Outputs - Bosch ICP-EZM2 Installer's Manual

Intrusion control panel
Hide thumbs Also See for ICP-EZM2:
Table of Contents

Advertisement

.
4.2.3

Outputs

You cannot program any wireless outputs without first completing the steps in Section 1.4 System
Setup on page 5
Output devices consist of horns, bells, or strobes.
Outputs
Enter an output number from 1 to 8.
1
Output Function
Press [1] to
select the current
option.
Press [2] to hear
more options.
Press [#] to exit
Output Function.
#
Exit Outputs
Return to the Installer Menu.
Record output programming entries in Section 4.3.6 Output Programming Items on page 51.
Bosch Security Systems, Inc. | 5/07 | F01U025147-01
Easy Series (ICP-EZM2) | Installer Guide | 4.0 Programming
Output Function
Description
Disabled
Output is disabled.
Intrusion
Output turns on when intrusion alarm occurs. To turn off output,
turn off system, or wait until end of intrusion bell cut-off time.
Intrusion Latching
Output turns on when intrusion alarm occurs. To turn off output,
turn off system.
Fire
Output turns on when a fire alarm occurs. To turn off output, turn off
system if it is already on, or wait until end of fire bell cut-off time.
Fire Latching
Output turns on when a fire alarm occurs. To turn off output, turn off
system if it is already on, or acknowledge alarm if system is off.
Intrusion and Fire
Output turns on when an intrusion or fire alarm occurs. To turn off
output, turn off system, or wait until end of bell cut-off time. Fire
alarms take priority over intrusion alarms.
Intrusion and Fire
Output turns on when an intrusion or fire alarm occurs. To turn off
Latching
output, turn off system if it is already on, or acknowledge alarm if
system is off. Fire alarms take priority over intrusion alarms.
System Reset
Output is normally on. Output turns off for approximately 10 sec
when system is reset. Use this function to supply power to devices
such as four-wire smoke detectors that require power interruption
to reset a latching alarm condition.
System On
Output turns on when the system is turned on, and remains on until
system is turned off.
System Ready
Output turns on when the system is ready to turn on (no faulted
points or system troubles exist).
Key Fob On/Off
Output turns on or off when the user presses the key fob's
key.
Refer to Expert Programming Item Numbers 616 and 626 on page
40 for more information.
Key Fob 2-sec
Output turns on for two seconds when the user presses the key
Pulse
fob's
Refer to Expert Programming Item Numbers 616 and 626 on page
40 for more information.
User Controlled
Output turns on or off when a user or the installer uses the Operate
Outputs option from the phone menus.
or
key.
or
33

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents