13 Operation and Control

13.1. Basic Function

Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes,
automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the
microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature
shifting. The compressor at outdoor unit is operating following the frequency instructed by the microcomputer at indoor unit that
judging the condition according to internal setting temperature and intake air temperature.
13.1.1. Internal Setting Temperature
Once the operation starts, remote control setting temperature will be taken as base value for temperature shifting processes. These
shifting processes are depending on the air conditioner settings and the operation environment. The final shifted value will be used
as internal setting temperature and it is updated continuously whenever the electrical power is supplied to the unit.
13.1.2. Cooling Operation
13.1.2.1. Thermostat control
• Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting temperature
< -2.0 C
• Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting temperature
> Capability supply OFF point.
13.1.3. Soft Dry Operation
13.1.3.1. Thermostat control
• Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting temperature
< -3.0 C
• Capability resume to indoor unit after waiting for 3 minutes, if the Intake Air temperature — Internal setting temperature
> Capability supply OFF point.
13.1.4. Heating Operation
13.1.4.1. Thermostat control
• Capability supply to indoor unit is OFF (Expansion valve closed) when Intake Air Temperature — Internal setting temperature
> +1.0 C
• During this condition, the indoor fan is stopped if compressor is ON.
• Capability resume supply to indoor unit after waiting for 3 minutes, if the Intake Air Temperature — Internal setting temperature
< Capability supply OFF point.
36