Parameter
Maximum charge
power (kW)
Maximum discharge
power (kW)
End-of-charge SOC
(%)
End-of-discharge
SOC (%)
Charge from grid
Grid charge cutoff
SOC

7.2.1.4 Capacity Control

Prerequisites
The screenshots in this section are captured from the SUN2000 app 6.23.00.125.
The actual screens may vary with app updates.
Description
If the inverter connects to an ESS and the ESS working mode is set to Maximum
self-consumption or TOU, you can set capacity control parameters.
Table 7-3 Application Scenario
Applicable Model
SUN2000-
(2KTL-6KTL)-L1
Issue 10 (2023-02-13)
Description
Retain this parameter to the
maximum charge power.
Additional configuration is not
required.
Retain this parameter to the
maximum discharge power.
Additional configuration is not
required.
Set the charge cutoff capacity.
Set the discharge cutoff
capacity.
If Charge from grid function is
disabled by default, comply
with the grid charge
requirements stipulated in local
laws and regulations when this
function is enabled.
Set the grid charge cutoff SOC.
Application Scenario
Single inverter + LUNA2000 directly connected to the
management system
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interaction
Value Range
● Charge: [0,
Maximum charge
power]
● Discharge: [0,
Maximum
discharge power]
90%–100%
0%–20% (When no PV
module is configured
or the PV modules
have no voltage for 24
hours, the minimum
value is 15%.)
● Disable
● Enable
[20%, 100%]
81