T8501A,B,C,D MICROELECTRONIC THERMOSTATS
Mode Display
(Press i key
to change)
Select
Not used
13
Degree tempera-
14
ture display
Not used
15 thru 18
Extended fan
19
operation in
a,b
heating
Extended fan
20
operation in
a
cooling
Not used
21 thru 23
Outdoor
24
temperature
a
display
Not used
25 thru 32
Minimum off time
33
for the
compressor
Heating setpoint
34
a
range stop
Cooling setpoint
35
a
range stop
System On
36
a
display
Temperature
37
display
adjustment
a
Available on select models.
b
Mode 02 must be set to 01 to extend fan operation.
c
T8501D is 48°F.
69-0959
Table 2. Thermostat Installer Setup Options (continued).
Factory-Setting
Display
Description
00
Temperature is
displayed in °F
00
No extended fan
operation after the call
for heat ends
00
No extended fan
operation after the call
for cool ends
00
No outdoor temperature
is displayed
05
5 minute minimum off
time for the compressor
90
Heating setpoint can be
set no higher than 90°F
c
45
Cooling setpoint can be
set no lower than 45°F
00
LCD On symbol is
displayed when system
is energized
00
No difference in
displayed temperature
and actual room
temperature
(Press
Display
01
01
01
01
00, 01,
02, 03 or
04
40 thru
90
c
45
thru
c
99
01
01 thru
06
6
Other Choices
or
key to change)
Description
Temperature is displayed in °C
Fan operation is extended
90 seconds after the call for
heat ends
Fan operation is extended
90 seconds after the call for
cool ends
Outdoor temperature is displayed.
Needs a C7089B1000 Outdoor
Sensor to operate.
Minimum number of minutes
(0 thru 5) the compressor will be
off between calls for the
compressor
Number can be set anywhere
between 40 and 90 in 1°F
increments
Number can be set anywhere
c
between 45
and 99 in 1°F
increments
Display is disabled, usually set for
01 for a zoned system
01—Display adjusts to 1°F higher
than actual room temperature
02—Display adjusts to 2°F higher
than actual room temperature
03—Display adjusts to 3°F higher
than actual room temperature
04—Display adjusts to 1°F lower
than actual room temperature
05—Display adjusts to 2°F lower
than actual room temperature
06—Display adjusts to 3°F lower
than actual room temperature

Advertisement

Table of Contents
loading

This manual is also suitable for:

T8501bT8501cT8501d

Table of Contents