7 MICROMASTER 440 specifications
Fault
Possible Causes
Ø Motor data identification failed.
F0041
Ø Alarm value =0: Load missing
Motor Data
Ø Alarm value =1: Current limit level
Identification
reached during identification.
Failure
Ø Alarm value =2: Identified stator
resistance less than 0.1% or
greater than 100%.
Ø Alarm value =3: Identified
rotorresistance less than 0.1% or
greater than 100%.
Ø Alarm value =4: Identified stator
reactance less than 50% and
greater than 500%
Ø Alarm value =5: Identified main
reactance less than 50% and
greater than 500%
Ø Alarm value =6: Identified rotor
time constant less than 10ms or
greater than 5s
Ø Alarm value =7: Identified total
leakage reactance less than 5%
and greater than 50%
Ø Alarm value =8: Identified stator
leakage reactance less than 25%
and greater than 250%
Ø Alarm value =9: Identified rotor
leakage inductance less than
25% and greater than 250%
Ø Alarm value = 20: Identified IGBT
on-voltage less than 0.5 or
greater than 10V
Ø Alarm value = 30: Current
controller at voltage limit
Ø Alarm value = 40: Inconsistence
of identified data set, at least one
identification failed
Ø Percentage values based on the
impedance Zb = Vmot,nom /
sqrt(3) / Imot,nom
Read or write failure while saving
F0051
non-volatile parameter.
Parameter
EEPROM Fault
Read failure for power stack
F0052
information or invalid data.
Power Stack
Fault
Read failure for IO EEPROM
F0053
information or invalid data
IO Eeprom
Fault
Ø Wrong IO board is connected.
F0054
Ø No ID detected on IO board,
Wrong IO
No data.
Board
Communications failure
F0060
Asic Timeout
No setpoint received from
F0070
communications board during
CB setpoint
telegram off time
fault
No response during telegram off time
F0071
via USS (BOP-link)
USS (BOP-
link) setpoint
fault
No response during telegram off time
F0072
via USS (COMM-link)
USS (COMM
link) setpoint
fault
76
Diagnose & Remedy
0:
Check that the motor is connected to the
inverter.
1-40:
Check if motor data in P304-311 are
correct.
Check what type of motor wiring is required (star,
delta).
Ø Factory Reset and new parameterization.
Ø Change inverter
Change inverter
Ø Check data
Ø Change IO module
1. Check data
2. Change IO module
1. Acknowledge fault
2. Change inverter if repeated
1. Check connections to the
communications board
2. Check the master
1. Check connections to the
communications board
2. Check the master
1. Check connections to the
communications board
2. Check the master
MICROMASTER 440
Issue A2
Reac-
tion
OFF2
OFF2
OFF2
OFF2
OFF2
OFF2
OFF2
OFF2
OFF2