Download Print this page

KitchenAid electric dryer Installation Instructions page 3

Advertisement

B
If local codes DO NOT permit
n
cabinet groundmg to the
k?ufral wire of the power supply co?d:
I. Remove terminal block cover.
WARNING: Potential Fire Hazard
Exhaust Systems longer than
specified will:
m Accumulate
lint.
) Shorten the life of the dryer.
m Reduce the performance
in ways
such as causing longer drying times
and increasing the use of energy.
The back pressure in any exhaust
system used must not exceed 0.6
inches of water column measured
with an inclined manometer at the
point that the exhaust system
connects to the dryer.
2. Attach a %: U.L.-listed strain relief
(U.L. marked on it) to the dryer
through the power supply cord hole
See Figure 4. Tighten strain relief
firmly to cabinet. Place the power
supply cord or direct wire through
the strain relief. Tighten screws on
strain relief.
I. Remove the grounding wire (green)
from the external grounding
connector and fasten under center
silver-colored
terminal block screw.
Conned
separate
copper
grounding
wire
,rom srlernal
grounding
conneclor
lo aDPro"%d
WO""d
6. Replace the i&minal block cover by
first installino the tab of the cover
For Mobile Home installation, the dryer
must
have an outside exhaust. If you
into the slot of the dryer rear panel
See Figure 3. Secure the cover
with the mounting screw.
7. Tighten strain relief clamp on power
supply cord. See Figure 4.
exhaust the dryer through the fl
and the area under your mobile
home is enclosed, the exhaust
system must terminate outslde
the enclosed area. Extension
beyond the enclosure will
orevent lint and moisture
-
Ungrounded
neutral
Exhaust
Requkments
build-up under the mobile home.
There are Exhaust Kits available that
allow you to direct filtered exhaust air
inside to conserve energy during the
winter months. Whirlpool has a Heat-
Humidity Saver Part No. 279427 which
can be used with Whirlpool dryers
providing their use does not violate
local codes. If you use one of these
kits, be aware that excessive moisture
in the home can cause many problems
and that you may see an increase in
the time required to dry a load. Also,
you must regularly clean the filter to
avoid excessive lint build-up which can
affect the dryer's performance.
WARNING:
Potential
Fire Hazard
l
Metal llexible duct may be used.
Do Not use non-metallic flexible duct
smce it is a potential fire hazard.
For Safety:
l
Do not exhaust dryer into a chimney,
furnace cold air duct, attic or crawl
4. Connect the neutral wire of the
power supply cord to the center
silver-colored
terminal of the
terminal block and connect the other
wires to the outer termmals. See
Figure 8. For connecting plain-end
field wire see Figure 6.
5. Connect a separate copper
groundmg wire (No. 10 minimum) lo
a grounded cold water pipe* by
means of a clamo and then lo the
frame of the appiiance at the
external grounding connector. Use
Part No. 665463 aroundina wire and
clamp assembly.&
not g;ound to
a gas supply pipe or hot water pipe.
Do not connect the power supply
cord to electric Dower SUDDIV until
space, or any other duct used for
ventina. Accumulated
lint could
becomk a fire hazard or moisture
could cause damage.
l
Clean the exhaust system
periodically, at least every 2 years.
l
Never install flexible duct
concealed in walls,
RecessedAma
INSTRUCTIONS
FOR RECESSED OR
CLOSET INSTALLATIONS
The following installation spacings and
door air openings for the dryer are
possible when installed and exhausted
as noted. (Spacing as indicated is In
inches and is minimum allowable.
For ease of installation and service.
additional spacing should be
considered.)
Exhaustlng the dryer outside is
recommended.
If you cannot exhaust
the dryer to the outside, use Exhaust
Deflector Kit LCK4000 available
from your KitchenAid dealer.
Outlet is located at the v
center of the bonom drver back.
,AJL24h
The Exhaust Duct can be route
up. down, left, right or straight
out the back of the dryer.
Metal Flexible Duct must
fully extended and suppo
when the dryer is in its iinal
position. DO NOT KINK OR
CRUSH THE DUCT.
An Exhaust Hood should ca
exhaust duct to prevent exhausted air
from returning into dryer. The outlel of
the hood must be at least 12 inches
from the ground or anything else that
may be in the path of the exhaust.
A 2% inch outlet Exhaust Hood should
TO PREVENT LARGE AMOUNTS OF
LINT AND MOISTURE FROM
ACCUMUlATING
AND TO MAINTAIN
DRYING EFFICIENCY, THIS MACHINE
MUST BE EXHAUSTED
OUTDOORS.
Unobstructed air openings are required
for laundry equipment when door is
installed. Closet installation must be
exhausted. Only recessed installation
with no cabinet or shelf above the dryer
can be non-exhausted.
Non-exhausted
recessed installations require an
exhaust deflector.
7. Tighten strain relief clamp on power
supply cord. See Figure 4.
C
If connecting to a
four-wire electrical
n system (mobile home):
1. Remove the terminal block cover by
removing Ihe screw shown in Figure 3.
2. Attach a %:' U.L.-listed strain relief
(U-L. marked on it) to the dryer
through the power supply cord hole.
See Figure 4. Tighten strain relief
firmlv to cabinet. Place the oower
supply cord or direct wire thorough
the strain relief. Tighten screws on
strain relief.
be used with short systems only. (This
outlet creates areater back oressure
than other ho& types.)
'
Exhaust Hoods with magnetic latches
should not be used.
The Maximum Length of the exhaust
system depends upon the type of duct,
number of elbows and lype.&f exhaust
hood. The maximum lenath for both
rigid and llexible duct is <hewn in chart.
i
lr-
t
3. Remove grounding wire (green) from
the external groundmg connector
and fasten under center silver-
colored terminal block screw,
4. Connect the grounding wire (green)
of the power supply cord to the
external groundmg connector.
5. Connect the neutral wire (white) of
the power supply cord to the center
silver-colored terminal 01 the
terminal block and connect the other
wires lo the outer terminals. See
Figure 10. For connecting plain-end
field wire, see Figure 6
*".I"
mmmum
from dryer cabfnel
rear panel lo wall
0s requred
lo, chxel
lnSlal,allO"
0, non-
exhausled
~ns,allat,on.
>ompanion appliance spacings should
ze considered.
Jetailed space requirements can be
'ound on the label located on the back
Jane1 of dryer.

Advertisement

loading