUCT
ELECTRONIC AIR CLEANER ARRAY
Fig. 4. Changing duct size gradually
to minimize turbulence.

INSTALLATION

When Installing This Product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi-
tion.
2. Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service techni-
cian.
4. After installation is complete, check out product opera-
tion as provided in these instructions.
WARNING
Electric Shock Hazard.
Can cause electrical shock or equipment damage.
Do not connect to power before installation is complete.
Unpacking Electronic Air Cleaner
The electronic air cleaner is shipped assembled. Check that
all components are included:
Galvanized steel cabinet with integral power supply.
Two electronic cells.
Pre-filter.
Two cell handles.
Literature package.
F58G COMMERCIAL DUCT MOUNTED ELECTRONIC AIR CLEANER1
20 DEGREE ANGLE PER
SIDE PER FITTING, 4 in.
PER LINEAR FOOT (1M
PER 3 LINEAR METERS).
M13458
5
Fastening Cabinet to Air Handler Duct Flange
Remove and set aside the pre-filter and electronic cells.
Assemble the array of air cleaner units in the required size
according to the Constructing F58G Array section.
Install a transition to the air handler duct if the opening is
different than the opening of the air cleaner array (see
Fig. 4).
Move the completed array into place against the air
handler duct flange.
Attach the air cleaner cabinets securely using no. 8 sheet
metal screws or rivets.
Attaching Cell Handles
The cell handle can be installed on either side of the cell:
1. Hold the handle while inserting the solid tab on the back
of the handle into the slot in the cell. Turn the handle 90
degrees clockwise to align the divided tab with the
square hole. See Fig. 5.
INSTALL HANDLE ON END OF CELL
CLOSEST TO ACCESS DOOR
Fig. 5. Installing cell handle.
2. Insert the divided tab into the square hole.
3. Fold up the wedge and insert it into the divided tab to
lock the handle in place. If necessary, press with a blunt
instrument like the end of a pliers.
Reassembling Air Cleaner
Insert the electronic cell with the contact board up and the
air flow arrow pointing downstream.
Tilt the cell toward you and insert the bottom of the cell first.
Rotate the top of the cell back into position under the
spring contacts.
If the cell does not seat properly, check the orientation of
the airflow arrow on the cell.
Assemble the pre-filter to the front of the unit by first
inserting the lower portion of the pre-filter into the slot at
the bottom of the cabinet.
Rotate the pre-filter back into position. When properly
installed, the actuator on the pre-filter is inserted into the
wiring tray of the air cleaner.
Rotate the latch to secure the pre-filter in place.
ROTATE 90
DEGREES
FOLD TAB
TO LOCK
HANDLE
IN PLACE
M6047A
68-0233

Hide quick links:

Advertisement

Table of Contents
loading