Menu - Test - ABB REF601 Applications Manual

Feeder protection and control/feeder protection
Hide thumbs Also See for REF601:
Table of Contents

Advertisement

Section 5
Use of LHMI
5.2.8
36
Menu – Test
Submenu Test and respective submenus shows and allows depending on the user
right to perform several kind of tests to verify the IED functionality:
Test -> Hardware: Enables Internal Hardware Tests, which includes LCD check,
Keyboard check and LEDs check. User can skip particular checks using interactive
menu selection.
Test -> Binary Output (BO): Enables testing of all output contact to test the
complete external circuit initiated by the output contact. Once test BO selected
output will be operated for around 2 sec.
Test -> Functional: Enables each protection function tests by loading fixed analog
values for five seconds and ignoring actual analog inputs. User can test all
protection stages and accordingly its relay configuration by having a simulated
analog values for 5 seconds.
The details of functions available in test mode are described as under the respective
section.
Remark:
To modify settings needs user rights of Setting or Admin user.
Following menu structure is used to navigate to the respective test settings:
Test
Figure 15: Test menu of relay REF601/REJ601 with its submenu
Test
Hardware
:YYY
Test
BO
Test
Functional
1MDU07212-YN Rev. A
REF601 / REJ601
Application Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rej601

Table of Contents