Siemens SIMATIC S7-1200 Function Manual page 370

Pid control
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

Instructions
9.2 PID_3Step
ErrorBits
Description

 ( DW#16#...)
2000
Invalid value at Feedback_PER parameter.
Check whether an error is pending at the analog input.
The actuator cannot be moved to the substitute output value and remains in its current position. Manual
mode is not possible in this state. You must deactivate position feedback (Config. FeedbackOn =
FALSE) to move the actuator from this state.
If automatic mode was active before the error occurred, ActivateRecoverMode = TRUE, and the error is
no longer pending, PID_3Step switches back to automatic mode.
4000
Invalid value at Feedback parameter. Value has an invalid number format.
The actuator cannot be moved to the substitute output value and remains in its current position. Manual
mode is not possible in this state. You must deactivate position feedback (Config. FeedbackOn =
FALSE) to move the actuator from this state.
If automatic mode was active before the error occurred, ActivateRecoverMode = TRUE, and the error is
no longer pending, PID_3Step switches back to automatic mode.
8000
Error during digital position feedback. Actuator_H = TRUE and Actuator_L = TRUE.
The actuator cannot be moved to the substitute output value and remains in its current position. Manual
mode is not possible in this state.
In order to move the actuator from this state, you must deactivate the "Actuator endstop" (Con-
fig.ActuatorEndStopOn = FALSE).
If automatic mode was active before the error occurred, ActivateRecoverMode = TRUE, and the error is
no longer pending, PID_3Step switches back to automatic mode.
370
Function Manual, 03/2017, A5E35300227-AC
PID control

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500

Table of Contents

Save PDF