Table of Contents

Advertisement

®
Relion
670 series
Transformer protection RET670 2.0
Product guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB RET670

  • Page 1 ® Relion 670 series Transformer protection RET670 2.0 Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Application

    A pole slip protection function is also available in RET670 to detect, evaluate, and take the required action for pole slipping RET670 has a fast, low-impedance differential protection occurrences in the power system.
  • Page 4 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Description of configuration A30 W1_QB1 W1_QB2 RET670 A30 – 2 Winding Transformer in single breaker arrangement 12AI (9I+3U) 1 → 0 W1_QA1 DFR/SER DR SMP PTRC DRP RDRE W1_CT 50BF 3I>BF...
  • Page 5 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Description of configuration B30 RET670 B30 - 2 Winding Transformer in multi breaker arrangement 24AI (9I+3U, 9I+3U) 1 → 0 W1_QB1 DFR/DER DR W1_QB2 SMP PTRC DRP RDRE W1_CT2 50BF 3I>...
  • Page 6 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Description of configuration A40 W1_QB1 W1_QB2 RET670 A40 – 3 Winding Transformer in single breaker arrangement 24AI (9I+3U, 9I+3U) 1 → 0 W1_QA1 DFR/SER DR SMP PTRC DRP RDRE W1_CT 50BF 3I>BF...
  • Page 7 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Description of configuration B40 RET670 B40 - 3 Winding Transformer in multi breaker arrangement 24AI (9I+3U, 9I+3U) 1 → 0 W1_QB1 DFR/DER DR W1_QB2 SMP PTRC DRP RDRE W1_CT2 50BF 3I>...
  • Page 8 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Description of configuration A10 W1_QB1 W1_QB2 RET670 A10 – Transformer backup protection 12AI (9I+3U) 1 → 0 W1_QA1 DFR/SER DR SMP PTRC DRP RDRE W1_CT 50BF 3I>BF 4(3I>) 3I>>...
  • Page 9 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Description of configuration A25 RET670 A25 – Voltage Control 12AI (6I+6U) ↑↓ ↑↓ DFR/SER DR TCM YLTC DRP RDRE TCM YLTC Usqi VN MMXU V MSQI V MMXU TRF1...
  • Page 10: Available Functions

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 2. Available functions Main protection functions = number of basic instances = option quantities 3-A03 = optional function included in packages A03 (refer to ordering details)
  • Page 11 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 Differential protection T2WPDIF Transformer differential protection, two winding T3WPDIF Transformer differential protection, three winding HZPDIF 1Ph high impedance differential 3-A02 3-A02 3-A02...
  • Page 12 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 ZMFPDIS High speed distance protection 0–1 ZMFCPDIS High speed distance protection 0–1 for series compensated lines ZMRPSB Power swing detection 1-B12 1-B12...
  • Page 13 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Back-up protection functions IEC 61850 ANSI Function description Transformer RET670 Current protection PHPIOC Instantaneous phase 2-C19 overcurrent protection OC4PTOC Four step phase overcurrent 2-C19 51_67 protection EFPIOC Instantaneous residual...
  • Page 14 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 ROV2PTOV Two step residual overvoltage 1-D01 2-D02 protection 1-D01 1-D01 1-D02 1-D02 OEXPVPH Overexcitation protection 1-D03 1-D03 2-D04 2-D04 VDCPTOV Voltage differential protection...
  • Page 15 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Control and monitoring functions IEC 61850 ANSI Function description Transformer RET670 Control SESRSYN Synchrocheck, energizing check and 1-B, 2- 1-B, 3- 1-B, 4- synchronizing APC30 Apparatus control for up to 6 bays, max...
  • Page 16 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 I103USRCMD Function commands user defined for IEC 60870-5-103 Secondary system supervision CCSSPVC Current circuit supervision FUFSPVC Fuse failure supervision VDSPVC Fuse failure supervision based on...
  • Page 17 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 TEIGAPC Elapsed time integrator with limit transgression and overflow supervision Monitoring CVMMXN, Measurements CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU AISVBAS Function block for service value...
  • Page 18 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 I103SUPERV Supervison status for IEC 60870-5-103 I103USRDEF Status for user defiend signals for IEC 60870-5-103 L4UFCNT Event counter with limit supervision Metering...
  • Page 19 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Communication IEC 61850 ANSI Function description Transformer RET670 Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC 60870-5-103 for...
  • Page 20 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 GOOSEVCTRCO GOOSE VCTR configuration for send and receive VCTRSEND Horizontal communication via GOOSE for VCTR GOOSEVCTRRC Horizontal communication via GOOSE for VCTR...
  • Page 21 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC 61850 ANSI Function description Transformer RET670 Transmission of analog data from LDCM Receive binary status from 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 6/3/3 remote LDCM Scheme communication ECPSCH...
  • Page 22 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Basic IED functions Table 1. Basic IED functions IEC 61850 or function Description name INTERRSIG Self supervision with internal event list SELFSUPEVLST Self supervision with internal event list TIMESYNCHGEN...
  • Page 23: Differential Protection

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 1. Basic IED functions, continued IEC 61850 or function Description name ALTRK Service tracking ACTIVLOG Activity logging parameters FSTACCS Field service tool access via SPA protocol over ethernet communication...
  • Page 24 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 resistor, and a voltage dependent resistor which are both mounted externally to the IED, are also required. three-winding power transformer with all The external resistor unit shall be ordered under IED...
  • Page 25: Impedance Protection

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 • Phase-to-phase current variation • Zero sequence current criterion • Low voltage criterion • Low current criterion Forward operation Phase-to-phase current variation takes the current samples as input and it calculates the variation using the sampling value based algorithm.
  • Page 26 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Full-scheme distance measuring, Mho characteristic ZMHPDIS The numerical mho line distance protection is a four zone full Forward scheme protection for back-up detection of short circuit and operation earth faults.
  • Page 27 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 The independent measurement of impedance for each fault Mho alternative quadrilateral characteristic is available. loop together with a sensitive and reliable built in phase ZMRPDIS together with Phase selection, quadrilateral...
  • Page 28 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 The zones can operate independently of each other in for protection of power lines and cables in complex network directional (forward or reverse) or non-directional mode. configurations, such as parallel lines, multi-terminal lines, and However, zone1 and zone2 is designed to measure in forward so on.
  • Page 29: Current Protection

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 detect, evaluate, and take the required action for pole slipping Four step phase overcurrent protection OC4PTOC occurrences in the power system. The four step three-phase overcurrent protection function OC4PTOC has an inverse or definite time delay independent for Out-of-step protection OOSPPAM step 1 to 4 separately.
  • Page 30 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Sensitive directional residual overcurrent and power Breaker failure protection CCRBRF protection SDEPSDE Breaker failure protection (CCRBRF) ensures a fast backup In isolated networks or in networks with high impedance...
  • Page 31: Voltage Protection

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 K settings and the sensitivity and NS2PTOC has a wide range of Voltage-restrained time overcurrent protection VRPVOC capability of detecting and tripping for negative sequence Voltage-restrained time overcurrent protection (VRPVOC) currents down to the continuous capability of a generator.
  • Page 32: Frequency Protection

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 is also used as a frequency stage initiating load restoring. A Overexcitation protection OEXPVPH definite time delay is provided for operate. When the laminated core of a power transformer or generator is subjected to a magnetic flux density beyond its design limits, SAPTOF is provided with an undervoltage blocking.
  • Page 33: Secondary System Supervision

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 9. Secondary system supervision • Distance protection function. • Undervoltage function. Current circuit supervision CCSSPVC • Energisation function and voltage check for the weak Open or short circuited current transformer cores can cause infeed logic.
  • Page 34 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 interlocking, synchrocheck, operator place selection and Reservation input RESIN external or internal blockings. The Reservation input (RESIN) function receives the reservation information from other bays. The number of instances is the...
  • Page 35: Scheme Communication

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Hardware selector switches are used extensively by utilities, in In the directional scheme, information of the fault current order to have different functions operating on pre-set values. direction must be transmitted to the other line end. With...
  • Page 36: Monitoring

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Trip matrix logic TMAGAPC Elapsed time integrator with limit transgression and overflow Trip matrix logic TMAGAPC function is used to route trip signals supervision (TEIGAPC) and other logical output signals to different output contacts on The Elapsed time integrator function TEIGAPC is a function that the IED.
  • Page 37 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 • measured voltages, currents, frequency, active, reactive Event list DRPRDRE and apparent power and power factor Continuous event-logging is useful for monitoring the system • measured analog values from merging units from an overview perspective and is a complement to specific •...
  • Page 38: Metering

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 measure value expander block (RANGE_XP) has been Disturbance recorder DRPRDRE introduced to enable translating the integer output signal from The Disturbance recorder function supplies fast, complete and the measuring functions to 5 binary signals: below low-low limit, reliable information about disturbances in the power system.
  • Page 39: Human Machine Interface

    IEDs. • Communication port for PCM600. SPA communication protocol A single glass or plastic port is provided for the ABB SPA The LHMI is used for setting, monitoring and controlling. protocol. This allows extensions of simple substation automation systems but the main use is for Substation 16.
  • Page 40: Remote Communication

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 with unsolicited events, time synchronizing and disturbance 19. Hardware description reporting is provided for communication to RTUs, Gateways or Hardware modules HMI systems. Power supply module PSM The power supply module is used to provide the correct internal...
  • Page 41 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 communication (SPA, IEC 60870-5-103 and DNP3 port) and High impedance resistor unit one port is dedicated for LON communication. The high impedance resistor unit, with resistors for pick-up value setting and a voltage dependent resistor, is available in a Line data communication module LDCM single phase unit and a three phase unit.
  • Page 42 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 IEC06000182-2-en.vsd IEC06000182 V2 EN Figure 15. A 1/2 x 19” size IED side-by-side with RHGS6. xx08000165.vsd IEC08000165 V1 EN Figure 14. Case with rear cover and 19” rack mounting kit...
  • Page 43: Connection Diagrams

    1MRK 504 141-BEN C Product version: 2.0 20. Connection diagrams Connection diagrams for Configured products Connection diagrams Connection diagram, RET670 2.0, A10 1MRK002803-TF The connection diagrams are delivered on the IED Connectivity Connection diagram, RET670 2.0, A30 1MRK002803-TA package DVD as part of the product delivery.
  • Page 44: Technical Data

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 21. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified...
  • Page 45 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 4. MIM - mA input module Quantity: Rated value: Nominal range: Input resistance = 194 Ohm Input range ± 5, ± 10, ± 20mA 0-5, 0-10, 0-20, 4-20mA...
  • Page 46 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Binary inputs and outputs Table 7. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%...
  • Page 47 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 9. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20% 220/250 V RL ±20%...
  • Page 48 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 11. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
  • Page 49 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 13. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250 V AC/DC Number of outputs...
  • Page 50 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 16. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% / %...
  • Page 51 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Type tests according to standards Table 18. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
  • Page 52 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 20. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
  • Page 53 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Differential protection Table 23. Transformer differential protection T2WPDIF, T3WPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of Ir at I ≤ Ir ±1.0% of I at I > Ir Reset ratio >...
  • Page 54 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 24. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operate characteristic Adaptable ± 1.0% of I for I ≤ I ± 1.0% of I for I > I Reset ratio >95%...
  • Page 55 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 26. Additional security logic for differential protection LDRGFC Function Range or value Accuracy Operate current, zero sequence current (1-100)% of lBase ±1.0% of I Operate current, low current operation (1-100)% of lBase ±1.0% of I...
  • Page 56 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Impedance protection Table 27. Distance measuring zone, Quad ZMQPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction Minimum operate residual (5-1000)% of IBase current, zone 1...
  • Page 57 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 28. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction IBase Minimum operate residual...
  • Page 58 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 30. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 4 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, ±...
  • Page 59 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 32. Faulty phase identification with load encroachment FMPSPDIS Function Range or value Accuracy Load encroachment criteria: Load ±2.0% static accuracy (1.00–3000.00) W/phase resistance, forward and reverse (5–70) degrees Conditions: Voltage range: (0.1–1.1) x U...
  • Page 60 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 34. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS Function Range or value Accuracy Minimum operate current (5-500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reactive reach, positive (0.50–3000.00) Ω/phase...
  • Page 61 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 36. Power swing detection ZMRPSB Function Range or value Accuracy Reactive reach ± 2.0% static accuracy (0.10-3000.00) W/phase Conditions: Voltage range: (0.1-1.1) x U Current range: (0.5-30) x I...
  • Page 62 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 40. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of U and phase-to-neutral undervoltage Reset ratio, undervoltage < 105%...
  • Page 63 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Current protection Table 42. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ± 1.0% of I at I ≤ I ± 1.0% of I at I > I Reset ratio >...
  • Page 64 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 44. Instantaneous residual overcurrent protection EFPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 65 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 46. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate value, negative (1-2500)% of lBase ± 1.0% of I at I £ I sequence current, step 1-4 ±...
  • Page 66 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 47. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of lBase Operate level for 3I ·cosj ± 1.0% of I at I £ I directional residual ±...
  • Page 67 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 48. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F Operate time: Time constant t = (1–1000)
  • Page 68 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 50. Breaker failure protection CCRBRF Function Range or value Accuracy Operate phase current (5-200)% of lBase ±1.0% of I at I £ I ±1.0% of I at I > I Reset ratio, phase current >...
  • Page 69 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 53. Directional overpower protection GOPPDOP Function Range or value Accuracy Power level (0.0–500.0)% of SBase ±1.0% of S at S ≤ S for Step 1 and Step 2 ±1.0% of S at S >...
  • Page 70 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 55. Capacitor bank protection CBPGAPC Function Range or value Accuracy Operate value, overcurrent (10-900)% of lBase ±2.0% of I at I ≤ I ±2.0% of I at I > I Reset ratio, overcurrent >95% at (100-900)% of IBase...
  • Page 71 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 56. Negative sequence time overcurrent protection for machines NS2PTOC Function Range or value Accuracy Operate current, step 1 - 2 (3-500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 72 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Voltage protection Table 57. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of UBase ±0.5% of U...
  • Page 73 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 58. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U > U Absolute hysteresis (0.0–50.0)% of...
  • Page 74 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 60. Overexcitation protection OEXPVPH Function Range or value Accuracy Operate value, start (100–180)% of ( UBase /f ± 0.5% of U rated Operate value, alarm (50–120)% of start level ±...
  • Page 75 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Frequency protection Table 63. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ± 2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f...
  • Page 76 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 65. Rate-of-change frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz Definite restore time delay (0.000-60.000) s...
  • Page 77 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Multipurpose protection Table 66. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh, UnbalancePh, phase1-phase2, phase2-...
  • Page 78 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 66. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, undervoltage at 1.2 to 0.8 x U , step 1 - (0.00 - 6000.00) s...
  • Page 79 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 67. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 80 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Secondary system supervision Table 68. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90%...
  • Page 81 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 70. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse (10.0-80.0)% of UBase ±0.5% of Ur failure Reset ratio <110% Operate time, block of main fuse Min.
  • Page 82 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Control Table 71. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase...
  • Page 83 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 72. Voltage control TR1ATCC and TR8ATCC Function Range or value Accuracy Transformer reactance (0.1–200.0)Ω, primary Time delay for lower command when fast step down mode is activated (1.0–100.0) s Voltage control set voltage (85.0–120.0)% of UBase...
  • Page 84 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 72. Voltage control TR1ATCC and TR8ATCC, continued Function Range or value Accuracy Time after position change before the value is accepted (1–60) s ± 0.2% or ± 200 ms...
  • Page 85 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Scheme communication Table 73. Scheme communication logic for residual overcurrent protection ECPSCH Function Range or value Accuracy Scheme type Permissive Underreaching Permissive Overreaching Blocking Communication scheme (0.000-60.000) s ±0.2% or ±20 ms whichever is greater coordination time Table 74.
  • Page 86 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Logic Table 75. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ± 0.2% or ± 30 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
  • Page 87 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 77. Configurable logic blocks Q/T Logic block Quantity with cycle time Range or value Accuracy medium normal ANDQT ORQT INVERTERQT XORQT SRMEMORYQT RSMEMORYQT TIMERSETQT (0.000-90000.000) s ± 0.5% ± 10 ms PULSETIMERQT (0.000-90000.000) s...
  • Page 88 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Monitoring Table 80. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) × f ± 2.0 mHz Voltage (0.1-1.5) ×U ± 0.5% of U at U£U ± 0.5% of U at U > U Connected current (0.2-4.0) ×...
  • Page 89 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 84. Current sequence component measurement CMSQI Function Range or value Accuracy Current positive sequence, I1 (0.1–4.0) × I ± 0.3% of I at I ≤ 0.5 × I Three phase settings ±...
  • Page 90 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 88. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
  • Page 91 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 92. Trip value recorder Function Value Buffer capacity Maximum number of analog inputs Maximum number of disturbance reports Table 93. Disturbance recorder Function Value Buffer capacity Maximum number of analog inputs...
  • Page 92 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Metering Table 94. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 95. Energy metering ETPMMTR...
  • Page 93 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Station communication Table 96. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
  • Page 94 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 102. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000ft m typically *)
  • Page 95 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Remote communication Table 106. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm Singlemode 9/125 µm...
  • Page 96 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Hardware Table 107. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 108. Water and dust protection level according to IEC 60529...
  • Page 97 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Basic IED functions Table 112. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 113. Time synchronization, time tagging...
  • Page 98 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 116. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 99 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Inverse characteristic Table 117. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-2.00) in steps of 0.01 ANSI/IEEE C37.112 , ± 2.0% or ± 40 ms whichever is greater æ...
  • Page 100 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 118. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: k = (0.05-2.00) in steps of 0.01 IEC 60255-151, ± 2.0% or ± 40 ms whichever is greater æ...
  • Page 101 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 120. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 102 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 121. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 103 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 122. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01...
  • Page 104: Ordering For Customized Ied

    The selected qty of each table must be filled in, if no selection is possible the code is 0 Example of a complete code: RET670*2.0-F00X00 - A00002260300001 - B5225255211252221111000001 - C0000888322260002221620300 - D33320010 - E66600 - F9 - S6 - G542 - H06000014444 - K00000110 - L01 - M186 - P01 - B1X0 - AC - KB - B - A3X0 - D1D1ARGN1N1XXXXXXX -AAFXXX - AX...
  • Page 105 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 128. Differential functions Function Function Ordering no Positi Available Selected Notes and identification rules Transformer differential protection, two winding T2WPDIF 1MRK005904-FA Note: One, and only Transformer differential protection, three winding...
  • Page 106 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 130. Impedance functions, alternatives Function Function Ordering no Positi Available Selec Notes identification rules Note: One, and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative.
  • Page 107 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 132. Current functions Function Function Ordering no Positi Available Selected Notes and identification rules Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AA Four step phase overcurrent protection OC4PTOC 1MRK005910-BA Instantaneous residual overcurrent protection...
  • Page 108 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 139. General calculation Position Table 140. General calculation functions Function Function Ordering no Positi Available Selected Notes and identification rules Frequency tracking filter SMAIHPAC 1MRK005915-KA Table 141. Secondary system supervision Position Table 142.
  • Page 109 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 149. Monitoring Position Table 150. Monitoring functions Function Function Ordering no Positi Available Selected Notes and identification rules Circuit breaker condition monitoring SSCBR 1MRK005924-HA 0-18 Table 151. Station communication Position Table 152.
  • Page 110 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 155. Mounting selection Mounting details with IP40 of protection from the front Selection Notes and Rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 19"...
  • Page 111 Product version: 2.0 Table 158. Analog system selection Analog system Selection Notes and Rules No first TRM included Note: Only valid in RET670–N00 Compression terminals Note: Only the same type of TRM (compression or ringlug) in the Ringlug terminals same terminal.
  • Page 112 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 160. Maximum quantity of I/O modules, with ring lug terminals, module limits se above Case sizes Maximum in case Possible locations for I/O modules with ringlug 1/1 x 19”, one (1) TRM P3, P5, P7, P9, P11, P13, P15 1/1 x 19”, two (2) TRM...
  • Page 113 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 161. Binary input/output module selection Binary input/output Selection Notes and Rules modules Slot position (rear view) Note! Max 3 positions in 1/2 rack, 8 in 3/4 rack with 1 TRM, 5 in 3/4...
  • Page 114 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Table 161. Binary input/output module selection, continued Binary input/output Selection Notes and Rules modules SOM Static output Note: SOM must not to be placed module, 12 outputs, in position nearest to NUM; 1/2...
  • Page 115: Ordering For Pre-Configured Ied

    Example code: RET670 *2.0-A30X00- A02H02-B1A3-AC-KB-B-A3X0-DAB1RGN1N1XXXXXXX-AXFXXX-AX. Using the code of each position #1-12 specified as RET670*1-2 2-3 3 3 3 3 3 3 3 3 3 3 3 3-4 4-5-6-7 7-8-9 9 9 9-10 10 10 10 10 10 10 10 10 10 10-11 11 11 11 11 11-12 12...
  • Page 116 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Software options Notes and Rules No option All fields in the ordering form do not need to be filled in Restricted earth fault protection, low Note: A01 only for A40/...
  • Page 117 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Software options Notes and Rules only for B40 and M17 Circuit breaker condition monitoring - 6 CB only for A10 and A40 Circuit breaker condition monitoring - 18 CB...
  • Page 118 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Analog input system Notes and Rules Compression terminals Ringlug terminals First TRM, 9I+3U 1A, 110/220V Note: Not in A25 First TRM, 9I+3U 5A, 110/220V Note: Not in A25 First TRM, 5I, 1A+4I, 5A+3U, 110/220V...
  • Page 119 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Binary input/output module, mA and time synchronization boards. Notes and Rules Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 120 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Remote end communication, DNP serial comm. and time synchronization modules Notes and Rules Slot position (rear view) Available slots in 1/2 case with 1TRM █ █ █ █ Note: Max 1 LDCM in 1/2 case Available slots in 3/4 and 1/1 case with 2 TRM █...
  • Page 121: Ordering For Accessories

    Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 24. Ordering for Accessories Accessories GPS antenna and mounting details GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA Cable for antenna, 20 m Quantity: 1MRK 001 665-AA Cable for antenna, 40 m...
  • Page 122 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 External resistor unit High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V operating voltage Quantity: RK 795 101-MA High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100V...
  • Page 123 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 504 138-UEN ANSI Quantity: 1MRK 504 138-UUS Technical manual Quantity: 1MRK 504 139-UEN ANSI Quantity:...
  • Page 124 Transformer protection RET670 2.0 1MRK 504 141-BEN C Product version: 2.0 Engineering manual, 670 series Quantity: 1MRK 511 308-UEN ANSI Quantity: 1MRK 511 308-UUS Cyber security guideline Quantity: 1MRK 511 309-UEN Reference information For our reference and statistics we would be pleased to be provided with the following application data:...
  • Page 126 For more information please contact: Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB does ABB AB not accept any responsibility whatsoever for potential errors Substation Automation Products or possible lack of information in this document.

Table of Contents