HEATING CAPACITY DATA
ARUM192BTE5 / ARUM192DTE5
192,000 Btu/h 208-230V / 460V Outdoor Units
Outdoor air
Combination
temp.
(%)
TC
°F DB °F WB
MBh
-12.6
-13.0
146.8
-7.0
-7.6
159.9
-4.0
-4.4
167.8
0.0
-0.4
177.3
5.0
4.5
189.0
10.0
9.0
202.1
15.0
14.0
213.3
20.0
19.0
230.5
100%
25.0
23.0
245.3
30.0
28.0
257.0
35.0
32.0
261.2
40.0
36.0
261.2
45.0
41.0
261.2
47.0
43.0
261.2
50.0
46.0
261.2
55.0
51.0
261.2
60.0
56.0
261.2
-12.6
-13.0
146.2
-7.0
-7.6
159.3
-4.0
-4.4
167.1
0.0
-0.4
177.3
5.0
4.5
189.0
10.0
9.0
202.1
15.0
14.0
213.3
20.0
19.0
236.2
90%
25.0
23.0
239.6
30.0
28.0
239.6
35.0
32.0
239.6
40.0
36.0
239.6
45.0
41.0
239.6
47.0
43.0
239.6
50.0
46.0
239.6
55.0
51.0
239.6
60.0
56.0
239.6
-12.6
-13.0
145.6
-7.0
-7.6
158.6
-4.0
-4.4
166.4
0.0
-0.4
176.4
5.0
4.5
188.9
10.0
9.0
207.3
15.0
14.0
214.3
20.0
19.0
214.3
80%
25.0
23.0
214.3
30.0
28.0
214.3
35.0
32.0
214.3
40.0
36.0
214.3
45.0
41.0
214.3
47.0
43.0
214.3
50.0
46.0
214.3
55.0
51.0
214.3
60.0
56.0
214.3
TC = Total Capacity (MBh).
PI = Power Input (kW) (includes compressor and outdoor fan).
The System Combination Ratio must be between 50–130%.
Nominal capacity as rated: 0 ft. above sea level with 25 ft. of refrigerant piping.
0 ft. level difference between outdoor and indoor units.
116 | PERFORMANCE DATA
59
61
64
PI
TC
PI
TC
kW
MBh
kW
MBh
14.01
146.8
14.65
146.8
15.44
159.9
16.07
159.9
16.29
167.8
16.93
167.8
17.35
176.9
17.98
176.4
18.67
189.0
19.30
189.0
19.99
201.5
20.62
200.7
21.28
213.3
21.91
213.3
22.91
229.7
23.26
228.4
24.45
241.8
23.45
236.6
22.78
249.2
21.94
237.4
21.11
251.7
20.43
237.4
19.44
251.7
18.92
237.4
17.81
251.7
17.44
237.4
17.33
251.7
16.98
237.4
16.70
251.7
16.35
237.4
15.67
251.7
15.35
237.4
14.57
251.7
14.27
237.4
13.87
146.2
14.35
146.2
15.30
159.3
15.77
159.3
16.15
167.1
16.63
167.1
17.21
176.9
17.68
176.4
18.53
189.0
19.00
189.0
19.85
201.5
20.32
200.7
21.14
213.3
21.61
213.3
23.11
228.4
22.64
216.9
21.73
230.5
21.30
216.9
20.36
230.5
19.95
216.9
18.99
230.5
18.61
216.9
17.62
230.5
17.26
216.9
16.27
230.5
15.94
216.9
15.84
230.5
15.52
216.9
15.25
230.5
14.94
216.9
14.31
230.5
14.03
216.9
13.31
230.5
13.04
216.9
12.06
145.6
12.48
145.6
13.49
158.6
13.90
158.6
14.34
166.4
14.76
166.4
15.40
176.4
15.81
176.4
16.72
188.9
17.13
188.9
18.04
202.2
18.45
194.5
19.51
206.4
19.74
194.5
19.79
206.4
19.44
194.5
18.60
206.4
18.26
194.5
17.40
206.4
17.09
194.5
16.21
206.4
15.91
194.5
15.01
206.4
14.73
194.5
13.84
206.4
13.58
194.5
13.47
206.4
13.22
194.5
12.98
206.4
12.73
194.5
12.18
206.4
11.95
194.5
11.33
206.4
11.11
194.5
©
Indoor Air Temp. °F DB/°F WB
67
70
PI
TC
PI
TC
kW
MBh
kW
MBh
kW
15.60
146.4
16.26
145.9
16.93
17.02
159.4
17.69
158.9
18.35
17.88
167.3
18.54
166.7
19.21
18.93
176.1
19.60
175.9
20.26
20.25
188.5
20.92
188.0
21.58
21.57
200.6
22.24
200.5
22.90
22.86
212.8
22.96
212.3
23.06
23.79
222.2
22.81
216.0
21.84
21.95
226.3
21.30
216.0
20.65
20.68
226.7
20.07
216.0
19.45
19.42
226.7
18.84
216.0
18.26
18.15
226.7
17.61
216.0
17.06
16.89
226.7
16.39
216.0
15.88
16.45
226.7
15.95
216.0
15.46
15.84
226.7
15.36
216.0
14.89
14.87
226.7
14.42
216.0
13.98
13.83
226.7
13.41
216.0
13.00
15.06
145.8
15.84
145.3
16.63
16.48
158.8
17.27
158.3
18.05
17.34
166.6
18.12
166.1
18.91
18.40
176.0
19.18
175.7
19.96
19.71
188.3
20.50
187.7
21.28
21.03
198.8
21.82
196.8
22.60
22.33
205.6
22.06
197.8
21.80
21.94
207.3
21.25
197.8
20.56
20.64
207.3
19.99
197.8
19.35
19.34
207.3
18.74
197.8
18.14
18.03
207.3
17.48
197.8
16.93
16.73
207.3
16.22
197.8
15.71
15.45
207.3
14.98
197.8
14.52
15.04
207.3
14.59
197.8
14.14
14.48
207.3
14.05
197.8
13.61
13.59
207.3
13.19
197.8
12.78
12.64
207.3
12.26
197.8
11.88
13.09
145.2
14.02
144.7
14.95
14.52
158.1
15.45
157.6
16.37
15.37
165.9
16.30
165.4
17.23
16.43
175.1
17.36
173.8
18.28
17.75
183.0
18.68
177.2
19.60
19.07
185.8
19.36
177.2
19.66
20.09
185.8
19.36
177.2
18.62
18.92
185.8
18.23
177.2
17.54
17.77
185.8
17.12
177.2
16.48
16.62
185.8
16.02
177.2
15.42
15.46
185.8
14.91
177.2
14.36
14.31
185.8
13.81
177.2
13.30
13.18
185.8
12.72
177.2
12.26
12.83
185.8
12.38
177.2
11.94
12.36
185.8
11.93
177.2
11.50
11.60
185.8
11.19
177.2
10.79
10.79
185.8
10.41
177.2
10.03
Nominal heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and
outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
73
76
PI
TC
PI
TC
PI
MBh
kW
MBh
kW
145.9
18.23
145.9
18.98
158.9
19.65
158.9
20.40
166.7
20.51
166.7
21.26
175.9
21.56
175.9
22.31
188.0
22.88
188.0
23.63
198.1
23.67
193.1
23.28
203.3
22.66
191.4
21.97
203.3
21.35
191.4
20.70
203.3
20.07
191.4
19.45
203.3
18.79
191.4
18.20
203.3
17.51
191.4
16.96
203.3
16.23
191.4
15.71
203.3
14.97
191.4
14.48
203.3
14.57
191.4
14.10
203.3
14.03
191.4
13.58
203.3
13.17
191.4
12.75
203.3
12.25
191.4
11.85
145.3
18.08
145.3
19.27
158.3
19.51
158.3
20.70
166.1
20.36
166.1
21.55
175.2
21.42
174.2
22.61
183.2
22.16
175.9
22.11
186.2
21.73
174.8
20.76
186.2
20.62
174.8
19.68
186.2
19.45
174.8
18.57
186.2
18.31
174.8
17.47
186.2
17.18
174.8
16.38
186.2
16.04
174.8
15.28
186.2
14.90
174.8
14.18
186.2
13.78
174.8
13.11
186.2
13.41
174.8
12.76
186.2
12.92
174.8
12.29
186.2
12.12
174.8
11.53
186.2
11.27
174.8
10.73
144.7
16.93
144.7
18.11
157.6
18.27
157.6
19.28
162.8
19.07
157.3
19.98
166.1
19.77
156.3
19.90
166.2
19.35
156.3
18.76
166.2
18.38
156.3
17.81
166.2
17.44
156.3
16.89
166.2
16.46
156.3
15.92
166.2
15.49
156.3
14.97
166.2
14.53
156.3
14.03
166.2
13.56
156.3
13.08
166.2
12.60
156.3
12.13
166.2
11.65
156.3
11.20
166.2
11.34
156.3
10.91
166.2
10.92
156.3
10.50
166.2
10.25
156.3
9.86
166.2
9.53
156.3
9.17
80
TC
Pl
MBh
kW
145.9
19.98
158.9
21.41
166.7
22.26
175.9
23.32
188.0
24.64
186.4
22.76
175.5
21.05
175.5
19.83
175.5
18.62
175.5
17.42
175.5
16.22
175.5
15.02
175.5
13.84
175.5
13.47
175.5
12.98
175.5
12.18
175.5
11.33
145.3
20.85
158.3
22.28
166.1
23.13
172.9
24.19
166.1
22.04
159.7
19.46
159.7
18.44
159.7
17.38
159.7
16.35
159.7
15.31
159.7
14.27
159.7
13.23
159.7
12.21
159.7
11.89
159.7
11.45
159.7
10.75
159.7
10.00
144.7
19.70
157.6
20.62
150.0
21.18
143.2
20.08
143.1
17.98
143.1
17.05
143.1
16.15
143.1
15.21
143.1
14.28
143.1
13.36
143.1
12.44
143.1
11.51
143.1
10.61
143.1
10.33
143.1
9.95
143.1
9.33
143.1
8.68