Mounting

5.1

Overview of mounting

Figure 5-1 SICLOCK TC100 - view of mounting
SICLOCK TC100 must be mounted in an easily accessible position in the control
cabinet.
The housing can be fixated by snap-on mounting to a standard mounting rail
(EN 50022-35) or to a SIMATIC S5 DIN rail (6ES5 710-8maxx).
A clearance of 100mm must be maintained above the device so that it can be
hooked in and out, and to facilitate unimpeded heat dissipation.
A clearance of at least 100mm must be maintained under the device for the pro-
cess signal plug.
We recommend mounting a suitable cable channel below this clearance.
Note
Ensure that the snap-on mounting is locked correctly.
See also Dimension drawing (Chapter 14).