Mitsubishi Electric FR-B-750 to 75K Instruction Manual

Mitsubishi Electric FR-B-750 to 75K Instruction Manual

Fr-b-750 to 75k (200v class), fr-b-750 to 110k (400v class)
Table of Contents

Advertisement

PRESSURE-RESISTANT, EXPLOSION-PROOF MOTOR DRIVING INVERTER
FR-B, B3
INSTRUCTION MANUAL (Applied)
Reduced torque type
FR-B-750 to 75K (200V CLASS)
FR-B-750 to 110K (400V CLASS)
Constant torque type
(Standard or low acoustic noise)
FR-B3-(N)400 to 37K
FR-B3-(N)H400 to 37K
Be sure to perform offline auto tuning in the motor running
mode and operate with the advanced magnetic flux vector
control when using the FR-B3 series.
(A700 SPECIFICATIONS)
OUTLINE
WIRING
PRECAUTIONS FOR USE
OF THE INVERTER
PARAMETERS
PROTECTIVE FUNCTIONS
PRECAUTIONS FOR
MAINTENANCE AND INSPECTION
SPECIFICATIONS
1
2
3
4
5
6
7

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric FR-B-750 to 75K

  • Page 1 PRESSURE-RESISTANT, EXPLOSION-PROOF MOTOR DRIVING INVERTER FR-B, B3 INSTRUCTION MANUAL (Applied) (A700 SPECIFICATIONS) Reduced torque type FR-B-750 to 75K (200V CLASS) FR-B-750 to 110K (400V CLASS) Constant torque type OUTLINE (Standard or low acoustic noise) FR-B3-(N)400 to 37K WIRING FR-B3-(N)H400 to 37K...
  • Page 2 Thank you for choosing this Mitsubishi Inverter. This Instruction Manual (applied) provides instructions for advanced use of the FR-B, B3 series inverters. Incorrect handling might cause an unexpected fault. Before using the inverter, always read this instruction manual and the instruction manual (basic) [IB-0600271ENG] packed with the product carefully to use the equipment to its optimum.
  • Page 3: Table Of Contents

    CONTENTS OUTLINE Product checking and parts identification ............2 Inverter and peripheral devices................3 1.2.1 Peripheral devices ........................4 Method of removal and reinstallation of the front cover........6 Installation of the inverter and enclosure design ..........8 1.4.1 Inverter installation environment....................8 1.4.2 Cooling system types for inverter enclosure................
  • Page 4 Noise and leakage currents ................40 3.1.1 Leakage currents and countermeasures ................. 40 3.1.2 Inverter-generated noises and their reduction techniques ............42 3.1.3 Power supply harmonics ......................44 3.1.4 Harmonic suppression guideline ..................... 45 Installation of a reactor ..................48 Power-off and magnetic contactor (MC) ............
  • Page 5 4.8.2 Starting frequency and start-time hold function (Pr. 13, Pr. 571) ........... 90 4.8.3 Acceleration/deceleration pattern (Pr. 29, Pr. 140 to Pr. 143, Pr. 380 to Pr. 383, Pr. 516 to Pr. 519) ........................91 4.8.4 Shortest acceleraiton/deceleration and optimum acceleration/deceleration (automatic acceleration/deceleration) (Pr.
  • Page 6 4.14.1 Retry function (Pr. 65, Pr. 67 to Pr. 69) ................155 4.14.2 Alarm code output selection (Pr. 76) ..................157 4.14.3 Input/output phase failure protection selection (Pr. 251, Pr. 872) ........158 4.14.4 Overspeed detection (Pr. 374) ..................... 158 4.14.5 Encoder signal loss detection (Pr.
  • Page 7 4.20.4 Frequency setting by pulse train input (Pr. 291, Pr. 384 to Pr. 386)........239 4.20.5 Encoder feedback control (Pr. 144, Pr. 285, Pr. 359, Pr. 367 to Pr. 369) ......242 4.20.6 Regeneration avoidance function (Pr. 665, Pr. 882 to Pr. 886) ..........244 4.21 Useful functions....................
  • Page 8 5.5.9 Speed varies during operation....................280 5.5.10 Operation mode is not changed properly ................280 5.5.11 Operation panel (FR-DU07) display is not operating............. 281 5.5.12 POWER lamp is not lit ......................281 5.5.13 Parameter write cannot be performed ................... 281 PRECAUTIONS FOR MAINTENANCE AND INSPECTION Inspection item....................
  • Page 9 APPENDICES Appendix 1 For customers who have replaced the older model with this inverter ....................308 Appendix 1-1 Replacement of the FR-B,B3 series (A500 specifications) ........308 Appendix 2 Control mode-based parameter (function) correspondence table and instruction code list ............310...
  • Page 10: Outline

    OUTLINE This chapter describes the basic "OUTLINE" for use of this product. Always read the instructions before using the equipment 1.1 Product checking and parts identification....2 1.2 Inverter and peripheral devices .......3 1.3 Method of removal and reinstallation of the front cover ...............6 1.4 Installation of the inverter and enclosure design ..8 <Abbreviations>...
  • Page 11: Product Checking And Parts Identification

    Product checking and parts identification 1.1 Product checking and parts identification Unpack the inverter and check the capacity plate on the front cover and the rating plate on the inverter side face to ensure that the product agrees with your order and the inverter is intact. ·...
  • Page 12: Inverter And Peripheral Devices

    Inverter and peripheral devices 1.2 Inverter and peripheral devices Three-phase AC power supply Use within the permissible power supply specifications of the inverter. (Refer to page 298) Inverter (FR-B,B3) Moulded case circuit breaker (MCCB) or The life of the inverter is influenced by earth leakage current breaker (ELB), ambient temperature.
  • Page 13: Peripheral Devices

    Inverter and peripheral devices 1.2.1 Peripheral devices Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be selected according to the capacity. Refer to the following list and prepare appropriate peripheral devices: 200V class Breaker Selection Input Side Magnetic Contactor *2,4 Applicable Inverter Type...
  • Page 14 Inverter and peripheral devices 400V class Breaker Selection Input Side Magnetic Contactor *2,4 Applicable Inverter Type Motor Output Reactor connection Reactor connection (kW) FR-B FR-B3 without with without with 30AF 5A 30AF 5A S-N10 S-N10 FR-B-750 FR-B3-(N)H400 0.75 30AF 5A 30AF 5A S-N10 S-N10...
  • Page 15: Method Of Removal And Reinstallation Of The

    Method of removal and reinstallation of the front cover 1.3 Method of removal and reinstallation of the front cover •Removal of the operation panel 1) Loosen the two screws on the operation panel. 2) Push the left and right hooks of the operation panel (These screws cannot be removed.) and pull the operation panel toward you to remove.
  • Page 16: Front Cover

    Method of removal and reinstallation of the front cover 30K or more • Removal 1) Remove installation screws on 2) Loosen the installation 3) Pull the front cover 2 toward you to the front cover 1 to remove the screws of the front cover 2. remove by pushing an installation front cover 1.
  • Page 17: Installation Of The Inverter And Enclosure Design

    Installation of the inverter and enclosure design 1.4 Installation of the inverter and enclosure design When an inverter enclosure is to be designed and manufactured, heat generated by contained equipment, etc., the environment of an operating place, and others must be fully considered to determine the enclosure structure, size and equipment layout.
  • Page 18 Installation of the inverter and enclosure design (3) Dust, dirt, oil mist Dust and dirt will cause such faults as poor contact of contact points, reduced insulation or reduced cooling effect due to moisture absorption of accumulated dust and dirt, and in-enclosure temperature rise due to clogged filter. In the atmosphere where conductive powder floats, dust and dirt will cause such faults as malfunction, deteriorated insulation and short circuit in a short time.
  • Page 19: Cooling System Types For Inverter Enclosure

    Installation of the inverter and enclosure design 1.4.2 Cooling system types for inverter enclosure From the enclosure that contains the inverter, the heat of the inverter and other equipment (transformers, lamps, resistors, etc.) and the incoming heat such as direct sunlight must be dissipated to keep the in-enclosure temperature lower than the permissible temperatures of the in-enclosure equipment including the inverter.
  • Page 20 Installation of the inverter and enclosure design (2) Clearances around the inverter To ensure ease of heat dissipation and maintenance, leave at least the shown clearances around the inverter. At least the following clearances are required under the inverter as a wiring space, and above the inverter as a heat dissipation space. (front) Ambient temperature and humidity Clearances...
  • Page 21 MEMO...
  • Page 22: Wiring

    WIRING This chapter describes the basic "WIRING" for use of this product. Always read the instructions before using the equipment 2.1 Wiring ..............14 2.2 Main circuit terminal specifications......16 2.3 Control circuit specifications........26 2.4 Connection of stand-alone option units ....34...
  • Page 23: Wiring

    Wiring 2.1 Wiring 2.1.1 Terminal connection diagram Sink logic *1. DC reactor (FR-HEL) *7. A CN8 connector is provided with the 75K Brake unit Be sure to connect the DC reactor or more. Main circuit terminal (Option) supplied with the 75K or more. Control circuit terminal When a DC reactor is connected to Jumper...
  • Page 24: Emc Filter

    Wiring 2.1.2 EMC filter This inverter is equipped with a built-in EMC filter (capacitive filter) and common mode core. The EMC filter is effective for reduction of air-propagated noise on the input side of the inverter. The EMC filter is factory-set to disable (OFF). To enable it, fit the EMC filter ON/OFF connector to the ON position. The input side zero-phase reactor, built-in the 55K or less inverter, is always valid regardless of on/off of the EMC filter on/off connector.
  • Page 25: Main Circuit Terminal Specifications

    Main circuit terminal specifications 2.2 Main circuit terminal specifications 2.2.1 Specification of main circuit terminal Terminal Terminal Name Description Symbol R/L1, Connect to the commercial power supply. S/L2, AC power input Keep these terminals open when using the high power factor converter T/L3 (MT-HC) U, V, W...
  • Page 26 Main circuit terminal specifications FR-B-5.5K, 7.5K FR-B-11K FR-B3-(N)5.5K, 7.5K FR-B3-(N)11K R1/L11 S1/L21 Screw size (M4) Charge lamp Jumper Charge lamp P/+ PR Jumper Jumper Jumper R1/L11 S1/L21 Screw size (M5) Screw size (M5) R/L1 S/L2 T/L3 R/L1 S/L2 T/L3 Explosion- Power supply proof Power supply...
  • Page 27 Main circuit terminal specifications 400V class FR-B-750 to 3700 FR-B-7.5K FR-B3-(N)H400 to 3700 FR-B3-(N)H5.5K 7.5K Jumper Screw size (M4) R/L1 S/L2 T/L3 Charge lamp Jumper R1/L11 S1/L21 P/+ PR Jumper Jumper R1/L11 S1/L21 Screw size Charge lamp (M4) Screw size Power (M4) Explosion-proof...
  • Page 28 Main circuit terminal specifications FR-B-37K FR-B-55K FR-B3-(N)H30K, 37K R1/L11 S1/L21 R1/L11 S1/L21 Screw size(M4) Screw size (M4) Charge lamp Charge lamp Jumper Jumper Screw size (M8) Screw size (M10) Screw size (M8) Screw size (30K: M6, 37K/45K: M8) R/L1 S/L2 T/L3 Jumper Screw size (M8) R/L1 S/L2 T/L3...
  • Page 29: Cables And Wiring Length

    Main circuit terminal specifications 2.2.3 Cables and wiring length (1) Applied cable size Select the recommended cable size to ensure that a voltage drop will be 2% max. If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque to decrease especially at the output of a low frequency.
  • Page 30 Main circuit terminal specifications 400V class (when input power supply is 440V) Cable Sizes Crimping Applicable Inverter Type Terminal Terminal HIV, etc. (mm Tightening Screw Earth Torque N·m R/L1, R/L1, Size FR-B FR-B3 U, V, W U, V, W P/+, P1 (Ground) S/L2, S/L2,...
  • Page 31 Main circuit terminal specifications (2) Notes on earthing (grounding) Always earth (ground) the motor and inverter. 1)Purpose of earthing (grounding) Generally, an electrical apparatus has an earth (ground) terminal, which must be connected to the ground before use. An electrical circuit is usually insulated by an insulating material and encased. However, it is impossible to manufacture an insulating material that can shut off a leakage current completely, and actually, a slight current flow into the case.
  • Page 32 Main circuit terminal specifications (3) Total wiring length The overall wiring length for connection of a motor should be within the value in the table below. (An explosion-proof test is not performed for the multiple motor connection.) Inverter Capacity 1500 or more FR-B, B3 (at normal operation) 300m 500m...
  • Page 33: When Connecting The Control Circuit And The Main Circuit Separately To The Power Supply (Separate Power)

    Main circuit terminal specifications 2.2.4 When connecting the control circuit and the main circuit separately to the power supply (separate power) <Connection diagram> When the protected circuit is activated, opening of the electromagnetic contactor (MC) on the inverter power supply side results in power loss in the control circuit, disabling the alarm output signal retention.
  • Page 34 Main circuit terminal specifications • FR-B-11K(200V/400V class) or more, FR-B3-(N)(H)11K or more 1) Remove the upper screws. 2) Remove the lower screws. 3) Pull the jumper toward you to remove. L21 Power supply terminal block 4) Connect the separate power supply for the control circuit cable for the control circuit to the Power supply terminal block...
  • Page 35: Control Circuit Specifications

    Control circuit specifications 2.3 Control circuit specifications 2.3.1 Control circuit terminals indicates that terminal functions can be selected using Pr. 178 to Pr. 196 (I/O terminal function selection) (Refer to page 118.) (1) Input signals Terminal Terminal Rated Refer to Description Symbol Name...
  • Page 36 Control circuit specifications Terminal Terminal Rated Refer to Description Symbol Name Specifications page 10VDC±0.4V Permissible load When connecting the frequency setting potentiometer at an initial Frequency current 10mA status, connect it to terminal 10. setting power Change the input specifications of terminal 2 when connecting it 5.2VDC±0.2V supply to terminal 10E.
  • Page 37 Control circuit specifications Terminal Terminal Rated Refer to Description Symbol Name Specifications page Permissible load Output item: current 2mA For meter Output frequency 1440pulses/s at (initial setting) 60Hz Signals can be output Maximum output Select one e.g. output frequency from NPN open from the open pulse: 50kpulses/s...
  • Page 38: Changing The Control Logic

    Control circuit specifications 2.3.2 Changing the control logic The input signals are set to sink logic (SINK) when shipped from the factory. To change the control logic, the jumper connector on the back of the control circuit terminal block must be moved to the other position.
  • Page 39 Control circuit specifications 4) Sink logic and source logic ⋅ In sink logic, a signal switches on when a current flows from the corresponding signal input terminal. Terminal SD is common to the contact input signals. Terminal SE is common to the open collector output signals. ⋅...
  • Page 40: Control Circuit Terminal Layout

    Control circuit specifications 2.3.3 Control circuit terminal layout Terminal screw size: M3.5 Tightening torque: 1.2N·m C2 10E 10 STOP (1) Common terminals of the control circuit (SD, 5, SE) Terminals SD, 5, and SE are all common terminals (0V) for I/O signals and are isolated from each other. Do not earth (ground).
  • Page 41: Wiring Instructions

    Control circuit specifications 2.3.4 Wiring instructions Terminals 5, SD and SE are common to the I/O signals and isolated from each other. Do not earth (ground). Avoid connecting the terminal SD and 5 and the terminal SE and 5. Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).
  • Page 42: When Connecting The Operation Panel Using A Connection Cable

    Control circuit specifications 2.3.5 When connecting the operation panel using a connection cable When connecting the operation panel (FR-DU07) to the inverter using a cable, the operation panel can be mounted on the enclosure surface and operationality improves. Parameter unit connection cable (FR-CB2 )(option) Operation panel(FR-DU07)
  • Page 43: Connection Of Stand-Alone Option Units

    Connection of stand-alone option units 2.4 Connection of stand-alone option units The inverter accepts a variety of stand-alone option units as required. Incorrect connection will cause inverter damage or accident. Connect and operate the option unit carefully in accordance with the corresponding option unit manual. 2.4.1 Connection of the brake unit (FR-BU/MT-BU5)(FR-B-75K or more) When connecting the brake unit (FR-BU(H)/MT-BU5) to improve the brake capability at deceleration, make connection...
  • Page 44 Connection of stand-alone option units (2) Connection with the MT-BU5 After making sure that the MT-BU5 is properly connected, set the following parameters. Pr. 30 Regenerative function selection = "1" Pr. 70 Special regenerative brake duty = "10%" (Refer to page 102) Explosion- MCCB proof...
  • Page 45: Connection Of The High Power Factor Converter (Mt-Hc)(Fr-B-75K Or More)

    Connection of stand-alone option units 2.4.2 Connection of the high power factor converter (MT-HC)(FR-B-75K or more) When connecting the high power factor converter (MT-HC) to suppress power harmonics, perform wiring securely as shown below. Incorrect connection will damage the high power factor converter and inverter. After making sure that the wiring is correct, set "2"...
  • Page 46: Connection Of Power Regeneration Converter (Mt-Rc) (75K Or More)

    Connection of stand-alone option units 2.4.3 Connection of power regeneration converter (MT-RC) (75K or more) When connecting a power regeneration converter (MT-RC), perform wiring securely as shown below. Incorrect connection will damage the regeneration converter and inverter. After connecting securely, set "1" in Pr.
  • Page 47 MEMO...
  • Page 48: Precautions For Use Of The Inverter

    PRECAUTIONS FOR USE OF THE INVERTER This chapter explains the "PRECAUTIONS FOR USE OF THE INVERTER" for use of this product. Always read the instructions before using the equipment 3.1 Noise and leakage currents........40 3.2 Installation of a reactor ..........48 3.3 Power-off and magnetic contactor (MC)....48 3.4 Precautions for use of the inverter ......49...
  • Page 49: Noise And Leakage Currents

    Noise and leakage currents 3.1 Noise and leakage currents 3.1.1 Leakage currents and countermeasures Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current flows. Since its value depends on the capacitances, carrier frequency, etc., low acoustic noise operation at the increased carrier frequency of the inverter will increase the leakage current.
  • Page 50 Noise and leakage currents (3) Selection of rated sensitivity current of earth (ground) leakage breaker When using the earth (ground) leakage circuit breaker with the inverter circuit, select its rated sensitivity current as follows, independently of the PWM carrier frequency: ⋅...
  • Page 51: Inverter-Generated Noises And Their Reduction Techniques

    Noise and leakage currents 3.1.2 Inverter-generated noises and their reduction techniques Some noises enter the inverter to malfunction it and others are radiated by the inverter to malfunction peripheral devices. Though the inverter is designed to be insusceptible to noises, it handles low-level signals, so it requires the following basic techniques.
  • Page 52 Noise and leakage currents Noise Propagation Measures Path When devices that handle low-level signals and are liable to malfunction due to noises, e.g. instruments, receivers and sensors, are contained in the enclosure that contains the inverter or when their signal cables are run near the inverter, the devices may be malfunctioned by air-propagated noises.
  • Page 53: Power Supply Harmonics

    Noise and leakage currents 3.1.3 Power supply harmonics The inverter may generate power supply harmonics from its converter circuit to affect the power generator, power capacitor etc. Power supply harmonics are different from noise and leakage currents in source, frequency band and transmission path.
  • Page 54: Harmonic Suppression Guideline

    Noise and leakage currents 3.1.4 Harmonic suppression guideline Harmonic currents flow from the inverter to a power receiving point via a power transformer. The harmonic suppression guideline was established to protect other consumers from these outgoing harmonic currents. The three-phase 200V input specifications 3.7kW or less are previously covered by "Harmonic suppression guideline for household appliances and general-purpose products"...
  • Page 55 Noise and leakage currents 1) Calculation of equivalent capacity P0 of harmonic generating equipment The "equivalent capacity" is the capacity of a 6-pulse converter converted from the capacity of consumer's harmonic generating equipment and is calculated with the following equation. If the sum of equivalent capacities is higher than the limit in Table 3, harmonics must be calculated with the following procedure: P0 = Σ...
  • Page 56 Noise and leakage currents 3) Harmonic suppression technique requirement If the outgoing harmonic current is higher than the maximum value per 1kW (contract power) × contract power, a harmonic suppression technique is required. 4) Harmonic suppression techniques Item Description Reactor installation Install an AC reactor (FR-HAL) on the AC side of the inverter or a DC reactor (FR-HEL) on (FR-HAL, FR-HEL) its DC side or both to suppress outgoing harmonic currents.
  • Page 57: Installation Of A Reactor

    Installation of a reactor 3.2 Installation of a reactor When the inverter is connected near a large-capacity power transformer (1000kVA or more and wiring length 10m max.) or when a power capacitor is to be switched over, an excessive peak current may flow in the power input circuit, damaging the converter circuit.
  • Page 58: Precautions For Use Of The Inverter

    Precautions for use of the inverter 3.4 Precautions for use of the inverter The FR-B, B3 series is a highly reliable product, but incorrect peripheral circuit making or operation/handling method may shorten the product life or damage the product. Before starting operation, always recheck the following items. (1) Use crimping terminals with insulation sleeve to wire the power supply and motor.
  • Page 59 Precautions for use of the inverter (12) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the inverter's input side and also make up a sequence which will not switch on the start signal. If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the power is restored.
  • Page 60: Parameters

    4 PARAMETERS This chapter explains the "PARAMETERS" for use of this product. Always read this instructions before use. The abbreviations in the explanations below are as follows: ...FR-B series, ...FR-B3 series, Parameters with above abbreviations supported by the corresponding series. (Parameters without abbreviations are supported by both FR-B and FR-B3 series.)
  • Page 61: Operation Panel (Fr-Du07)

    Operation panel (FR-DU07) 4.1 Operation panel (FR-DU07) 4.1.1 Parts of the operation panel (FR-DU07) Operation mode indication PU: Lit to indicate PU operation mode. EXT: Lit to indicate external operation mode. NET: Lit to indicate network operation mode. Rotation direction indication FWD: Lit during forward rotation REV: Lit during reverse rotation Forward/reverse operation...
  • Page 62: Basic Operation (Factory Setting)

    Operation panel (FR-DU07) 4.1.2 Basic operation (factory setting) Operation mode switchover At powering on (external operation mode) PU Jog operation mode (Refer to page 54) (Example) Value change and frequency flicker. PU operation mode Frequency setting has been (output frequency monitor) written and completed!! Output current monitor Output voltage monitor...
  • Page 63: Change The Parameter Setting Value

    Operation panel (FR-DU07) 4.1.3 Change the parameter setting value Changing example Change the Pr. 1 Maximum frequency . Operation Display Screen at powering on The monitor display appears. PU indication is lit. Press to choose the PU operation mode. The parameter Press to choose the parameter number read...
  • Page 64: Parameter List

    Parameter List 4.2 Parameter List 4.2.1 Parameter list For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made from the operation panel (FR-DU07).
  • Page 65 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page 0 to 120Hz/ 0 to 120Hz, Frequency jump 1A 0 to 60Hz, 0.01Hz 9999 9999 9999 0 to 120Hz/ 0 to 120Hz, Frequency jump 1B 0 to 60Hz,...
  • Page 66 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page Number of retries at alarm occurrence 0 to 10, 101 to 110 Retry waiting time 0 to 10s 0.1s Retry count display erase ...
  • Page 67 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page 0 to 0 to 120Hz/ PID control automatic switchover 0.01Hz 9999 120Hz, 0 to 60Hz, frequency 9999 9999 10, 11, 20, 21, 50, 51, 60, PID action selection 0.1% 100%...
  • Page 68 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page User group registered display/batch 9999, (0 to 16) clear User group registration 0 to 999, 9999 9999 User group clear 0 to 999, 9999 9999 0 to 12, 14,...
  • Page 69 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page Terminal 1 added compensation  0 to 100% 0.1% 100% amount (terminal 2) Terminal 1 added compensation  0 to 100% 0.1% amount (terminal 4) ...
  • Page 70 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page   0.01Hz Brake opening frequency 0 to 30Hz   Brake opening current 0 to 220% 0.1% 130% ...
  • Page 71 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page 0 to 120Hz/ 0 to 0.01Hz 9999 Speed feedback range 120Hz, 0 to 60Hz, 9999 9999 Feedback gain 0 to 100 111, 1024 Number of encoder pulses...
  • Page 72 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page Output interruption detection time 0 to 3600s, 9999 0.1s 0 to 120Hz/ 0.01Hz Output interruption detection level 0 to 120Hz 0 to 60Hz Output interruption cancel level 900 to 1100%...
  • Page 73 Parameter List Setting Range Minimum Initial Value Refer Func- Parame- Customer Name Setting tion Setting FR-B FR-B3 FR-B FR-B3 Increments Page    FM terminal calibration (900)    AM terminal calibration (901) 0 to 120Hz/ Terminal 2 frequency setting bias 0.01Hz 0 to 120Hz (902)
  • Page 74 Parameters according to purposes Control mode Before operating the FR-B3 series 4.4.1 Setting the FR-B3 series (advanced magnetic flux vector control) (Pr. 80, Pr. 81, Pr. 89 ) ........68 4.4.2 Offline auto tuning (Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 684, Pr. 859) ............. 70 Adjust the output torque of the motor (current) 4.5.1 Stall prevention operation (Pr.
  • Page 75 4.14.4 Overspeed detection (Pr. 374)..........................158 4.14.5 Encoder signal loss detection (Pr. 376)........................158 4.14.6 Fault definition (Pr. 875) ............................159 4.15 Energy saving operation and energy saving monitor 4.15.1 Energy saving monitor (Pr. 891 to Pr. 899)......................160 4.16 Frequency setting by analog input (terminal 1, 2, 4) 4.16.1 Function assignment of analog input terminal (Pr.
  • Page 76: Control Mode

    Control mode Control mode (1) V/F Control (FR-B series only) ⋅ It controls frequency and voltage so that the ratio of frequency (F) to voltage (V) is constant when changing frequency. (2) Advanced magnetic flux vector control (FR-B3 series only) ⋅...
  • Page 77: Before Operating The Fr-B3 Series

    Before operating the FR-B3 series 4.4 Before operating the FR-B3 series 4.4.1 Setting the FR-B3 series (advanced magnetic flux vector control) (Pr. 80, Pr. 81, Pr. 89 ) Setting can be made only for FR-B3 series. For explosion-proof certification, the FR-B3 series are tested with the rotation mode under the advanced magnetic flux control after the offline auto tuning has been performed.
  • Page 78 Before operating the FR-B3 series (1) Setting procedure of FR-B3 (advanced magnetic flux vector control) Perform secure wiring. (Refer to page 14) For the motor capacity and the number of motor poles (Pr.80 and Pr.81), the advanced magnetic flux vector control is set in the initial setting. (Change unnecessary) (Refer to page 68) Set offline auto tuning.
  • Page 79: Offline Auto Tuning (Pr. 80 To Pr. 84, Pr. 90 To Pr. 94, Pr. 96, Pr. 684, Pr. 859)

    Before operating the FR-B3 series 4.4.2 Offline auto tuning ( Pr. 80 to Pr. 84 , Pr. 90 to Pr. 94 , Pr. 96 , Pr. 684, Pr. 859 ) Setting can be made only for FR-B3 series. • What is offline auto tuning? When performing FR-B3 series, the motor can be run with the optimum operating characteristics by automaticaly measuring the motor constants (offline auto tuning) even when each motor constants differs, other manufacturer's motor is used, or the wiring length is long.
  • Page 80 Before operating the FR-B3 series (1) Before performing offline auto tuning Check the following before performing offline auto tuning. · A motor should be connected. Note that the motor should be at a stop at a tuning start. When performing the offline auto tuning, always select the rotation mode (Pr.96="101"). ·...
  • Page 81 Before operating the FR-B3 series (3) Execution of tuning CAUTION · Before performing tuning, check the monitor display of the operation panel (FR-DU07) or parameter unit (FR-PU04/FR- PU07) if the inverter is in the state ready for tuning. (Refer to 2 below) 1)When performing PU operation, press of the operation panel.
  • Page 82 Before operating the FR-B3 series 3)When offline auto tuning ends, press of the operation panel during PU operation. For external operation, turn off the start signal (STF signal or STR signal). This operation resets the offline auto tuning and the PU's monitor display returns to the normal indication. (Without this operation, next operation cannot be started.) REMARKS ·...
  • Page 83: Adjust The Output Torque Of The Motor (Current)

    Adjust the output torque of the motor (current) 4.5 Adjust the output torque of the motor (current) 4.5.1 Stall prevention operation (Pr. 22, Pr. 23, Pr. 48, Pr. 49, Pr. 66, Pr. 114, Pr. 115, Pr. 148, Pr. 149, Pr. 154, Pr. 156, Pr. 157, Pr. 858, Pr. 868) This function monitors the output current and automatically changes the output frequency to prevent the inverter from coming to an alarm stop due to overcurrent, overvoltage, etc.
  • Page 84 Adjust the output torque of the motor (current) CAUTION ⋅ If an overload status lasts long, an inverter trip (e.g. electronic thermal relay function (E.THM)) may occur. ⋅ When Pr. 156 has been set to activate the fast-response current limit (initial setting), the Pr. 22 setting should not be higher than 170%.
  • Page 85 Adjust the output torque of the motor (current) (4) Set multiple stall prevention operation levels (Pr. 48, Pr. 49, Pr. 114, Pr. 115) ⋅ Setting "9999" in Pr. 49 Second stall prevention operation frequency and turning the RT signal on make Pr. 48 Second stall prevention operation current valid.
  • Page 86 Adjust the output torque of the motor (current) (5) Stall prevention operation level setting by terminal 1 (terminal 4) (analog variable) (Pr. 148, Pr. 149, Pr. 858, Pr. 868) ⋅ To set the stall prevention operation level using terminal 1 (analog input), set Pr. 868 Terminal 1 Current limit level (%) Set the current limit level at 10V/5V input function assignment to "4".
  • Page 87 Adjust the output torque of the motor (current) (7) Limit the stall prevention operation and fast-response current limit operation according to the operating status (Pr. 156) ⋅ Refer to the following table and select whether fast-response current limit operation will be performed or not and the operation to be performed at OL signal output.
  • Page 88: Limit The Output Frequency

    Limit the output frequency 4.6 Limit the output frequency Purpose Parameter that must be Set Refer to Page Set upper limit and lower limit of Maximum/minimum Pr. 1, Pr. 2 output frequency frequency Perform operation by avoiding Frequency jump Pr. 31 to Pr. 36 mechanical resonance points 4.6.1 Maximum/minimum frequency (Pr.
  • Page 89: Avoid Mechanical Resonance Points (Frequency Jump) (Pr. 31 To Pr. 36)

    Limit the output frequency 4.6.2 Avoid mechanical resonance points (Frequency jump) (Pr. 31 to Pr. 36) When it is desired to avoid resonance attributable to the natural frequency of a mechanical system, these parameters allow resonant frequencies to be jumped. Setting Range Parameter Name...
  • Page 90: Frequency Setting By External Terminals

    Frequency setting by external terminals 4.7 Frequency setting by external terminals Purpose Parameter that must be Set Refer to Page Make frequency setting by Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Multi-speed operation combination of terminals Pr. 232 to Pr. 239 Perform jog operation Jog operation Pr.
  • Page 91 Frequency setting by external terminals (1) Multi-speed setting (Pr. 4 to Pr. 6) Speed 1 (High speed) ⋅ Operation is performed at the frequency set in Pr. 4 when the RH Speed 5 Speed 2 Speed 6 signal turns on, Pr. 5 when the RM signal turns on, and Pr. 6 when the (Middle speed) Speed 4 Speed 3...
  • Page 92: Jog Operation (Pr. 15, Pr. 16)

    Frequency setting by external terminals 4.7.2 Jog operation (Pr. 15, Pr. 16) You can set the frequency and acceleration/deceleration time for jog operation. Jog operation can be performed from either the outside or PU. Can be used for conveyor positioning, test operation, etc. Setting Range Parameter Initial...
  • Page 93 Frequency setting by external terminals (2) Jog operation from PU Inverter ⋅ Set the PU (FR-DU07/FR-PU07/FR-PU04) to the jog operation mode. Operation is performed only Three-phase AC Motor power supply while the start button is pressed. FR-DU07 Operation Indication Confirmation of the RUN indication and operation mode indication The monitor mode should have been selected.
  • Page 94: Input Compensation Of Multi-Speed And Remote Setting (Pr. 28)

    Frequency setting by external terminals 4.7.3 Input compensation of multi-speed and remote setting (Pr. 28) By inputting the frequency setting compensation signal (terminal 1, 2), the speed (frequency) can be compensated for relative to the multi-speed setting or the speed setting by remote setting function. Parameter Name Initial Value...
  • Page 95 Frequency setting by external terminals (2) Frequency setting storage ⋅ The frequency setting storage function stores the remotely-set frequency (frequency set by RH/RM operation) into the memory (EEPROM). When power is switched off once, then on, operation is resumed with that output frequency value.
  • Page 96 Frequency setting by external terminals REMARKS During jog operation or PID control operation, the remote setting function is invalid. Setting frequency is "0" ⋅ Even when the remotely-set Remotely-set frequency stored last time frequency is cleared by turning on the RL (clear) signal after Within 1 minute turn off (on) of both the RH and Remotely-set frequency stored last time...
  • Page 97: Setting Of Acceleration/Deceleration Time And Acceleration/Deceleration Pattern

    Setting of acceleration/deceleration time and acceleration/deceleration pattern 4.8 Setting of acceleration/deceleration time and acceleration/deceleration pattern Purpose Parameter that must be Set Refer to Page Motor acceleration/deceleration time Pr. 7, Pr. 8, Pr. 20, Pr. 21, Acceleration/deceleration time setting Pr. 44, Pr. 45, Pr. 110, Pr. 111 Starting frequency and start- Starting frequency Pr.
  • Page 98 Setting of acceleration/deceleration time and acceleration/deceleration pattern (2) Deceleration time setting (Pr. 8, Pr. 20) ⋅ Use Pr. 8 Deceleration time to set the deceleration time required to reach 0Hz from Pr. 20 Acceleration/deceleration reference frequency. ⋅ Set the deceleration time according to the following formula. Pr.
  • Page 99: Starting Frequency And Start-Time Hold Function (Pr. 13, Pr. 571)

    Setting of acceleration/deceleration time and acceleration/deceleration pattern 4.8.2 Starting frequency and start-time hold function (Pr. 13, Pr. 571) You can set the starting frequency and hold the set starting frequency for a certain period of time. Set these functions when you need the starting torque or want to smooth motor drive at a start. Parameter Name Initial Value...
  • Page 100: Acceleration/Deceleration Pattern (Pr. 29, Pr. 140 To Pr. 143, Pr. 380 To Pr. 383, Pr. 516 To Pr. 519)

    Setting of acceleration/deceleration time and acceleration/deceleration pattern 4.8.3 Acceleration/deceleration pattern (Pr. 29, Pr. 140 to Pr. 143, Pr. 380 to Pr. 383, Pr. 516 to Pr. 519) You can set the acceleration/deceleration pattern suitable for application. You can also set the backlash measures that stop acceleration/deceleration once at the parameter-set frequency and time during acceleration/deceleration.
  • Page 101 Setting of acceleration/deceleration time and acceleration/deceleration pattern (3) S-pattern acceleration/deceleration B (Pr. 29 = "2") Setting value "2" [S-pattern acceleration ⋅ For prevention of load shifting in conveyor and other applications /deceleration B] Since acceleration/deceleration is always made in an S shape from current frequency (f2) to target frequency (f1), this function eases shock produced at acceleration/deceleration and is effective for load collapse prevention, etc.
  • Page 102 Setting of acceleration/deceleration time and acceleration/deceleration pattern (6) S-pattern acceleration/deceleration D (Pr. 29 = "5", Pr. 516 to Pr. 519) ⋅ Set the time taken for S-pattern operation of S-pattern acceleration/deceleration using Pr. 516 to Pr. 519. Set each S-pattern operation time for acceleration start (Pr. 516), acceleration completion (Pr.
  • Page 103: Shortest Acceleraiton/Deceleration And Optimum Acceleration/Deceleration (Automatic Acceleration/Deceleration) (Pr. 61 To Pr. 63, Pr. 292, Pr. 293)

    Setting of acceleration/deceleration time and acceleration/deceleration pattern 4.8.4 Shortest acceleraiton/deceleration and optimum acceleration/deceleration (automatic acceleration/deceleration) (Pr. 61 to Pr. 63, Pr. 292, Pr. 293) Setting can be made only for FR-B3 series. The inverter operates in the same conditions as when appropriate values are set in each parameter even if acceleration/deceleration time and V/F pattern are not set.
  • Page 104 Setting of acceleration/deceleration time and acceleration/deceleration pattern (2) Optimum acceleration/deceleration mode (Pr. 292 = "3") ⋅ The optimum operation within the rating range where the inverter can be continuously used regardless of the inverter capability is performed. Automatically set torque boost and acceleration/deceleration time so that the average current during acceleration/ deceleration is the rated current by the self-learning of the inverter.
  • Page 105: Selection And Protection Of A Motor

    Selection and protection of a motor 4.9 Selection and protection of a motor Purpose Parameter that must be Set Refer to Page Motor protection from overheat Electronic thermal O/L relay Pr. 9 Use the constant torque motor Applied motor * Pr.
  • Page 106 Selection and protection of a motor (2) Electronic thermal relay function alarm output and alarm signal (THP signal) ⋅ The alarm signal (THP) is output when the electronic thermal 100%: Electronic thermal relay function alarm operation value relay function cumulative value reaches 85% of the level set in Electronic thermal 100% Pr.
  • Page 107 Selection and protection of a motor (4) PTC thermistor input (PTC signal) Explosion- Inverter Inverter proof motor AU(PTC) PTC thermistor input connection example AU/PTC switchover switch Factory-set to "AU". Set to the "PTC" position to validate the PTC signal input. Built-in PTC thermistor of the motor can be input to the PTC signal (AU terminal).
  • Page 108: Applied Motor (Pr. 71)

    Selection and protection of a motor 4.9.2 Applied motor (Pr. 71) Setting can be made only for FR-B series. Setting of the used motor selects the thermal characteristic appropriate for the motor. Setting is necessary when using a constant-torque motor. Thermal characteristic of the electronic thermal relay function suitable for the motor is set.
  • Page 109: Motor Brake And Stop Operation

    Motor brake and stop operation 4.10 Motor brake and stop operation Purpose Parameter that must be Set Refer to Page Motor braking torque adjustment DC injection brake Pr. 10 to Pr. 12 Improve the motor braking torque Selection of a regenerative brake Pr.
  • Page 110 Motor brake and stop operation When Pr. 11 = "0.1 to 10s" (1) Operation frequency setting (Pr. 10) ⋅ When the frequency at which the DC injection brake operates is set in Pr. 10, the DC injection brake (zero speed control, servo lock) is operated when this frequency is reached during deceleration.
  • Page 111: Selection Of Regenerative Brake (Pr. 30, Pr. 70) (75K Or More)

    Motor brake and stop operation 4.10.2 Selection of regenerative brake (Pr. 30, Pr. 70) (75K or more) Setting can be made only for FR-B series. When making frequent starts/stops, use the brake unit (FR-BU, MT-BU5) to increase the regenerative brake duty.
  • Page 112 Motor brake and stop operation (3) When using the high power factor converter (MT-HC) (FR-B-75K or more) When using the high power factor converter (MT-HC), another explosion-proof test is necessary. Note, however, that the test is not necessary when using the high power factor converter for power factor improvement.
  • Page 113: Stop Selection (Pr. 250)

    Motor brake and stop operation 4.10.3 Stop selection (Pr. 250) Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns off. Used to stop the motor with a mechanical brake, etc. together with switching off of the start signal. You can also select the operations of the start signals (STF/STR).
  • Page 114: Stop-On Contact Control Function (Pr. 6, Pr. 48, Pr. 270, Pr. 275)

    Motor brake and stop operation 4.10.4 Stop-on contact control function (Pr. 6, Pr. 48, Pr. 270, Pr. 275) Setting can be made only for FR-B3 series. To ensure accurate positioning at the upper limit etc. of a <Without stop-on-contact control> <With stop-on-contact control>...
  • Page 115 Motor brake and stop operation (1) Set stop-on-contact control ⋅ Make sure that the inverter is in external operation mode. (Refer to page 182 ) ⋅ Set"1 or 3" in Pr. 270 Stop-on contact/load torque high-speed frequency control selection . ⋅...
  • Page 116 Motor brake and stop operation (3) Set frequency when stop-on-contact control (Pr. 270 = 1, 3) is selected ⋅ The following table lists the frequencies set when the input terminals (RH, RM, RL, RT, JOG) are selected together. Bold frame indicates stop-on-contact control is valid. ⋅...
  • Page 117: Brake Sequence Function (Pr. 278 To Pr. 285, Pr. 292)

    Motor brake and stop operation 4.10.5 Brake sequence function (Pr. 278 to Pr. 285, Pr. 292) Setting can be made only for FR-B3 series. This function is used to output from the inverter the mechanical brake operation timing signal in vertical lift and other applications.
  • Page 118 Motor brake and stop operation (1) Set the brake sequence mode ⋅ The brake sequence function is valid only when the external operation mode, external/PU combined operation mode 1 or network operation mode is selected. ⋅ Set "7 or 8" (brake sequence mode) in Pr. 292 . To ensure more complete sequence control, it is recommended to set "7"...
  • Page 119 Motor brake and stop operation (4) Protective functions If any of the following errors occurs in the brake sequence mode, the inverter results in an alarm, shuts off the output, and turns off the brake opening request signal (BOF). Error Display Description (Detection frequency) - (output frequency) >...
  • Page 120: Orientation Control (Pr. 350 To Pr. 366, Pr. 369)

    Motor brake and stop operation 4.10.6 Orientation control (Pr. 350 to Pr. 366, Pr. 369) This function is used with a position detector (encoder) installed to the spindle of a machine tool, etc. to allow a rotation shaft to be stopped at the specified position (oriented). Option FR-A7AP is necessary.
  • Page 121 Motor brake and stop operation Parameter Initial Setting Name Description Number Value Range Measure the time taken after passing the creep 0 to 60.0s switchover position and output the orientation fault signal Orientation limit 9999 (ORM) if orientation is not completed within the set time. 9999 Set to 120s.
  • Page 122 Motor brake and stop operation (3) Selecting stop position command (Pr. 350 Stop position command selection ) ⋅ Select either the internal stop position command (Pr. 356) or the external stop position command (16-bit data using the FR-A7AX). Pr.350 Setting Stop Position Command Source Internal stop position command (Pr.
  • Page 123 Motor brake and stop operation • Relationship between stop position command and 16-bit data Operation Pr. 350 Pr. 360 Stop position 16 bit data 16 bit data selection Stop position command Speed command command selection (FR-A7AX) 0: speed command Internal (Pr. 356) Speed command 16 bit data 0:internal...
  • Page 124 Motor brake and stop operation (6) Orientation operation (under V/F control, advanced magnetic flux vector control) Orientation during running 1) When the orientation command (X22) is input, the motor speed decreases to the orientation speed set in Pr. 351 Orientation speed . (Pr. 351 initial value: 2Hz) 2) After the speed reaches the orientation speed, the speed decreases to the creep speed set in Pr.
  • Page 125 Motor brake and stop operation Orientation from stop After turning on the orientation command (X22), turning on the start signal will increase the motor speed to the orientation speed set in Pr. 351 Orientation speed, then orientation operation same as when "orientation during running" is performed.
  • Page 126 Motor brake and stop operation Servo torque selection (Pr. 358 ) Pr. 358 Setting Remarks Function 0 1 2 3 4 5 6 7 8 9 10 11 12 13 1) Servo torque function selection With servo torque function × ×...
  • Page 127: Function Assignment Of External Terminal And Control

    Function assignment of external terminal and control 4.11 Function assignment of external terminal and control Purpose Parameter that must be Set Refer to Page Input terminal function Assign function to input terminal Pr. 178 to Pr. 189 selection Set MRS signal (output shutoff) to MRS input selection Pr.
  • Page 128 Function assignment of external terminal and control (1) Input terminal function assignment ⋅ Use Pr. 178 to Pr. 189 to set the functions of the input terminals. ⋅ Refer to the following table and set the parameters: Application :Corres- pondence Signal Refer to Setting...
  • Page 129 Function assignment of external terminal and control CAUTION ⋅ Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Please make setting after confirming the function of each terminal. ⋅ One function can be assigned to two or more terminals. In this case, the terminal inputs are ORed. ⋅...
  • Page 130: Inverter Output Shutoff Signal (Mrs Signal, Pr. 17)

    Function assignment of external terminal and control 4.11.2 Inverter output shutoff signal (MRS signal, Pr. 17) The inverter output can be shut off from the MRS signal. The logic of the MRS signal can also be selected. Parameter Initial Setting Name Description Number...
  • Page 131: Condition Selection Of Function Validity By The Second Function Selection Signal (Rt) And Third Function Selection Signal (X9) (Rt Signal, X9 Signal, Pr. 155)

    Function assignment of external terminal and control 4.11.3 Condition selection of function validity by the second function selection signal (RT) and third function selection signal (X9) (RT signal, X9 signal, Pr. 155) You can select the second (third) function using the RT(X9) signal. You can also set the condition (reflection conditon) where the second function and third function become valid.
  • Page 132: Start Signal Selection (Stf, Str, Stop Signal, Pr. 250)

    Function assignment of external terminal and control 4.11.4 Start signal selection (STF, STR, STOP signal, Pr. 250) You can select the operation of the start signal (STF/STR). Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns off. Used to stop the motor with a mechanical brake, etc.
  • Page 133 Function assignment of external terminal and control (2) 3-wire type (STF, STR, STOP signal) ⋅ A three-wire type connection is shown below. ⋅ The start self-holding selection becomes valid when the STOP signal is turned on. In this case, the forward/reverse rotation signal functions only as a start signal.
  • Page 134: Output Terminal Function Selection (Pr. 190 To Pr. 196)

    Function assignment of external terminal and control 4.11.5 Output terminal function selection (Pr. 190 to Pr. 196) You can change the functions of the open collector output terminal and relay output terminal. Setting Range Parameter Name Initial Value Initial Signal Number FR-B FR-B3...
  • Page 135 Function assignment of external terminal and control Application :Corres- Refer Setting pondence Signal Related Function Operation × :Non-corres- Name Parameters Page pondence Positive Negative FR-B FR-B3 Logic Logic Output when the inverter power is turned on, then output after reset Inverter operation ...
  • Page 136 Function assignment of external terminal and control Application :Corres- Refer Setting pondence Signal Related Function Operation × :Non-corres- Name Parameters pondence Page Positive Negative FR-B FR-B3 Logic Logic Average current value and Current average maintenance timer value are output as value monitor pulses.
  • Page 137 Function assignment of external terminal and control (2) Inverter operation ready signal (RY signal) and inverter running signal (RUN, RUN3 signal) Power ⋅ When the inverter is ready to operate, the output of the supply operation ready signal (RY) is on. (It is also on during inverter running.) ⋅...
  • Page 138 Function assignment of external terminal and control (3) Alarm output signal (ALM, ALM2 signal) ⋅ If the inverter comes to an alarm stop, the ALM and ALM2 Inverter alarm occurrence signals are output. (output shutoff) ⋅ The ALM2 signal remains on during a reset period after alarm occurrence.
  • Page 139: Detection Of Output Frequency (Su, Fu, Fu2 , Fu3, Ls Signal, Pr. 41 To Pr. 43, Pr. 50, Pr. 116, Pr. 865)

    Function assignment of external terminal and control 4.11.6 Detection of output frequency (SU, FU, FU2 , FU3, LS signal, Pr. 41 to Pr. 43, Pr. 50, Pr. 116, Pr. 865) The inverter output frequency is detected and output to the output signal. Setting Range Parameter Initial...
  • Page 140 Function assignment of external terminal and control (3) Low speed detection (LS signal, Pr. 865) ⋅ The low speed detection signal (LS) is output when the output frequency reduces below the Pr. 865 Low speed detection setting. Pr.865 ⋅ For the LS signal, set "34 (positive logic) or 134 (nega- tive logic)"...
  • Page 141: Output Current Detection Function (Y12 Signal, Y13 Signal, Pr. 150 To Pr. 153, Pr. 166, Pr. 167)

    Function assignment of external terminal and control 4.11.7 Output current detection function (Y12 signal, Y13 signal, Pr. 150 to Pr. 153, Pr. 166, Pr. 167) The output power during inverter running can be detected and output to the output terminal. Parameter Name Initial Value...
  • Page 142: Detection Of Output Torque (Tu Signal, Pr. 864)

    Function assignment of external terminal and control (2) Zero current detection (Y13 signal, Pr. 152, Pr. 153) ⋅ If the output current remains lower than the Pr. 152 setting Output during inverter operation for longer than the time set in Pr. current 153, the zero current detection (Y13) signal is output from Pr.152...
  • Page 143: Remote Output Function (Rem Signal, Pr. 495 To Pr. 497)

    Function assignment of external terminal and control 4.11.9 Remote output function (REM signal, Pr. 495 to Pr. 497) You can utilize the on/off of the inverter's output signals instead of the remote output terminal of the programmable logic controller. Parameter Name Initial Value Setting Range Description...
  • Page 144: Monitor Display And Monitor Output Signal

    Monitor display and monitor output signal 4.12 Monitor display and monitor output signal Purpose Parameter that must be Set Refer to Page Display motor speed Speed display and speed Pr. 37, Pr. 144, Pr. 505, Pr. 811 Set speed setting DU/PU main display data Change PU monitor display data selection...
  • Page 145 Monitor display and monitor output signal CAUTION ⋅ In the FR-B series, the output frequency of the inverter is displayed in terms of synchronous speed, and therefore, it is unequal to the actual speed by motor slip. Since the FREQROL-B3 series are operated by the advanced magnetic flux vector control, this display changes to the actual speed (estimated value calculated based on the motor slip) and actual speed from the encoder when encoder feed back control is performed.
  • Page 146: Du/Pu, Fm, Am Terminal Monitor Display Selection (Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891)

    Monitor display and monitor output signal 4.12.1 DU/PU, FM, AM terminal monitor display selection (Pr. 52, Pr. 54, Pr. 158, Pr. 170, Pr. 171, Pr. 268, Pr. 563, Pr. 564, Pr. 891) The monitor to be displayed on the main screen of the operation panel (FR-DU07)/parameter unit (FR-PU04/FR- PU07) can be selected.
  • Page 147 Monitor display and monitor output signal Pr. 52 Setting Full-scale Pr. 54 (FM) Value of the Types of Monitor Increments Pr. 158 (AM) Description PU main Terminal FM DU LED Setting monitor and AM ×   Alarm display 0/100 Displays 8 past alarms individually.
  • Page 148 Monitor display and monitor output signal Pr. 52 Setting Full-scale Pr. 54 (FM) Value of the Types of Monitor Increments Pr. 158 (AM) Description PU main Terminal FM DU LED Setting monitor and AM PID set point 0.1% 100% Displays the set point, measured value and PID measured 0.1% 100%...
  • Page 149 Monitor display and monitor output signal (2) Display set frequency during Pr. 52 stop (Pr. 52) Type of Monitor During running/stop During stop During running ⋅ When Pr. 52 is set to "100", the set frequency monitor is displayed during Output Output frequency Output frequency...
  • Page 150 Monitor display and monitor output signal (4) Cumulative power monitor and clear (Pr. 170, Pr. 891) ⋅ On the cumulative power monitor (Pr. 52 = "25"), the output power monitor value is added up and is updated in 1h increments. ⋅...
  • Page 151: Reference Of The Terminal Fm (Pulse Train Output) And Am (Analog Voltage Output) (Pr. 55, Pr. 56, Pr. 291, Pr. 866, Pr. 867)

    Monitor display and monitor output signal 4.12.2 Reference of the terminal FM (pulse train output) and AM (analog voltage output) (Pr. 55, Pr. 56, Pr. 291, Pr. 866, Pr. 867) Two types of monitor output, pulse train output from the terminal FM and analog voltage output from the terminal AM, are available.
  • Page 152 Monitor display and monitor output signal *1 Not needed when the operation panel (FR-DU07) or parameter unit (FR-PU04 ) is used for calibration. /FR-PU07 This resistor is used when calibration must be made near the frequency meter for such a reason as a remote frequency meter. Note that the needle of the frequency meter may not deflect to full-scale when the calibration resistor is connected.
  • Page 153 Monitor display and monitor output signal (2) Frequency monitoring reference (Pr. 55) • Set the frequency to be based when the frequency is selected as the output of the terminal FM and terminal AM. • Set the inverter output frequency (set frequency) at which the pulse speed of the terminal FM is 1440 pulses/s (50K pulses/s).
  • Page 154: Terminal Fm, Am Calibration (Calibration Parameter C0 (Pr. 900), C1 (Pr. 901))

    Monitor display and monitor output signal 4.12.3 Terminal FM, AM calibration (Calibration parameter C0 (Pr. 900), C1 (Pr. 901)) By using the operation panel or parameter unit, you can calibrate terminal FM and terminal AM to full scale deflection. Parameter Name Initial Value Setting Range...
  • Page 155 Monitor display and monitor output signal (2) AM terminal calibration (C1 (Pr. 901)) ⋅ Terminal AM is factory-set to provide a 10VDC output in the full-scale status of the corresponding monitor item. Calibration parameter C1 (Pr. Inverter 901) allows the output voltage ratios (gains) to be adjusted according to the meter scale.
  • Page 156 Monitor display and monitor output signal (3) How to calibrate the terminal FM when using the operation panel (FR-DU07) Operation Display (When Pr. 54=1) Confirmation of the RUN indication and operation mode indication The parameter Press to choose the parameter number read setting mode.
  • Page 157: Operation Selection At Power Failure And Instantaneous Power Failure

    Operation selection at power failure and instantaneous power failure 4.13 Operation selection at power failure and instantaneous power failure Purpose Parameter that must be Set Refer to Page At instantaneous power failure Automatic restart operation Pr. 57, Pr. 58, Pr. 162 to Pr. 165, occurrence, restart inverter without after instantaneous power Pr.
  • Page 158 Operation selection at power failure and instantaneous power failure (1) Automatic restart after instantaneous power failure operation ⋅ When instantaneous power failure protection (E.IPF) and undervotage 15ms to 100ms protection (E.UVT) are activated, the inverter output is shut off. (Refer to Power page 272 for E.IPF and E.UVT.) supply...
  • Page 159 Operation selection at power failure and instantaneous power failure Without frequency search When Pr. 162 = 1, 11 (without frequency serch) When Pr. 162 = "1" or "11", automatic restart operation is performed in a reduced voltage system, where the voltage is Instaneous (power failure) time gradually risen with the output frequency unchanged from prior Power supply...
  • Page 160 Operation selection at power failure and instantaneous power failure (4) Restart coasting time (Pr. 57) ⋅ Coasting time is the time from when the motor speed is detected until automatic restart control is started. ⋅ Set Pr. 57 to "0" to perform automatic restart operation. The coasting time is automatically set to the value below. Generally this setting will pose no problems.
  • Page 161: Power Failure-Time Deceleration-To-Stop Function (Pr. 261 To Pr. 266, Pr. 294 )

    Operation selection at power failure and instantaneous power failure 4.13.2 Power failure-time deceleration-to-stop function (Pr. 261 to Pr. 266, Pr. 294 ) When a power failure or undervoltage occurs, the inverter can be decelerated to a stop or can be decelerated and re-accelerated to the set frequency.
  • Page 162 Operation selection at power failure and instantaneous power failure (3) Power failure stop mode (Pr. 261 = "1, 11") ⋅ If power is restored during power failure deceleration, deceleration to Pr.261 = 1 Power a stop is continued and the inverter remains stopped. To restart, turn supply off the start signal once, then turn it on again.
  • Page 163 Operation selection at power failure and instantaneous power failure (6) Power failure deceleration signal (Y46 signal) ⋅ After deceleration at an instantaneous power failure, inverter can not start even if the start command is given. In this case, check the power failure deceleration signal (Y46 signal). (at occurrence of input phase failure protection (E.ILF), etc.) ⋅...
  • Page 164: Operation Setting At Alarm Occurrence

    Operation setting at alarm occurrence 4.14 Operation setting at alarm occurrence Refer to Purpose Parameter that must be Set Page Recover by retry operation at alarm Retry operatoin Pr. 65, Pr. 67 to Pr. 69 occurrence Output alarm code from terminal Alarm code output function Pr.
  • Page 165 Operation setting at alarm occurrence ⋅ Using Pr. 65 you can select the alarm that will cause a retry to be executed. No retry will be made for the alarm not indicated. (Refer to page 266 for the alarm description.) indicates the errors selected for retry.
  • Page 166: Alarm Code Output Selection (Pr. 76)

    Operation setting at alarm occurrence 4.14.2 Alarm code output selection (Pr. 76) At alarm occurrence, its description can be output as a 4-bit digital signal from the open collector output terminals.The alarm code can be read by a programmable controller, etc., and its corrective action can be shown on a display, etc.
  • Page 167: Input/Output Phase Failure Protection Selection (Pr. 251, Pr. 872)

    Operation setting at alarm occurrence 4.14.3 Input/output phase failure protection selection (Pr. 251, Pr. 872) You can disable the output phase failure protection function that stops the inverter output if one of the inverter output side (load side) three phases (U, V, W) opens. The input phase failure protection function of the inverter input side (R/L1, S/L2, T/L3) can be made valid.
  • Page 168: Fault Definition (Pr. 875)

    Operation setting at alarm occurrence 4.14.6 Fault definition (Pr. 875) When motor thermal protection is activated, an alarm can be output after the motor decelerates to a stop. Initial Parameter Setting Name Description Number Range Value Normal operation Fault definition The motor decelerates to stop when motor thermal protection is activated.
  • Page 169: Energy Saving Operation And Energy Saving Monitor

    Energy saving operation and energy saving monitor 4.15 Energy saving operation and energy saving monitor Refer to Purpose Parameter that must be Set Page Pr. 52, Pr. 54, Pr. 158, How much energy can be saved Energy saving monitor Pr. 891 to Pr. 899 4.15.1 Energy saving monitor (Pr.
  • Page 170 Energy saving operation and energy saving monitor (1) Energy saving monitor list ⋅ The following provides the items that can be monitored by the power saving monitor (Pr. 52, Pr. 54, Pr. 158 = "50"). (Only 1) power saving and 3) power saving average value can be output to Pr. 54 (terminal FM) and Pr. 158 (terminal AM)) Parameter Setting Energy Saving...
  • Page 171 Energy saving operation and energy saving monitor (2) Power saving instantaneous monitor ( 1) power savings, 2) power saving rate ) ⋅ On the power saving monitor ( 1)), an energy saving effect as compared to the power consumption during commercial power supply operation (estimated value) is calculated and displays on the main monitor.
  • Page 172 Energy saving operation and energy saving monitor (5) Power estimated value of commercial power supply operation (Pr. 892, Pr. 893, Pr. 894) ⋅ Select the commercial power supply operation pattern from among the four patterns of discharge damper control (fan), inlet damper control (fan), valve control (pump) and commercial power supply drive, and set it to Pr. 894 Control selection during commercial power-supply operation.
  • Page 173 Energy saving operation and energy saving monitor (6) Annual power saving amount, power charge (Pr. 899) ⋅ By setting the operation time rate [%] (ratio of time when the motor is actually driven by the inverter during a year) in Pr. 899, the annual energy saving effect can be predicted. ⋅...
  • Page 174: Frequency Setting By Analog Input (Terminal 1, 2, 4)

    Frequency setting by analog input (terminal 1, 2, 4) 4.16 Frequency setting by analog input (terminal 1, 2, 4) Purpose Parameter that must be Set Refer to Page Function assignment of analog input Terminal 1 and terminal 4 function Pr. 858, Pr. 868 terminal assignment Selection of voltage/current input...
  • Page 175: Analog Input Selection (Pr. 73, Pr. 267)

    Frequency setting by analog input (terminal 1, 2, 4) 4.16.2 Analog input selection (Pr. 73, Pr. 267) You can select the function that switches between forward rotation and reverse rotation according to the analog input terminal selection specifications, the override function and the input signal polarity. Description Initial Setting...
  • Page 176 Frequency setting by analog input (terminal 1, 2, 4) ⋅ Refer to the following table and set Pr. 73 and Pr. 267. ( indicates the main speed setting) Compensation Input Pr. 73 Terminal 2 Terminal 1 Terminal 4 Pr. 73 Terminal and Polarity Setting...
  • Page 177 Frequency setting by analog input (terminal 1, 2, 4) (2) Perform operation by analog input voltage Inverter ⋅ The frequency setting signal inputs 0 to 5VDC (or 0 to 10VDC) to across Forward rotation the terminals 2-5. The 5V (10V) input is the maximum output frequency. The maximum output frequency is reached when 5V (10V) is input.
  • Page 178: Analog Input Compensation (Pr. 73, Pr. 242, Pr. 243, Pr. 252, Pr. 253)

    Frequency setting by analog input (terminal 1, 2, 4) 4.16.3 Analog input compensation (Pr. 73, Pr. 242, Pr. 243, Pr. 252, Pr. 253) A fixed ratio of analog compensation (override) can be made by the added compensation or terminal 2 as an auxiliary input for multi-speed operation or the speed setting signal (main speed) of the terminal 2 or terminal 4.
  • Page 179 Frequency setting by analog input (terminal 1, 2, 4) (2) Override function (Pr. 252, Pr. 253) ⋅ Use the override function to change the main speed at a fixed ratio. ⋅ Set any of "4, 5, 14, 15" in Pr. 73 to select an override. ⋅...
  • Page 180: Response Level Of Analog Input And Noise Elimination (Pr. 74, Pr. 849)

    Frequency setting by analog input (terminal 1, 2, 4) 4.16.4 Response level of analog input and noise elimination (Pr. 74, Pr. 849) Response level and stability of frequency reference command by analog input (terminal 1, 2, 4) signal can be adjusted.
  • Page 181: Bias And Gain Of Frequency Setting Voltage (Current) (Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) To C7(Pr. 905))

    Frequency setting by analog input (terminal 1, 2, 4) 4.16.5 Bias and gain of frequency setting voltage (current) (Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905)) You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting signal (0 to 5V, 0 to 10V or 0 to 20mADC).
  • Page 182 Frequency setting by analog input (terminal 1, 2, 4) (2) Change frequency maximum analog input. (Pr. 125, Pr. 126) Initial value ⋅ Set a value in Pr. 125 (Pr. 126) when changing only 60Hz the frequency setting (gain) of the maximum analog input power (current).
  • Page 183 Frequency setting by analog input (terminal 1, 2, 4) (5) Frequency setting voltage (current) bias/gain adjustment method (a)Method to adjust any point by application of voltage (current) to across the terminals 2-5 (4-5). Operation Display Confirmation of the RUN indication and operation mode indication The inverter must be at a stop.
  • Page 184 Frequency setting by analog input (terminal 1, 2, 4) (b) Method to adjust any point without application of a voltage (current) to across terminals 2-5(4-5). (To change from 4V (80%) to 5V (100%)) Operation Display Confirmation of the RUN indication and operation mode indication The inverter must be at a stop.
  • Page 185: Operation Display

    Frequency setting by analog input (terminal 1, 2, 4) (c) Method to adjust only the frequency without adjustment of a gain voltage (current). (When changing the gain frequency from 60Hz to 50Hz) Operation Display Pr. 125) or Terminal 2 input Terminal 4 input (Pr.
  • Page 186: Misoperation Prevention And Parameter Setting Restriction

    Misoperation prevention and parameter setting restriction 4.17 Misoperation prevention and parameter setting restriction Purpose Parameter that must be Set Refer to Page Limit reset function Reset selection/disconnected Make alarm stop when PU is disconnected Pr. 75 PU detection/PU stop selection Stop from PU Parameter write disable Prevention of parameter rewrite...
  • Page 187 Misoperation prevention and parameter setting restriction (2) Disconnected PU detection • This function detects that the PU (FR-DU07/FR-PU04/FR-PU07) has been disconnected from the inverter for longer than 1s and causes the inverter to provide an alarm output (E.PUE) and come to an alarm stop. •...
  • Page 188: Parameter Write Selection (Pr. 77)

    Misoperation prevention and parameter setting restriction 4.17.2 Parameter write selection (Pr. 77) You can select whether write to various parameters can be performed or not. Use this function to prevent parameter values from being rewritten by misoperation. Parameter Setting Name Initial Value Description Number...
  • Page 189: Reverse Rotation Prevention Selection (Pr. 78)

    Misoperation prevention and parameter setting restriction 4.17.3 Reverse rotation prevention selection (Pr. 78) This function can prevent reverse rotation fault resulting from the incorrect input of the start signal. Parameter Name Initial Value Setting Range Description Number Both forward and reverse rotations allowed Reverse rotation prevention selection...
  • Page 190 Misoperation prevention and parameter setting restriction (2) User group function (Pr. 160, Pr. 172 to Pr. 174) ⋅ The user group function is designed to display only the parameters necessary for setting. ⋅ From among all parameters, a maximum of 16 parameters can be registered to a user group. When Pr. 160 is set to "1", only the parameters registered to the user group can be accessed.
  • Page 191: Selection Of Operation Mode And Operation Location

    Selection of operation mode and operation location 4.18 Selection of operation mode and operation location Refer to Purpose Parameter that must be Set Page Operation mode selection Operation mode selection Pr. 79 Started in network operation mode Operation mode at power on Pr.
  • Page 192 Selection of operation mode and operation location (1) Operation mode basics ⋅ The operation mode is to specify the source of inputting the start command and set frequency of the inverter. PU operation mode ⋅ Select "external operation mode" when Operation Personnel performing operation by basically using the control...
  • Page 193: Parameter Setting

    Selection of operation mode and operation location (3) Operation mode selection flow In the following flowchart, select the basic parameter setting and terminal connection related to the operation mode. START Connection Parameter setting Operation Where is the start command source? From external (STF/STR terminal) Where is the frequency set?
  • Page 194 Selection of operation mode and operation location (4) External operation mode (setting "0" (initial value), "2") ⋅ Select the external operation mode when performing operation providing frequency setting potentiometer, start switch, etc. externally connecting them to the control circuit terminals of the inverter.
  • Page 195 Selection of operation mode and operation location (6) PU/external combined operation mode 1 (setting "3") ⋅ Select the PU/external combined operation mode 1 when making frequency setting from the operation panel (FR-DU07) or parameter unit (FR-PU04/FR- PU07) and inputting the start command with the external start switch.
  • Page 196 Selection of operation mode and operation location (8) Switch-over mode (setting "6") ⋅ While continuing operation, you can switch between the PU operation, external operation and network operation (when RS-485 terminals or communication option is used). Operation Mode Switching Switching Operation/Operating Status Select the PU operation mode with the operation panel or parameter unit.
  • Page 197 Selection of operation mode and operation location (10) Switching of operation mode by external terminal (X16 signal) ⋅ When external operation and operation from the operation panel are used together, use of the PU-external operation switching signal (X16) allows switching between the PU operation mode and external operation mode during a stop (during a motor stop, start command off).
  • Page 198 Selection of operation mode and operation location (11) Switching of operation mode by external terminal (X65, X66 signal) ⋅ When Pr. 79 = any of "0, 2, 6, 7", the operation mode switching signals (X65, X66) can be used to change the PU or external operation mode to network operation mode during a stop (during a motor stop or start command off).
  • Page 199: Operation Mode At Power On (Pr. 79, Pr. 340)

    Selection of operation mode and operation location 4.18.2 Operation mode at power on (Pr. 79, Pr. 340) When power is switched on or when power comes back on after instantaneous power failure, the inverter can be started up in network operation mode. After the inverter has started up in the network operation mode, parameter write and operation can be performed from a program.
  • Page 200: Operation Command Source And Speed Command Source During Communication Operation (Pr. 338, Pr. 339, Pr. 550, Pr. 551)

    Selection of operation mode and operation location 4.18.3 Operation command source and speed command source during communication operation (Pr. 338, Pr. 339, Pr. 550, Pr. 551) When the RS-485 terminals or communication option is used, the external operation command and speed command can be made valid.
  • Page 201 Selection of operation mode and operation location (3) Controllability through communcation Operation External/PU External/PU NET Operation NET Operation Condition Combined Combined Mode Operation External (when RS-485 (when (Pr. 551 Operation Mode Operation communication Location Operation Operation terminals are Mode 2 Setting) option is used) used)
  • Page 202 Selection of operation mode and operation location (4) Operation at alarm occurrence External/PU External/PU NET Operation Operation NET Operation Combined Combined (when Mode Alarm External (when RS-485 Operation Operation Mode communication Definition Operation Operation terminals are Condition Mode 1 option is used) used) (Pr.
  • Page 203 Selection of operation mode and operation location (5) Selection of control source in network operation mode (Pr. 338, Pr. 339) ⋅ As control sources, there are the operation command sources that control the signals related to the inverter start command and function selection and the speed command source that controls the signals related to frequency setting. ⋅...
  • Page 204 Selection of operation mode and operation location [Explanation of table] External : Control is valid only from external terminal signal. : Control only from communication is valid Combined : Control is valid from either of external terminal and communication.  : Control is invalid from either of external terminal and communication.
  • Page 205: Communication Operation And Setting

    Communication operation and setting 4.19 Communication operation and setting Refer to Purpose Parameter that must be Set Page Initial setting of computer link Communication operation from PU connector Pr. 117 to Pr. 124 communication (PU connector) Initial setting of computer link Pr.
  • Page 206: System Configuration

    Maker FA-T-RS40 Mitsubishi Electric Engineering Co., Ltd. * The converter cable cannot connect two or more inverters (the computer and inverter are connected on a 1:1 basis). Since the product is packed with the RS-232C cable and RS-485 cable (10BASE-T + RJ-45 connector), the cable and connector need not be prepared separately.
  • Page 207: Wiring And Arrangement Of Rs-485 Terminals

    Communication operation and setting 4.19.2 Wiring and arrangement of RS-485 terminals (1) RS-485 terminal layout Name Description RDA1 OPEN Inverter receive+ (RXD1+) RDB1 Inverter receive- Terminating resistor switch (RXD1-) Factory-set to "OPEN". RDA2 Inverter receive+ Set only the terminating resistor switch of (RXD2+) (for branch) 100Ω...
  • Page 208 Communication operation and setting (3) RS-485 terminal system configuration Connection of a computer to the inverter (1:1 connection) Computer Computer Inverter Inverter RS-485 RS-485 RS-485 terminals terminals Maximum RS-232C interface/ cable terminals Converter Twisted pair cable Twisted pair cable *Set the terminating resistor switch to the "100Ω" position. Combination of computer and multiple inverters (1:n connection) Station 0 Station 1...
  • Page 209 Communication operation and setting (4) RS-485 terminal wiring method Wiring of one RS-485 computer and one inverter Computer Wiring of one RS-485 computer and "n" inverters (several inverters) Compiter Station 0 Station 1 Station n Make connections in accordance with the manual of the computer used. Fully check the terminal numbers of the computer since they change with the model.
  • Page 210: Initial Settings And Specifications Of Rs-485 Communication

    Communication operation and setting 4.19.3 Initial settings and specifications of RS-485 communication (Pr. 117 to Pr. 124, Pr. 331 to Pr. 337, Pr. 341, Pr. 549) Used to perform required settings for communication between the inverter and personal computer. There are two different communications: communication using the PU connector of the inverter and communication using the RS-485 terminals.
  • Page 211: Communication Eeprom Write Selection (Pr. 342)

    Communication operation and setting [RS-485 terminal communication related parameter] Parameter Initial Name Setting Range Description Number Value RS-485 communication station Set the inverter station number. (same 0 to 31 (0 to 247) specifications as Pr. 117) number 3, 6, 12, 24, 48, Used to select the communication speed.
  • Page 212: Mitsubishi Inverter Protocol (Computer Link Communication)

    Communication operation and setting 4.19.5 Mitsubishi inverter protocol (computer link communication) You can perform parameter setting, monitor, etc. from the PU connector or RS-485 terminals of the inverter using the Mitsubishi inverter protocol (computer link communication). (1) Communication specifications ⋅ The communication specifications are given below. Related Item Description...
  • Page 213 Communication operation and setting (3) Communication operation presence/absence and data format types ⋅ Data communication between the computer and inverter is made in ASCII code (hexadecimal code). ⋅ Communication operation presence/absence and data format types are as follows: Running Parameter Inverter Parameter Operation...
  • Page 214 Communication operation and setting (4) Data definitions 1) Control codes Signal Name ASCII Code Description Start Of Text (start of data) End Of Text (end of data) Enquiry (communication request) Acknowledge (no data error detected) Line Feed Carriage Return Negative Acknowledge (data error detected) 2) Inverter station number Specify the station number of the inverter which communicates with the computer.
  • Page 215 Communication operation and setting 7) Error Code If any error is found in the data received by the inverter, its definition is sent back to the computer together with the NAK code. Error Error Item Error Description Inverter Operation Code The number of errors consecutively detected in communication Computer NAK error request data from the computer is greater than allowed number of...
  • Page 216 Communication operation and setting (6) Retry count setting (Pr. 121, Pr. 335) ⋅ Set the permissible number of retries at occurrence of a data receive error. (Refer to page 206 for data receive error for retry) ⋅ When data receive errors occur consecutively and exceed the permissible number of retries set, an inverter alarm (E.PUE) is provided and the output is shut off.
  • Page 217 Communication operation and setting (8) Instructions for the program 1) When data from the computer has any error, the inverter does not accept that error. Hence, in the user program, always insert a retry program for data error. 2) All data communication, e.g. run command or monitoring, are started when the computer gives a communication request.
  • Page 218 Communication operation and setting (9) Setting items and set data After completion of parameter setting, set the instruction codes and data then start communication from the computer to allow various types of operation control and monitoring. Number of Read/ Instruction Item Data Description Data Digits...
  • Page 219 Communication operation and setting Number of Read/ Instruction Item Data Description Data Digits Write Code (format) All parameters return to the initial values. Any of four different all clear operations are performed according to the data. Communi- Calibration Other Pr. cation Pr.
  • Page 220 Communication operation and setting List of calibration parameters Instruction code Parameter Name Read Write Extended C2(902) Terminal 2 frequency setting bias frequency C3(902) Terminal 2 frequency setting bias 125(903) Terminal 2 frequency setting gain frquency C4(903) Terminal 2 frequency setting gain C5(904) Terminal 4 frequency setting bias frequency C6(904)
  • Page 221 Communication operation and setting [Alarm data] Refer to page 265 for details of alarm description. Data Description Data Description Data Description Alarm description display example (instruction code H74) No alarm E.PTC E.MB2 E.OC1 E.OPT E.MB3 For read data H30A0 (Previous alarm ..THT) E.OC2 E.OP3 E.MB4...
  • Page 222 Communication operation and setting [Inverter status monitor] Instruction Item Description Example Code Length b0:RUN (inverter running)* [Example 1] H02 During forward b1:Forward rotation rotation b2:Reverse rotation Inverter b3:SU (up to frequency) * status 8bit b4:OL (overload) * monitor [Example 2] H80 Stop at alarm b5:IPF (instantaneous power failure) * occurrence...
  • Page 223: Modbus-Rtu Communication Specifications (Pr. 331, Pr. 332, Pr. 334, Pr. 343, Pr.539, Pr. 549)

    Communication operation and setting 4.19.6 Modbus-RTU communication specifications (Pr. 331, Pr. 332, Pr. 334, Pr. 343, Pr.539, Pr. 549) Using the Modbus-RTU communication protocol, communication operation or parameter setting can be performed from the RS-485 terminals of the inverter. Parameter Name Initial Value Setting Range...
  • Page 224 Communication operation and setting (2) Outline The Modbus protocol is the communication protocol developed by Modicon for PLC. The Modbus protocol performs serial communication between the master and slave using the dedicated message frame. The dedicated message frame has the functions that can perform data read and write. Using the functions, you can read and write the parameter values from the inverter, write the input command of the inverter, and check the operating status.
  • Page 225 Communication operation and setting (4) Message frame (protocol) Communication method Basically, the master sends a query message (question) and the slave returns a response message (response). When communication is normal, Device Address and Function Code are copied as they are, and when communication is abnormal (function code or data code is illegal), bit 7 (= 80h) of Function Code is turned on and the error code is set to Data Bytes.
  • Page 226 Communication operation and setting (5) Message format types The message formats corresponding to the function codes in Table 1 on page 216 will be explained. Read holding register data (H03 or 03) Can read the description of 1) system environment variables, 2) real-time monitor, 3) alarm history, and 4) inverter parameters assigned to the holding register area (refer to the register list (page 222)).
  • Page 227 Communication operation and setting Write multiple holding register data (H06 or 06) You can write the description of 1) system environment variables and 4) inverter parameters assigned to the holding register area (refer to the register list (page 222)). Query message 1) Slave Address 2) Function 3) Register Address 4) Preset Data...
  • Page 228 Communication operation and setting Function diagnosis (H08 or 08) A communication check can be made since the query message sent is returned unchanged as a response message (function of subfunction code H00). Subfunction code H00 (Return Query Data) Query Message 1) Slave Address 2) Function 3) Subfunction 4) Date...
  • Page 229 Communication operation and setting ⋅ Description of normal response 1) to 4) (including CRC check) of the normal response are the same as those of the query message. Example) To write 0.5s (H05) to 41007 (Pr. 7) at the slave address 25 (H19) and 1s (H0A) to 41008 (Pr. 8). Query Message Slave Starting...
  • Page 230 Communication operation and setting Error response An error response is returned if the query message received from the master has an illegal function, address or data. No response is returned for a parity, CRC, overrun, framing or busy error. CAUTION No response message is sent in the case of broadcast communication also.
  • Page 231 Communication operation and setting (6) Modbus registers System environment variable Register Definition Read/Write Remarks 40002 Inverter reset Write Any value can be written 40003 Parameter clear Write Set H965A as a written value. 40004 All parameter clear Write Set H99AA as a written value. 40006 Parameter clear Write...
  • Page 232 Communication operation and setting Real-time monitor Refer to page 137 for details of the monitor description. Register Definition Increments Register Definition Increments Register Definition Increments 40201 Output frequency 0.01Hz 0.01kW/ 0.01/ 40213 Input power 40228 Motor output 0.1kW 0.1kW 0.01A/ 40202 Output current 0.1A...
  • Page 233 Communication operation and setting Parameter Parameters Register Parameter Name Read/Write Remarks 41000 to Refer to the parameter list (page 55) for The parameter number + 41000 is the 0 to 999 Read/write 41999 the parameter names. register number. Terminal 2 frequency setting bias C2(902) 41902 Read/write...
  • Page 234 Communication operation and setting Alarm history Register Definition Read/Write Remarks 40501 Alarm history 1 Read/write 40502 Alarm history 2 Read Being 2 bytes in length, the data is stored as 40503 Alarm history 3 Read "H00 ". The error code can be referrred to in 40504 Alarm history 4 Read...
  • Page 235 Communication operation and setting (7) Pr. 343 Communication error count You can check the cumulative number of communication errors. Parameters Setting Range Minimum Setting Range Initial Value (Read only) CAUTION The number of commnication errors is temporarily stored into the RAM. As it is not stored into the EEPROM, performing a power supply reset or inverter reset clears the value to 0.
  • Page 236 Communication operation and setting (9) Signal loss detection (Pr. 539 Modbus-RTU communication check time interval) ⋅ If a signal loss (communication stop) is detected between the inverter and master as a result of a signal loss detection, a communication error (E.SER) occurs and the inverter output is shut off. ⋅...
  • Page 237: Special Operation And Frequency Control

    Special operation and frequency control 4.20 Special operation and frequency control Refer Purpose Parameter that must be Set to Page Perform process control such as pump and air Pr. 127 to Pr. 134, PID control volume. Pr. 575 to Pr. 577 Load torque high speed Increase speed when the load is light.
  • Page 238 Special operation and frequency control Parameter Setting Range Initial Name Description Number Value FR-B FR-B3 For deviation lamp input, time (Td) required for providing only the manipulated variable for the proportional (P) action. 0.01 to 10.00s As the differential time increases, greater response is made PID differential time 9999 to a deviation change.
  • Page 239 Special operation and frequency control (2) PID action overview 1) PI action A combination of P action (P) and I action (I) for providing a Deviation Set point manipulated variable in response to deviation and changes with time. Measured value [Operation example for stepped changes of measured value] P action (Note) PI action is the sum of P and I actions.
  • Page 240 Special operation and frequency control 4)Reverse action Increases the manipulated variable (output frequency) if deviation X = (set point - measured value) is positive, and decreases the manipulated variable if deviation is negative. Deviation Set point [Heating] X>0 Cold Increase Decrease X<0 point...
  • Page 241 Special operation and frequency control (4) I/O signals and parameter setting ⋅ Turn on the X14 signal to perform PID control. When this signal is off, PID action is not performed and normal inverter operation is performed. (Note that the X14 signal need not be turned on for PID control via L ORKS communication.) ⋅...
  • Page 242 Special operation and frequency control (5) PID control automatic switchover control (Pr. 127) ⋅ For a fast system startup at an operation start, the system can be started up in normal operation mode only at a start. ⋅ When the frequency is set to Pr. 127 PID control automatic switchover frequency within the range 0 to 400Hz, the system starts up in normal operation mode from a start until Pr.
  • Page 243 Special operation and frequency control (8) Adjustment procedure Adjust the PID control parameters, Pr. 127 to Pr. 134 and Pr. 575 to Pr. 577. Parameter setting Set the I/O terminals for PID control. (Pr. 178 to Pr. 189 (input terminal Terminal setting function selection), Pr.
  • Page 244 Special operation and frequency control <Set point input calibration> 1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5. 2. Enter in C2 (Pr. 902) the frequency which should be output by the inverter at the deviation of 0% (e.g. 0Hz). 3.
  • Page 245: Load Torque High Speed Frequency Control (Pr. 4, Pr. 5, Pr. 270 To Pr. 274)

    Special operation and frequency control 4.20.2 Load torque high speed frequency control (Pr. 4, Pr. 5, Pr. 270 to Pr. 274) Load torque high speed frequency control is a function <Without high-speed <With high-speed which automatically sets the operational maximum frequency control>...
  • Page 246 Special operation and frequency control (1) Load torque high speed frequency control setting · Set "2 or 3 (FR-B3 series only) " in Pr. 270 Stop-on contact/load torque high-speed frequency control selection. · When operating with the load torque high speed frequency function selection signal (X19) on, the inverter automatically changes the maximum frequency within the setting range of Pr.
  • Page 247: Droop Control (Pr. 286 To Pr. 288)

    Special operation and frequency control 4.20.3 Droop control (Pr. 286 to Pr. 288) Setting can be made only for FR-B3 series. This function is designed to balance the load in proportion to the load torque to provide the speed drooping characteristic.
  • Page 248: Frequency Setting By Pulse Train Input (Pr. 291, Pr. 384 To Pr. 386)

    Special operation and frequency control 4.20.4 Frequency setting by pulse train input (Pr. 291, Pr. 384 to Pr. 386) The inverter speed can be set by inputting pulse train from terminal JOG. In addition, synchronous speed operation of inverters can be performed by combining pulse train I/O. Setting Range Parameter Initial...
  • Page 249 Special operation and frequency control * When the wiring length of the open collector output connection is long, input pulse can not be recognized because of a pulse shape deformation due to the stray capacitances of the wiring. When wiring length is long (10m or more of 0.75mm twisted cable is recommended), connect an open collector output signal and power supply using a pull up resistance.
  • Page 250 Special operation and frequency control (4) Synchronous speed operation by pulse I/O Inverter (master) To next inverter (slave) Pull up resistance* Speed Speed Pulse train command command input To next inverter (slave) Pulse train Pulse train output output * When the wiring length between FM and JOG is long, a pulse shape is deformed due to the stray capacitances of the wiring and input pulse can not be recognized.
  • Page 251: Encoder Feedback Control (Pr. 144, Pr. 285, Pr. 359, Pr. 367 To Pr. 369)

    Special operation and frequency control 4.20.5 Encoder feedback control (Pr. 144, Pr. 285, Pr. 359, Pr. 367 to Pr. 369) This controls the inverter output frequency so that the motor speed is constant to the load variation by detecting the motor speed with the speed detector (encoder) to feed it back to the inverter.
  • Page 252 Special operation and frequency control (2) Selection of encoder feedback control (Pr. 367 ) ⋅ When a value other than "9999" is set in Pr. 367 Speed feedback range, encoder feedback control is valid. Regeneration load Speed feedback range Driven load Using the set point (frequency at which stable speed operation is performed) as reference, set the higher and Set value...
  • Page 253: Regeneration Avoidance Function (Pr. 665, Pr. 882 To Pr. 886)

    Special operation and frequency control 4.20.6 Regeneration avoidance function (Pr. 665, Pr. 882 to Pr. 886) This function detects a regenerative status and increases the frequency to avoid the regenerative status. Possible to avoid regeneration by automatically increasing the frequency and continue operation if the fan happens to rotate faster than the set speed due to the effect of another fan in the same duct.
  • Page 254 Special operation and frequency control (2) To detect the regenerative status during deceleration faster (Pr. 884) ⋅ As the regeneration avoidance function cannot respond to an abrupt voltage change by detection of the bus voltage level, the ratio of bus voltage change is detected to stop deceleration if the bus voltage is less than Pr. 883 Regeneration avoidance operation level.
  • Page 255: Useful Functions

    Useful functions 4.21 Useful functions Refer to Purpose Parameter that must be Set Page Increase cooling fan life Cooling fan operation selection Pr. 244 Inverter part life display Pr. 255 to Pr. 259 To determine the maintenance time Maintenance output function Pr.
  • Page 256: Display Of The Life Of The Inverter Parts (Pr. 255 To Pr. 259)

    Useful functions 4.21.2 Display of the life of the inverter parts (Pr. 255 to Pr. 259) Degrees of deterioration of main circuit capacitor, control circuit capacitor, cooling fan and inrush current limit circuit can be diagnosed by monitor. When any part has approached the end of its life, an alarm can be output by self diagnosis to prevent a fault. (Use the life check of this function as a guideline since the life except the main circuit capacitor is calculated theoretically.) For the life check of the main circuit capacitor, the alarm signal (Y90) will not be output if a measuring method of...
  • Page 257 Useful functions ⋅ The life alarm signal (Y90) turns on when any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current limit circuit reaches the life alarm output level. ⋅ For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) to any of Pr. 190 to Pr. 196 (output terminal function selection).
  • Page 258: Maintenance Timer Alarm (Pr. 503, Pr. 504)

    Useful functions (5) Cooling fan life display ⋅ The cooling fan speed of 40% or less is detected and "FN" is displayed on the operation panel (FR-DU07) and parameter unit (FR-PU04/FR-PU07). As an alarm display, Pr. 255 bit 2 is turned on and also an alarm is output to the Y90 signal.
  • Page 259: Current Average Value Monitor Signal (Pr. 555 To Pr. 557)

    Useful functions 4.21.4 Current average value monitor signal (Pr. 555 to Pr. 557) The average value of the output current during constant speed operation and the maintenance Output Input unit unit timer value are output as a pulse to the current Inverter average value monitor signal (Y93).
  • Page 260 Useful functions (3) Setting of Pr. 557 Current average value monitor signal output reference current Set the reference (100%) for outputting the signal of the current average value. Obtain the time to output the signal from the following formula. Output current average value ×...
  • Page 261: Free Parameter (Pr. 888, Pr. 889)

    Useful functions 4.21.5 Free parameter (Pr. 888, Pr. 889) You can input any number within the setting range 0 to 9999. For example, the number can be used: ⋅ As a unit number when multiple units are used. ⋅ As a pattern number for each operation application when multiple units are used. ⋅...
  • Page 262: Setting Of The Parameter Unit And Operation Panel

    Setting of the parameter unit and operation panel 4.22 Setting of the parameter unit and operation panel Purpose Parameter that must be Set Refer to Page Switch the display language of the PU display language selection Pr. 145 parameter unit Use the setting dial of the operation panel like a volume for frequency Operation panel operation selection...
  • Page 263 Setting of the parameter unit and operation panel (1) Using the setting dial like a volume to set the frequency. Operation example Changing the frequency from 0Hz to 60Hz during operation Operation Display Screen at powering on The monitor display appears. PU indication is lit.
  • Page 264: Buzzer Control (Pr. 990)

    Setting of the parameter unit and operation panel (2) Disable the setting dial and key operation of the operation panel (Press [MODE] long (2s)) ⋅ Operation using the setting dial and key of the operation panel can be made invalid to prevent parameter change and unexpected start and stop.
  • Page 265: Parameter Clear

    Parameter clear 4.23 Parameter clear POINT · Set "1" in Pr. CL parameter clear to initialize all parameters. (Parameters are not cleared when "1" is set in Pr. 77 Parameter write selection. In addition, calibration parameters are not cleared.) Operation Display Screen at powering on The monitor display appears.
  • Page 266: All Parameter Clear

    All parameter clear 4.24 All parameter clear POINT · Set "1" in ALLC parameter clear to initialize all parameters. (Parameters are not cleared when "1" is set in Pr. 77 Parameter write selection. In addition, calibration parameters are not cleared.) Display Operation Screen at powering on...
  • Page 267: Parameter Copy And Parameter Verification

    Parameter copy and parameter verification 4.25 Parameter copy and parameter verification PCPY Setting Description Cancel Copy the source parameters to the operation panel. Write the parameters copied to the operation panel into the destination inverter. Verify parameters in the inverter and operation panel. (Refer to page 259.) REMARKS ·...
  • Page 268: Parameter Verification

    Parameter copy and parameter verification flicker alternately Appears when parameters are copied between the inverter of or less and or more. 1. Set "0" in Pr. 160 User group read selection. 2. Set the following setting (initial value) in Pr. 989 Parameter copy alarm release. 55K or less 75K or more Pr.
  • Page 269: Check And Clear Of The Alarm History

    Check and clear of the alarm history 4.26 Check and clear of the alarm history (1) Check for the alarm (major fault) history Monitor/frequency setting Parameter setting [Operation panel is used [Parameter setting change] for operation] Alarm history [Operation for displaying alarm history] Eight past alarms can be displayed with the setting dial.
  • Page 270 Check and clear of the alarm history (2) Clearing procedure POINT · The alarm history can be cleared by setting "1" in Er.CL Alarm history clear. (The alarm history is not cleared when "1" is set in Pr. 77 Parameter write selection) Display Operation Screen at powering on...
  • Page 271 MEMO...
  • Page 272: Protective Functions

    5 PROTECTIVE FUNCTIONS This chapter describes the basic "PROTECTIVE FUNCTION" for use of this product. Always read the instructions before using the equipment 5.1 Reset method of protective function......264 5.2 List of alarm display ..........265 5.3 Causes and corrective actions ........266 5.4 Correspondences between digital and actual characters ...............278 5.5 Check first when you have troubles ......279...
  • Page 273: Reset Method Of Protective Function

    Reset method of protective function When an alarm (major failures) occurs in the inverter, the protective function is activated bringing the inverter to an alarm stop and the PU display automatically changes to any of the following error (alarm) indications. If your fault does not correspond to any of the following errors or if you have any other problem, please contact your sales representative.
  • Page 274: List Of Alarm Display

    List of alarm display 5.2 List of alarm display Operation Panel Refer Operation Panel Refer Name Name Indication Indication Output side earth (ground) E.GF E - - - Alarm history fault overcurrent HOLD Operation panel lock E.LF Output phase failure External thermal relay E.OHT Er1 to 4 Parameter write error...
  • Page 275: Causes And Corrective Actions

    Causes and corrective actions 5.3 Causes and corrective actions (1) Error Message A message regarding operational troubles is displayed. Output is not shut off. Operation Panel HOLD Indication Name Operation panel lock Description Operation lock mode is set. Operation other than is made invalid.
  • Page 276 Causes and corrective actions Operation Panel Indication Name Parameter read error Description An error occurred in the EEPROM on the operation panel side during parameter copy reading. Check point ---- ------- --- · Make parameter copy again. (Refer to page 258.) Corrective action ·...
  • Page 277 Causes and corrective actions (2) Warnings When the protective function is activated, the output is not shut off. Operation Panel FR-PU04 Indication FR-PU07 Name Stall prevention (overcurrent) When the output current of the inverter exceeds the stall prevention operation level (Pr. 22 Stall prevention operation level, etc.), this function stops the increase in frequency until During the overload current decreases to prevent the inverter from resulting in overcurrent...
  • Page 278 Causes and corrective actions Operation Panel FR-PU04 Indication FR-PU07 Name Regenerative brake pre-alarm Appears if the regenerative brake duty reaches or exceeds 85% of the Pr. 70 Special regenerative brake duty value. If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV_) occurs. The RBP signal can be simultaneously output with the [RB] display.
  • Page 279 Causes and corrective actions (4) Major fault When the protective function is activated, the inverter output is shut off and an alarm is output. Operation Panel FR-PU04 E.OC1 OC During Accs Indication FR-PU07 Name Overcurrent shut-off during acceleration When the inverter output current reaches or exceeds approximately 220% of the rated current during Description acceleration, the protective circuit is activated to stop the inverter output.
  • Page 280 Causes and corrective actions Operation Panel FR-PU04 E.OV2 Stedy Spd OV Indication FR-PU07 Name Regenerative overvoltage shut-off during constant speed If regenerative energy causes the inverter's internal main circuit DC voltage to reach or exceed the Description specified value, the protective circuit is activated to stop the inverter output. The circuit may also be activated by a surge voltage produced in the power supply system.
  • Page 281 Causes and corrective actions FR-PU04 Operation Panel E.IPF Inst. Pwr. Loss Indication FR-PU07 Name Instantaneous power failure If a power failure occurs for longer than 15ms (this also applies to inverter input shut-off), the instantaneous power failure protective function is activated to stop the inverter output in order to prevent the control circuit from malfunctioning.
  • Page 282 Causes and corrective actions FR-PU04 Operation Panel E.GF Ground Fault Indication FR-PU07 Name Output side earth (ground) fault overcurrent This function stops the inverter output if an earth (ground) fault overcurrent flows due to an earth Description (ground) fault that occurred on the inverter's output (load) side. Check point Check for an earth (ground) fault in the motor and connection cable.
  • Page 283 Causes and corrective actions Operation Panel E. 1 to FR-PU04 Fault 1 to Fault 3 Indication E. 3 FR-PU07 Name Option alarm Stops the inverter output if a contact faullt or the like of the connector between the inverter and Description communication option occurs or if a communication option is fitted to the connector 1 or 2.
  • Page 284 Causes and corrective actions E. 6 Fault 6 Operation Panel FR-PU04 E. 7 Fault 7 Indication FR-PU07 E.CPU CPU Fault Name CPU error Description Stops the inverter output if the communication error of the built-in CPU occurs. Check point Check for devices producing excess electrical noises around the inverter. ·...
  • Page 285 Causes and corrective actions Operation Panel FR-PU04 E.ECT No encoder signal Indication FR-PU07 Name Signal loss detection Stops the inverter output when the encoder signal is shut off under orientation control, encoder Description feedback control. · Check for the encoder signal loss. ·...
  • Page 286 Causes and corrective actions FR-PU04 Fault 14 Operation Panel E.SER Indication FR-PU07 VFD Comm error Name Communication error (inverter) This function stops the inverter output when communication error occurs consecutively for more than permissible retry count when a value other than "9999" is set in Pr. 335 RS-485 communication retry count Description during RS-485 communication from the RS-485 terminals.
  • Page 287: Correspondences Between Digital And Actual Characters

    Correspondences between digital and actual characters 5.4 Correspondences between digital and actual characters There are the following correspondences between the actual alphanumeric characters and the digital characters displayed on the operation panel. Actual Digital Actual Digital Actual Digital...
  • Page 288: Check First When You Have Troubles

    Check first when you have troubles 5.5 Check first when you have troubles POINT If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then reset the required parameter values and check again. 5.5.1 Motor does not start 1) Check the main circuit Check that a proper power supply voltage is applied (operation panel display is provided).
  • Page 289: Speed Greatly Differs From The Setting

    Check first when you have troubles 5.5.5 Speed greatly differs from the setting Check that the frequency setting signal is correct. (Measure the input signal level.) Check that the Pr. 1, Pr. 2, Calibration parameter C2 to C7 settings are correct Check that the input signal lines are not affected by external noise.
  • Page 290: Operation Panel (Fr-Du07) Display Is Not Operating

    Check first when you have troubles 5.5.11 Operation panel (FR-DU07) display is not operating Check that the operation panel is connected to the inverter securely. 5.5.12 POWER lamp is not lit Check that wiring is securely performed and installation is correct. 5.5.13 Parameter write cannot be performed Make sure that operation is not being performed (signal STF or STR is not ON).
  • Page 291 MEMO...
  • Page 292: Precautions For Maintenance And Inspection

    PRECAUTIONS FOR MAINTENANCE AND INSPECTION This chapter provides the "PRECAUTIONS FOR MAINTENANCE AND INSPECTION" of this product. Always read the instructions before using the equipment 6.1 Inspection item ............284 6.2 Measurement of main circuit voltages, currents and powers..............291...
  • Page 293: Inspection Item

    Inspection item The inverter is a static unit mainly consisting of semiconductor devices. Daily inspection must be performed to prevent any fault from occurring due to the adverse effects of the operating environment, such as temperature, humidity, dust, dirt and vibration, changes in the parts with time, service life, and other factors. •...
  • Page 294: Daily And Periodic Inspection

    Inspection item 6.1.3 Daily and periodic inspection Interval Corrective Action at Inspection Item Description Alarm Occurrence Surrounding Check the ambient temperature, humidity, dirt, Improve emvironment environment corrosive gas, oil mist , etc Check alarm location and General Overall unit Check for unusual vibration and noise retighten Power supply Check that the main circuit voltages and control...
  • Page 295: Display Of The Life Of The Inverter Parts

    Inspection item 6.1.4 Display of the life of the inverter parts The self-diagnostic alarm is output when the life span of the control circuit capacitor, cooling fan, each parts of the inrush current limit circuit is near to give an indication of replacement time . The life alarm output can be used as a guideline for life judgement.
  • Page 296: Cleaning

    Inspection item 6.1.6 Cleaning Always run the inverter in a clean status. When cleaning the inverter, gently wipe dirty areas with a soft cloth immersed in neutral detergent or ethanol. CAUTION Do not use solvent, such as acetone, benzene, toluene and alcohol, as they will cause the inverter surface paint to peel off. The display, etc.
  • Page 297 Inspection item (1) Cooling fan The replacement interval of the cooling fan used for cooling the parts generating heat such as the main circuit semiconductor is greatly affected by the ambient temperature. When unusual noise and/or vibration is noticed during inspection, the cooling fan must be replaced immediately.
  • Page 298 Inspection item • Reinstallation (FR-B-1500 to 75K(200V), FR-B3-(N)1500 to 37K, FR-B-2200 to 110K(400V), FR-B3-(N)H2200 to 37K) 1) After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces up. AIR FLOW <Fan side face>...
  • Page 299: Inverter Replacement

    Inspection item (2) Replacement procedure of the cooling fan when using a heatsink protrusion attachment (FR-A7CN) When replacing a cooling fan, remove a top cover of the heatsink protrusion attachment and perform replacement. After replacing the cooling fan, replace the top cover in the original position.
  • Page 300: Measurement Of Main Circuit Voltages, Currents And Powers

    Measurement of main circuit voltages, currents and powers 6.2 Measurement of main circuit voltages, currents and powers Since the voltages and currents on the inverter power supply and output sides include harmonics, measurement data depends on the instruments used and circuits measured. When instruments for commercial frequency are used for measurement, measure the following circuits with the instruments given on the next page.
  • Page 301 Measurement of main circuit voltages, currents and powers Measuring points and instruments Measuring Item Measuring Instrument Remarks (Reference Measured Value) Point Across R/L1-S/ Commercial power supply Power supply voltage L2, S/L2-T/L3, T/ Moving-iron type AC voltmeter Within permissible AC voltage fluctuation L3-R/L1 (Refer to page 298) Power supply side...
  • Page 302: Measurement Of Powers

    Measurement of main circuit voltages, currents and powers 6.2.1 Measurement of powers Using an electro-dynamometer type meter, measure the power in both the input and output sides of the inverter using the two- or three-wattmeter method. As the current is liable to be imbalanced especially in the input side, it is recommended to use the three-wattmeter method.
  • Page 303: Measurement Of Currents

    Measurement of main circuit voltages, currents and powers 6.2.3 Measurement of currents Use a moving-iron type meter on both the input and output sides of the inverter. However, when using the FR-B3 series low noise type, do not use that meter since an eddy-current losses produced in the internal metal parts of the meter will increase and the meter may burn out.
  • Page 304: Measurement Of Converter Output Voltage (Across Terminals P/+ - N/-)

    Measurement of main circuit voltages, currents and powers 6.2.6 Measurement of converter output voltage (across terminals P/+ - N/-) The output voltage of the converter is developed across terminals P/+ - N/- and can be measured with a moving-coil type meter (tester). Although the voltage varies according to the power supply voltage, approximately 270V to 300V (approximately 540V to 600V for the 400V class) is output when no load is connected and voltage decreases when a load is connected.
  • Page 305 MEMO...
  • Page 306: Specifications

    7 SPECIFICATIONS This chapter provides the "SPECIFICATIONS" of this product. Always read the instructions before using the equipment 7.1 FR-B Series Specifications........298 7.2 FR-B3 Series Specifications........300 7.3 Outline dimension drawings ........302...
  • Page 307: Fr-B Series Specifications

    FR-B Series Specifications 7.1 FR-B Series Specifications 7.1.1 FR-B series ratings FR-B series (suitable for inverter drive reduced-torque explosion-proof type motor) 200V class 1500 2200 3700 5.5K 7.5K Type FR-B- 60Hz standard 0.4 0.75 reduced-torque 50Hz standard reduced-torque Applicable motor capacity (kW) *1 60Hz standard constant torque...
  • Page 308: Fr-B Series Common Specifications

    FR-B Series Specifications 7.1.2 FR-B series common specifications Control method Sine wave PWN control (V/F constant control) Output frequency range 0.2 to 120Hz (22K or less), 0.2 to 60Hz (30K or more) 0.015Hz/0 to 60Hz (terminal 2, 4: 0 to 10V/12bit) Frequency Analog input 0.03Hz/0 to 60Hz (terminal 2, 4: 0 to 5V/11bit, 0 to 20mA/about 11bit, terminal 1: 0 to ±10V/12bit)
  • Page 309: Fr-B3 Series Specifications

    FR-B3 Series Specifications 7.2 FR-B3 Series Specifications 7.2.1 FR-B3 series ratings FR-B3 series (suitable for inverter drive constant-torque explosion-proof type motor) 200V class 1500 2200 3700 18.5 Type FR-B3-(N)- Applicable motor capacity (kW) 0.75 18.5 Rated capacity (kVA) 12.6 17.6 23.3 Rated current (A) 17.5...
  • Page 310: Fr-B3 Series Common Specifications

    FR-B3 Series Specifications 7.2.2 FR-B3 series common specifications Control method Soft-PWM control/high carrier frequency PWM control (selectable from among, advanced magnetic flux vector control). Output frequency range 0.2 to 120Hz 0.015Hz/0 to 60Hz (terminal 2, 4: 0 to 10V/12bit) Frequency Analog input 0.03Hz/0 to 60Hz (terminal 2, 4: 0 to 5V/11bit, 0 to 20mA/about 11bit, terminal 1: 0 to ±10V/12bit) setting...
  • Page 311: Outline Dimension Drawings

    Outline dimension drawings 7.3 Outline dimension drawings 7.3.1 Inverter outline dimension drawings FR-B-750 (200V class), FR-B3-(N)400, 750 2-φ6 hole Inverter Type FR-B3-(N)400 FR-B-750, FR-B3-(N)750 Unit: mm FR-B-1500 to 3700 (200V class), FR-B3-(N)1500 to 3700 FR-B-750 to 3700 (400V class), FR-B3-(N)H400 to 3700 2-φ6 hole * The FR-B-750,1500, FR-B3-(N)H 400 to...
  • Page 312 Outline dimension drawings FR-B-5.5K to 11K(200V class), FR-B3-(N)5.5K to 11K FR-B-7.5K,15K(400V class), FR-B3-(N)H5.5K to 15K 2-φ6 hole Inverter Type FR-B-5.5K, 7.5K (200V), FR-B-7.5K (400V) FR-B3-(N)(H)5.5K, 7.5K FR-B-11K(200V), FR-B-15K(400V) 101.5 FR-B3-(N)(H)11K, 15K Unit: mm FR-B-15K,22K(200V class), FR-B3-(N)15K to 22K FR-B-22K(400V class), FR-B3-(N)H18.5K, 22K 2-φ10 hole 10.5 Unit: mm...
  • Page 313 Outline dimension drawings FR-B-30K to 55K (200V class), FR-B3-(N)30K, 37K FR-B-37K, 55K (400V class), FR-B3-(N)H30K, 37K 2-φd hole Inverter Type FR-B-30K (200V/400V) FR-B3-(N)(H)30K FR-B-37K, 45K (200V), FR-B-37K, 55K (400V) FR-B3-(N)(H)37K FR-B-55K (200V) Unit: mm FR-B-75K, 90K (400V class) DC reactor supplied 2-φ12hole Rating plate 2-terminal...
  • Page 314 Outline dimension drawings FR-B-75K (200V class) FR-B-110K (400V class) 2-φ12 hole DC reactor supplied Rating plate 2-terminal (for M12 bolt) 4-installation hole (for S screw) Within Earth (ground) terminal (for M6 screw) DC Reactor Type Mass (kg) FR-HEL-75K (FR-B-75K) FR-HEL-H110K (FR-B-110K) Unit: mm...
  • Page 315: Outline Drawing

    Outline dimension drawings Operation panel (FR-DU07) <Outline drawing> <Panel cutting dimension drawing> Panel 27.8 FR-DU07 3.2max Air- bleeding hole Cable 2-M3 screw Operation panel connection connector (FR-ADP) Unit: mm Parameter unit (option) (FR-PU07) <Outline drawing> <Panel cutting dimension drawing> 25.05 (14.2) (11.45) Air-bleeding...
  • Page 316 APPENDICES This chapter provides the "APPENDICES" of this product. Always read the instructions before using the equipment.
  • Page 317 For customers who have replaced the older model with this inverter Appendix 1 For customers who have replaced the older model with this inverter Appendix 1-1 Replacement of the FR-B,B3 series (A500 specifications) (1) Instructions for installation 1)Removal procedure of the front cover was changed. (with screws) Please note. (Refer to page 6.) 2)Removal procedure of the operation panel was changed.
  • Page 318 For customers who have replaced the older model with this inverter (4) Main differences between the explosion proof inverter and standard inverter Specifications FR-B3-(N) (FR-A700 specifications) FR-A700 200V class 200V 50Hz 200/220V 60Hz 200V to 220V 50Hz 200V to 240V 60Hz Power supply voltage 400V class...
  • Page 319 Appendix 2 Control mode-based parameter (function) correspondence table and instruction code list These instruction codes are used for parameter read and write by using Mitsubishi inverter protocol with the RS-485 communication. (Refer to page 201 for RS-485 communication) Validity and invalidity according to operation mode are as follows: :Usable parameter ×...
  • Page 320 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control Speed display Up-to-frequency sensitivity Output frequency detection Output frequency detection for reverse rotation Second acceleration/ deceleration time Second deceleration time Second stall prevention operation current Second stall prevention operation frequency...
  • Page 321 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control × Motor rated voltage × Rated motor frequency Speed control gain (magnetic × × flux vector) × × Motor constant (R1) × × Motor constant (R2) ×...
  • Page 322 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control Speed setting switchover × × PU display language selection Stall prevention level at 0V input Stall prevention level at 10V input Output current detection level Output current detection signal delay time Zero current detection level...
  • Page 323 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control × IPF terminal function selection × OL terminal function selection × FU terminal function selection × ABC1 terminal function selection × ABC2 terminal function selection Multi-speed setting (speed 8) Multi-speed setting (speed 9) Multi-speed setting (speed 10)
  • Page 324 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control Stop-on contact excitation × current low-speed multiplying factor × Brake opening frequency × Brake opening current Brake opening current detection × time × Brake operation time at start ×...
  • Page 325 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control DO6 output selection RA1 output selection RA2 output selection RA3 output selection × AM0 0V adjustment × AM1 0mA adjustment × Digital input unit selection RS-485 communication station RS-485 communication speed RS-485 communication stop bit...
  • Page 326 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control Orientation position loop gain Completion signal output delay time Encoder stop check time Orientation limit Recheck time Speed feedback range Feedback gain Number of encoder pulses Overspeed detection level Encoder signal loss detection enable/disable selection...
  • Page 327 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control S-pattern time at a start of deceleraiton S-pattern time at a completion of deceleraiton Modbus-RTU commnunication check time interval Frequency command sign selection (CC-Link) Communication station number (CC-Link) Baud rate (CC-Link)
  • Page 328 Instruction Model based Correspondence Table Code FR-B FR-B3 Parameter Name Advanced magnetic flux V/F Control vector control Regeneration avoidance compensation frequency limit value Regeneration avoidance voltage gain × × Free parameter 1 × × Free parameter 2 Cumulative power monitor digit shifted times Load factor Energy saving monitor reference...
  • Page 329 REVISIONS *The manual number is given on the bottom left of the back cover. Print Date Revision Manual Number May., 2006 IB(NA)-0600272ENG-A First edition For Maximum Safety • Mitsubishi inverters are not designed or manufactured to be used in equipment or systems in situations that can affect or endanger human life.

Table of Contents