8 | MALFUNCTION CODE OF OUTDOOR UNIT
Table 5-2 (8/10.5/18 KW)
Display
Malfunction or Protection
E2
Communication malfunction between indoor/outdoor units
E4
T3&T4 temperature sensor malfunction
E5
Power voltage protection
E6
Fan Protection
E7
Compressor discharge temperature sensor malfunction
E9
EEPROM malfunction
EA
A fan in the Aregion run for more than 5 minutes in Heat mode
Eb
2 times of E6 protection in 10 minutes
H0
Communication malfunction between IR341/main board
P1
Hi-pressure protection
P2
Low-pressure protection
P3
Input current protection
P4
Compressor discharge protection temperature
P5
Condenser high temperature protection
P6
Inverter module protection
P8
Typhoon protection
PE
Indoor evaporator hi-tempprotection
L0
Module malfunction
L1
DC generatrix low voltage protection
L2
DC generatrix high voltage protection
L3
Reserved
L4
MCE malfunction/simultaneously/cycle loop
L5
Zero speed protection
L6
Reserved
L7
Wrong phase protection
L8
Speed difference>15Hz protection between the front and the back clock
L9
Speed difference>15Hz protection between the real and the setting speed
Display Function Instruction:
1. When stand by, LED displaying the amount of indoor units online which communicate with outdoor units.
2. When operation, LED displaying frequency value of compressor.
3. When defrost, LED displaying "dF".