Mitsubishi FX3U-4AD User Manual page 61

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
Common Items
4.4.2
FX
-4AD-PTW-ADP
3U
Specifications
Number of input points
Input signal
Rated temperature range
Digital output
Resolution
• Ambient temperature: 25°C±5°C ±0.5% for full scale
Overall accuracy
• Ambient temperature: 0°C to 55°C ±1.0% for full scale
• FX
Time required for
conversion
• FX
Input characteristics
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
0 points
occupied
(This number of points is not related to the maximum number of input/output points of the PLC.)
Centigrade(°C)
3-wire platinum resistance thermometer sensor(s)
-100°C to +600°C
-1000 to +6000
0.2°C to 0.3°C
/FX
Series PLC : 200µs (Data updated every scan time.)
3U
3UC
Series PLC : 250µs (Data updated every scan time.)
3G
+6150
+6000
-100°C
0
+600°C
Temperature
-1000
-1150
4 Comparison of Performance Specifications
FX
-4AD-PTW-ADP
3U
Fahrenheit(°F)
4ch
JIS C 1604-1997
-148°F to +1112°F
-1480 to +11120
0.4°F to 0.5°F
+11390
+11120
-148°F
-1750
4.4 Temperature Sensor Input
0
+1112°F
-1480 Temperature
A-39
A
B
C
D
E
F
G
H
I
J

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents