11.2 Outdoor Unit

Attached accessories
No.
Accessories part
Qty.
Drain elbow
1
1
Rubber cap
8
2
11.2.1 Select the Best Location
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
Avoid installations in areas where the ambient temperature may drop below -20°C.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinery oil, etc), it
lifespan maybe shorten.
When installing the product in a place where it will
be affected by typhoon or strong wind such as
wind blowing between buildings, including the
rooftop of a building and a place where there is no
building in surroundings, fix the product with an
overturn prevention wire, etc. (Overturn prevention
fitting model number: K-KYZP15C)
If piping length is over 10 m, additional refrigerant should be added as shown in the table.
Model
UX09*E5*, UX12*E5*,
UD12*E5*, UD16*E5*,
ø15.88mm
UX09*E8*, UX12*E8*,
UX16*E8*, UD09*E8*,
UD12*E8*, UD16*E8*
Example:
If piping length is 30m, the quantity of additional refrigerant should be 1000g. [(30-10)m x 50 g/m = 1000g]
11.2.2 Install the Outdoor Unit
11.2.2.1
Installation Diagram
It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation,
please consult authorized dealer/specialist.
This illustration is for explanation purposes only.
No.
Accessories part
Protective bushing
3
Piping size
Rated Length
Gas
Liquid
Ø9.52mm
(5/8")
(3/8")
Vinyl tape (Wide)
Saddle
Indoor/Outdoor connecting cable
- For UX09*E5*, UX12*E5*, UD12*E5*, UD16*E5* use 4-CORE WIRE min 4.0mm
- For UX09*E8*, UX12*E8*, UX16*E8*, UD09*E8*, UD12*E8*, UD16*E8* use
6-CORE WIRE min 1.5mm
Type designation 60245 IEC 57 or heavier cord
ø9.52mm (3/8") Liquid refrigerant piping
ø15.88mm (5/8") Gas refrigerant piping
[
Check that the cables do not
touch the compressor, etc.
Optional Accessory
Qty.
No.
Base Pan Heater
CZ-NE3P
2
4
It is strongly recommended to install a Base Pan Heater
(optional) if the outdoor unit is install in cold climate area.
Refer the Base Pan Heater (optional) installation instruction
for details of installation.
Max. Elevation (m)
(m)
5
20
2
]
60
Accessories part
Min. Piping
Max. Piping
Length (m)
Length (m)
3
30
2
Qty.
1
Additional
Refrigerant (g/m)
50