Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : ASYA07/09/12LCC
[Condition]
Ambient
Indoor 15 - 23degC, Outdoor 2 - 12degC
temperature
Refrigerant
Standard amount
amount
Piping
7.5m (Height difference 1m)
length
Power
50Hz - 230V
voltage
Operation
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
condition
Measuring
outdoor unit overall current with the current clamp meter at Power Cable.
method
Caution
Start operation with the condition of the Indoor Unit air filter clean.
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*9LSACW series
3
2.8
2.6
2.4
2.2
2
1.8
0
5
outdoor ambient temparature C
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*9LSACW series
4.50
4.00
3.50
3.00
0
5
outdoor ambient temparature C
15 C
20 C(Indoor inlet tempe)
23 C
10
15
6.5
5.5
15 C
4.5
20 C(Indoor inlet temp)
23 C
10
15
08-03
ASYA12LCC
15degC
3.4
20degC
(Indoor ambient temp. )
23degC
3.2
3
2.8
2.6
2.4
2.2
2
0
2
4
6
Outdoor ambient temparature [degC]
ASYA12LCC
7
15degC
20degC
(Indoor ambient temp. )
23degC
6
5
4
0
2
4
6
Outdoor ambient temparature [degC]
8
10
12
14
8
10
12
14

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents