The WHMI can be accessed locally and remotely.
• Locally by connecting the laptop to the protection relay
• Remotely over LAN/WAN
2.7

User authorization

The user management for the protection relay can be handled in two possible ways.
Only one user management way can be enabled in the protection relay at a time.
For more information, see the cyber security deployment guideline.
2.7.1

Local user account management

Four factory default user accounts (VIEWER, OPERATOR, ENGINEER and
ADMINISTRATOR) have been predefined for the LHMI and the WHMI, each with
different rights and default passwords. The roles for these user accounts are the
same as the username. Additional user accounts can be added for the protection
relay.
IED Users in PCM600 is used to manage the user accounts. Each protection relay
supports eight fixed roles and 50 user accounts belonging to any one of these roles.
Each user account can be mapped to a maximum of eight roles.
The factory default passwords can be changed with Administrator user rights or
by the users themselves. Relay user passwords can be changed using the LHMI, IED
Users in PCM600 or the WHMI. Only Administrator can create user accounts and
update the roles-to-rights mapping. Administrator can also reset the passwords of
the users.
User authorization is disabled by default for the LHMI and can be enabled with
the
Passwords. WHMI always requires authentication. Changes in user management
settings do not cause the protection relay to reboot. The changes are taken into use
immediately after committing the changed settings.
2.7.2

Central account management

The user accounts and roles can be created and authenticated centrally in a CAM
server. CAM needs to be activated in the protection relay from Account Management
in PCM600.
A CAM server can be an Active Directory (AD) server such as Windows AD. There can
also be a secondary or redundant CAM server configured which can act as a backup
CAM server if the primary CAM server is not accessible.
REX640
Technical Manual
Submenus
Local override parameter via the menu path Configuration > Authorization >
Description
Used to view the menu tree structure for the
protection relay's setting parameters
Used to change the language
Used to end the session