C09-0
Parameter protection
Set this parameter to prevent unintentional operations from operation panel.
Changing of the data can be protected per function group with the setting value as shown
below.
× : Protected
(Note 1)
(Note 2)
C09-1
Operation panel lock
FWD , REV , STOP key operations are protected.
= 1: All operation possible
= 2: All operation lock
Note, the motor will stop when the STOP key is pressed for two seconds
= 3: Only STOP key can be operated.
C09-2
LCL switchover protection
= 1: LCL mode switchover ( STOP + SET ) during running disabled
(Note)
= 2: LCL mode switchover ( STOP + SET ) during running enabled
C09-6
Fault history buffer clear
The fault history details can be cleared by setting the value to 1 and then pressing SET
key. This setting will not be registered in the internal memory. Thus, this parameter must be
set each time.
Nothing will occur if set to a value other than 1.
Use this before handing the unit over to the final user.
6. Control Functions and Parameter Settings
: Unprotected
(changeable)
(unchangeable)
Set 2 to lock all changes.
Set 1 to allow all changes. The 9 setting is for maker maintenance, do not set it.
Even when stopped, if the terminal block's RUN, R.RUN, F.JOG or R JOG is ON,
switchover to remote is not possible.