X22 Terminals: Smart Line Module - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Note
The Smart Line Module signals ready-to-operate, even though one of the external
conductors is not available. In this case the feedback is deactivated and a warning message
is output to X21/2 (DO, Warning I*t). If the feedback was deactivated by applying a "High"
signal to terminal X22/2 (DI, Disable), no warning message will be output to X21/2 (DO,
Warning I*t).
Note
For operation, 24 V DC must be connected to terminal 3 and ground to terminal 4. When
removed, pulse inhibit is activated, feedback is deactivated and the bypass relay drops out.
If the Line Module is not disconnected from the line supply when the EP terminal is
deactivated (e.g. a main contactor is not installed), the DC link remains charged.
NOTICE
If a drive line-up is switched off by means of the line disconnecting device, the voltage at
terminals 3 (EP +24 V) and 4 (EP M) must be interrupted beforehand. This can be carried
out using a leading breaking auxiliary contact (≥ 10 ms), for example.
This protects external loads located parallel to the drive on the same switching component.
3.5.3.5

X22 terminals: Smart Line Module

Table 3-39
Terminal block X22
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm
Type: Screw terminal 1 (see Connection Engineering section)
Booksize power units
Manual, (GH2), 06/2008, 6SL3097-2AC00-0BP6
3.5 Smart Line Modules (5 kW und 10 kW) with internal air cooling
Designation
24 V power supply
DI: Disable Regeneration
DI: Reset
Ground
2
Technical specifications
Electronics power supply for controlling digital inputs
X22.2 and 3.
Deactivate feedback (high active).
No power is supplied back to the network from the DC
link. The regenerative energy of the motors may have
to be reduced using a combination of the Braking
Module and braking resistor.
Reset faults (positive edge)
Electronics ground
Line Modules Booksize
247

Advertisement

Table of Contents
loading

Table of Contents