Programmable controllers ethernet module

Advertisement

When R0621 is set to ON, 100 data words are received from the sender (IP address =
192.0.0.5, Port number = 5000) and are stored in D2000 to D2099. When the operation is
finished, R0621 is reset to OFF automatically.
UDP Socket Close SEND instruction is used.
A: H3100 (fixed)
A+1: UDP close command (H0034)
A+2: Socket number (1 to 12)
Sample program
12544 = H3100
52 = H0034
Socket number =1
When R0623 is set to ON, the UDP socket is closed. When the operation is finished, R0623 is
reset to OFF automatically.
[ A SEND B ]▬
B: Result status
B+1: Error code
Page
8