GE Digital Energy 1018959 Operating Manual page 49

Digital energy snmp / web adapter
Hide thumbs Also See for Digital Energy 1018959:
Table of Contents

Advertisement

Address
Type
Word
Word 2
1
30X08
30X09
FLOAT
30X10
30X11
FLOAT
30X12
30X13
FLOAT
30X14
30X15
FLOAT
30X16
30X17
FLOAT
30X18
30X19
FLOAT
30X20
30X21
FLOAT
30X22
30X23
FLOAT
30X24
30X25
FLOAT
30X26
30X27
FLOAT
30X28
30X29
FLOAT
30X30
30X31
FLOAT
30X32
30X33
FLOAT
30X34
30X35
FLOAT
30X36
30X37
FLOAT
30X38
30X39
FLOAT
30X40
30X41
FLOAT
30X42
30X43
FLOAT
30X44
30X45
FLOAT
30X46
30X47
FLOAT
30X48
30X49
FLOAT
30X50
30X51
FLOAT
30X52
30X53
FLOAT
30X54
30X55
FLOAT
30X56
30X57
FLOAT
30X58
30X59
FLOAT
30X60
30X61
FLOAT
30X62
30X63
FLOAT
30X64
30X65
FLOAT
30X66
30X67
FLOAT
30X68
30X69
FLOAT
30X70
30X71
FLOAT
30X72
30X73
FLOAT
30X74
30X75
FLOAT
30X76
30X77
FLOAT
30X78
30X79
FLOAT
30X80
30X81
FLOAT
30X82
30X83
FLOAT
30X84
30X85
FLOAT
30X86
30X87
FLOAT
Modifications reserved
OPM_CNT_SNM_BAS_CRD_1GB_V014.doc
Description
Input Frequency L1
Input Voltage L1
Input Current L1
Input True Power L1
Input Frequency L2
Input Voltage L2
Input Current L2
Input True Power L2
Input Frequency L3
Input Voltage L3
Input Current L3
Input True Power L3
Output Frequency
Output Voltage L1
Output Current L1
Output Power L1
Output Percent Load L1
Output Voltage L2
Output Current L2
Output Power L2
Output Percent Load L2
Output Voltage L3
Output Current L3
Output Power L3
Output Percent Load L3
Bypass Frequency
Bypass Voltage L1
Bypass Current L1
Bypass Power L1
Bypass Voltage L2
Bypass Current L2
Bypass Power L2
Bypass Voltage L3
Bypass Current L3
Bypass Power L3
Est. Minute Remaining
Est. Charge Remaining
Battery Voltage
Battery Current
Battery Temperature
Notes
The present input frequency. Units: Hertz
The present input voltage, RMS value. Units: Volts
The present input current, RMS value. Units: Amp
The present input true power. Units: Watts
The present input frequency. Units: Hertz
The present input voltage, RMS value. Units: Volts
The present input current, RMS value. Units: Amp
The present input true power. Units: Watts
The present input frequency. Units: Hertz
The present input voltage, RMS value. Units: Volts
The present input current, RMS value. Units: Amp
The present input true power. Units: Watts
The present output frequency. Units: Hertz
The present output voltage, RMS value. Units: Volts
The present output current, RMS value. Units: Amp
The present output true power. Units: Watts
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the
percent load of true power capacity and the percent
load of VA.
The present output voltage, RMS value. Units: Volts
The present output current, RMS value. Units: Amp
The present output true power. Units: Watts
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the
percent load of true power capacity and the percent
load of VA.
The present output voltage, RMS value. Units: Volts
The present output current, RMS value. Units: Amp
The present output true power. Units: Watts
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the
percent load of true power capacity and the percent
load of VA.
The present bypass frequency. Units: Hertz
The present bypass voltage, RMS value. Units: Volts
The present bypass current, RMS value. Units: Amp
The present bypass true power. Units: Watts
The present bypass voltage, RMS value. Units: Volts
The present bypass current, RMS value. Units: Amp
The present bypass true power. Units: Watts
The present bypass voltage, RMS value. Units: Volts
The present bypass current, RMS value. Units: Amp
The present bypass true power. Units: Watts
An estimate of the time to battery charge depletion
under the present load conditions if the utility power is
off and remains off, or if it were to be lost and remain
off. Units: Minutes
An estimate of the battery charge remaining
expressed as a percent of full charge.
The present battery voltage. Units: Volts
The present battery current (into battery). Units: Amp.
Positive values for currents going into the battery.
The ambient temperature at or near the UPS Battery
casing. Units: degrees centigrade (°C)
Page 49/69
Operating Manual SNMP/Web Adapter