Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
6.1.1.1
3312FL
Figure 7. An example of a Win128 dialog box is the "Analog
photo electric smoke detector 4301" properties dialog box.
For more information, see Win128 help.
Connections, if nothing else is specified, see drawing 128-21.
Analog Sensor Bases (ASB)
3312 Analog Base. An analog detector (Sensor) is to be plugged in
3312. Terminals for ext. LED 2217 / 2218. Prepared for
mechanical lock of the detector. Recess for label holder 3391.
The base has an address label on which the plugged-in
detector's technical address is to be written.
3313 Analog Base. Like 3312 but instead of screw terminals for the
COM loop and ext. LED this base has fast connectors.
3314 Analog Base. Like 3312FL but no connector for ext. LED.
3312F
4313 Analog Base with isolator. An analog detector (Sensor) is to be
plugged in 4313.
Prepared for mechanical lock of the detector. Recess for label
holder 3391. It has also a built-in short circuit isolator with the
same function as the Addressable short circuit isolator 4370
(see page 42). The isolator's technical address is set with an
Address setting tool (AST) 3314. The base has an address label
on which both the plugged-in detector's technical address and
the isolator's technical address are to be written.
The Address setting tool 3314 is also used for mode setting:
NORMAL mode: Used for 4313 in EBL128.
EBL128 Planning Instructions V1.1.x
Terminals for ext. LED 2217 / 2218.
32