Installation - Hitachi air core 600 Installation & Maintenance Manual

Ducted unit cooling only type
Table of Contents

Advertisement

·Air inlet and outlet are free of obstructions.
·The air passage is not blocked.
·Condensate can drain properly.
·Overhead structure can support the weight of the
indoor unit.
·The false ceiling is not seem to be at an incline.
·Adequate clearance for maintenance and service is
provided.(See Fig.3.1.1 )
·Piping between the indoor and outdoor units is within
the allowable limits.(refer to the installation of the
outdoor unit )
·The indoor unit, outdoor unit, power supply wiring
and transmission wiring must be kept at least 3.3ft.(1m)
away from televisions and radios to prevent
electromagnetic interference.
(Noise may be generated depending on the conditions
under which the electric wave is generated, even if a
3.3ft allowance is maintained.)
·Do not install the indoor unit in a machine shop or
kitchen where vapor from oil or its mist flows to the
indoor unit. The oil will deposit on the heat exchanger,
thereby reducing the performance of the indoor unit,
and in severe cases, damaging the indoor unit.
Use suspension bolts to install the unit. Check whether
·
or not the overhead structure can support the
weight of the unit. If there is a risk that the structure
cannot provide adequate support, reinforce the structure
before installing the unit.
For bottom intake, replace the chamber lid in the
procedure listed in fig.
(1) Remove the chamber lid.
(2) Reattach the removed filter in the orientation
shown in Fig. 3.1.2, reattach the removed
chamber lid in the orientation shown in Fig. 3.1.3,
refer to Fig.3.1.3 for the direction of filter.
Fig.3.1.3
(bottom return invaild for 48K/60K model)
Intake-side flange
Filter(invalid for some models)
Chamber lid
Fig.3.1.2
Chamber lid
Filter(invalid for
some models)
Intake-side flange
Installation and Maintenance

3.2 Installation

3.2.1 Suspension bolts
(1) Consider the pipe direction, wiring, and
maintenance carefully. choose the proper
direction and location for installation.
(2) Install the suspension bolts as shown in Fig. 3.2.1
below.
·For the concrete
6 to 6-5/16 in.
(150 to160mm)
Concrete
Steel bar
Suspension bolts
(W3/8 or M10)
·For the wooden beam
Wood rib
2-3/8 to 3-1/2 in.
(
60 to 90 mm
)
Wooden beam
Fig. 3.2.1 Securing the suspension bolts
3.2.2 The position of the suspension bolts and the pipes
(1) Mark the location of the suspension bolts, the
refrigerant pipes, and the drain pipes.
(2) The dimension are shown below.
Model
18/25K
30/36K
42/48/55K
Fig. 3.3 Suspension bolts
23
·For the steel beam
Screw in
220 to 330 lb.
(100 to150kg)
" " shaped steel beam
Suspension bolts
(W3/8 or M10)
Nut
Round washer
Square washer
Nut
Suspension bolts
Air outlet
a
b
Air inlet
a
b
c
1231
1180
375
1177
1140
666
1334
1300
756
(Unit: mm)
d
447
720
800