FDCIE Maintenance

32
The FDCIE shall be maintained and tested in accordance with the Australian standard
AS1851.
To avoid the Fault TX output(s) to be activated, they can be disabled via menu H2/B5 (or
via an open door, see chapter "Open door" page 56. However, in Australia the routing
equipment must be isolated via the ASE.
Regarding the fault condition, see chapter "Fault", page 71 and "Fault messages", page 72
Note: Most of the faults have approximately 60 seconds delay.
Each control unit should be tested as follows:
Perform monthly / quarterly / yearly test (menu H1).
Remove one battery fuse (e.g. F2 on the Main board 5012). The following fault
message will be shown within one minute:
Re-place the fuse and acknowledge the fault (menu H6).
Check the manual call points on the panel door. Take required measures. Use
the manual call point test key to activate fire alarm.
Check some control outputs. Are they activated according to programmed control
expressions?
32.1

Replacing a TLON Connection Board and/or the Main Board

In a TLON network programming, some unique data is stored in a memory on the 5090
TLON connection board and some stored in a memory on the main board.
Note: The main board 5012 is not compatible with the old TLON connection board 1590.
Replacing only a TLON connection board 5090
After replacing the board:
In TLON Manager version 1.2 do "Replace", "Update" and "Save".
In TLON Manager version ≥ V2.0 do "Replace" and "Update" ("Save" is
automatically done).
Replacing both a TLON connection board 5090 and also the Main Board
After replacing the boards:
In TLON Manager version 1.2 do "Replace", "Update" and "Save".
In TLON Manager version ≥ V2.0 do "Replace" and "Update" ("Save" is
automatically done).
Replacing the Main board
After replacing the main board, mount the TLON connection board(s) in the same position
as on the replaced main board:
In TLON Manager version 1.2 do "Update" and "Save".
In TLON Manager version ≥ V2.0 do "Update" ("Save" is automatically done).
FAULT: Battery not connected CU xx