Detail Of Input And Output Signals - Toshiba TOSVERT VF-S15 series Function Manual

Tosvert vf-s15 series cc-link option unit
Hide thumbs Also See for TOSVERT VF-S15 series:
Table of Contents

Advertisement

5.5.6. Detail of input and output signals

1. Output signals (Master -> Inverter)
The output signals from the master unit are indicated. (Input signals to inverter)
Device No.
RYn0
Forward run command
RYn1
Reverse run command
RYn2
Input terminal function 3(S1)
RYn3
Input terminal function 4(S2)
RYn4
Input terminal function 5(S3)
RYn5
Input terminal function 6(S4)
RYn6
Input terminal function (PIOFF)
RYn7
Input terminal function 8(AD1)
RYn8
Input terminal function 9(ESTP)
Intercept output to inverter
RYn9
(Coast stop)
Frequency priority CC-Link
RYnA
Command priority CC-Link
RYnB
Monitor command
RYnC
Frequency setting command
RYnD
(RAM)
RYnE
Reserved**
RYnF
Instruction code execution request
RY(n+1)0
Reserved**
to Y(n+1)9
RY(n+1)A
Error reset request
RY(n+1)B
Reserved**
to RY(n+1)F
"n" is depend on the station number.
* The input terminal function can be changed by the input terminal function selections(
(But there are functional restrictions. Refer to the following page.)
** Set OFF ("0") to reserved bit.
***When RYn0 and RYn1 are ON simultaneously, the rotation is followed a parameter f105(default = stop).
Signal
OFF: Stop command ON: Forward run command***
OFF: Stop command ON: Reverse run command***
The function depends on input terminal selection 3 (c142) *
The function depends on input terminal selection 4 (c143) *
The function depends on input terminal selection 5 (c144) *
The function depends on input terminal selection 6 (c145) *
The function depends on input terminal selection 7 (c146) *
The function depends on input terminal selection 8 (c147) *
The function depends on input terminal selection 9 (c148) *
Stop the output of the inverter when turned on this signal.
(Stop the output in the secondary circuit)
Speed commands are entered from the CC-Link.
Signals from the CC-Link are used to start and stop operation
When the monitor command (RYnC) is switched on, each
monitored values are set to remote registers RWrn, RWrn+1,
RWrn+4 to RWrn+7 and monitoring flag (RXnC) switches on.
While the monitor command (RYnC) is on, the monitored
value is always updated.
When the frequency setting command (RYnD) is switched
on, the set frequency RWwn+1 is written to the inverter.
After the writing completion, frequency setting completion flag
(RXnD) switches on.
When the frequency setting command (RYnD) is ON, the set
frequency is always updated.
Reserved**
When the instruction code execution request (RYnF) is
switched on, processes corresponding to the instruction codes
are set to RWwn+2, RWwn+10, RWwn+12, RWwn+14,
RWwn+16 and RWwn+18 are executed.
After completion of instruction code execution, instruction code
execution completion flag (RXnF) switches on.
When an instruction code execution error occurs, a value other
than 0 is set to the reply code (RWrn+2, RWrn+10, RWrn+12,
RWrn+14, RWrn+16 and RWrn+18)
The instruction code execution request is effective only when
this signal changes from OFF to ON.
Special monitor (72H) is chosen by the instruction code, and
this signal always updates a monitor value during ON.
Reserved**
If the error reset request (RY(n+1)A) is switched on only
when an inverter fault occurs, the inverter is reset and the
error status flag (RX(n+1)A) switches off.
Reserved**
- 21 -
Description
c142 to c148
E658130
).