Terminal Marking; Protection Of Compensation Reactor And Drain Coil; Cvt Grounding - GE OTCF Instruction Manual

Capacitor voltage transformer
Table of Contents

Advertisement

Instruction Manual
If the carrier system is not connected
to the HF terminal during operation,
the carrier grounding switch must
remain at the "Closed" position. See
item 5.9.

5.5. Terminal marking

The marking of the primary and
secondary terminals is done according
to the specified standard for the
project. Check the markings on the
set of approved drawings.
The wiring diagram for the secondary
terminals are those shown on the
drawings.
5.6. Protection of compensation reactor
and drain coil
To
provide
overvoltages arising from voltage
fluctuations in the CVT, protection
sparkers
are
compensation reactor and the drain
coil and are located in the secondary
© GE Grid Solutions
protection
against
supplied
to
the
terminal box.
These sparkers may be of two types:
Spark gap: Air insulation with
preset factory setting. Refer to
the CVT secondary terminal box
drawing for more details.
This setting cannot be modified
on-site.
Spark gap type example
Encapsulated: Gas insulation
with pre-set operating voltage.
Refer to the CVT secondary
terminal box drawing for more
details on which type is used.
Encapsulated type example

5.7. CVT grounding

The CVT tank has two grounding
points located on the tank's own
body. At least one of the points must
be connected to the substation
earthing system using appropriate
cables.