Selection and protection of a motor
(2) Use two motors (Pr. 450)
Set Pr. 450 Second applied motor to use two different motors with one inverter.
When "9999" (initial value) is set, no function is selected.
When a value other than 9999 is set in Pr. 450, the second motor is valid when the RT signal turns on.
For the RT signal, set "3" in any of Pr. 178 to Pr. 184 (input terminal function selection) to assign the function.
REMARKS
The RT signal acts as the second function selection signal and makes the other second functions valid. (Refer to page 134)
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 184 (input terminal function selection) may affect other functions.
Make setting after confirming the function of each terminal.
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
Set the electronic thermal relay function to the thermal characteristic for the constant-torque motor when
using a geared motor (GM-G, GM-D, GM-SY, GM-HY2 series) to perform advanced magnetic flux vector control
or general-purpose magnetic-flux vector control.
Parameters referred to
Pr. 0 Torque boost
Pr. 12 DC injection brake operation voltage
Pr. 80 Motor capacity, Pr. 81 Number of motor poles
Pr. 82 to Pr. 84, Pr. 90 to Pr. 94 (motor constants), Pr. 96 Auto tuning setting/status
Pr. 800 Control method selection
112
CAUTION
Refer to page 77
Refer to page 121
Refer to page 113
Refer to page 76
Refer to page 113