[ IV Test Run Mode ]
IV Test Run Mode

[1] Standard Operation Data (Reference Data)

1. PURY
(1) Cooling operation
Operating conditions
Outdoor unit
LEV opening
Pressure
Outdoor
unit
Temp. of
each
section
Indoor
unit
Operation
Power supply
Ambient
Indoor
tempera-
Outdoor
ture
No. of connected
units
Indoor
No. of operating
unit
units
Model
Main pipe
Piping
Branch pipe
Total pipe length
Fan speed
Amount of refrigerant
Electric current
Voltage
Indoor unit
BC controller (1/3)
Oil return section
High pressure/Low presuure
BC controller liquid/intermediate
Discharge (TH1)
Hear exchanger outlet (TH5)
Accumulator inlet
Accumulator outlet
Inlet
Liquid level detection, upper
(TH4)
Liquid level detection, lower
(TH3)
Compressor shell bottom
LEV inlet
Hear exchanger outlet
PURY-200
CMB-104
V/Hz
200/60
27.0/19.0
DB/WB
°C
35.0/24.0
Unit
4
-
4
-
80
71
56
5
m
5
5
25
-
Hi
Hi
Hi
kg
15.4
A
27.7
V
200
330
460
430
Pulse
2000
-
160
180
20.7/5.0
MPa
19.6/19.6
107 [225]
50 [122]
7 [45]
10 [50]
12 [54]
°C
40 [104]
[°F]
35 [95]
75 [167]
26 [79]
15 [59]
- 6 -
Outdoor unit model
PURY-250
CMB-104
200/60
27.0/19.0
35.0/24.0
4
4
22
112
80
5
5
5
5
5
25
Hi
Hi
Hi
17.2
34.7
200
300
410
330
-
2000
-
180
19.4/4.0
18.3/18.3
110 [230]
47 [117]
7 [45]
10 [50]
12 [54]
40 [104]
35 [95]
70 [158]
30 [86]
15 [59]
71
22
5
5
Hi
Hi
460
300
165
-