In the Alarm Verific menu, you set the times within which the
user must confirm a triggered alarm (ACK Within). The Invest
Time submenu specifies the time available to the user to enter
the alarm triggering area before the notification appliance is
activated. You can also use NAC 1 to specify whether:
Time setting for alarm acknowledgement
2
2
1
1
Time setting for verification time
2
2
Bosch Sicherheitssysteme GmbH
Alert switches NAC 1 on immediately in the event of an
alarm. NAC 1 is then switched off during the verification
time and switched on again after the verification time.
With Evacuate, NAC 1 is switched off during the delay time
and only activated during the actual alarm.
Press zone key 2. This takes you to the Delay Config
menu.
Press zone key 2.
This takes you to the Alarm Verific submenu.
Press zone key 1.
This takes you to the ACK Within submenu.
Use the zone keys to set the respective delay.
4
1 30 s
...
2= 60 s (default setting)
3 90 s
4 120s
Press zone key 2. This takes you to the Delay Config
menu.
Press zone key 2.
This takes you to the Alarm Verific submenu.