4.2.4 Grounding the ESS
Prerequisites
● The grounding should comply with the local electrical safety regulations.
● Do not connect devices such as fuses and switches to ground cables.
● Connect ground cables to the ground points of the ESS enclosure or the main
●
●
Context
The ESS can be grounded using ground lugs or ground cables. The requirements
are as follows:
●
●
Connect ground cables
Method 1:Connect ground cables to the ground points of the ESS enclosure
Step 1 Connect ground cables to the ground points of the ESS using M12x30 stainless
steel bolt assemblies. The ground cables can be routed through plastic-coated
metal hoses based on site requirements.
Issue 02 (2021-11-15)
CA UTION
ground bar of the control unit cabin based on site requirements.
The ESS is installed.
The grounding requirements are clear.
Ground lug: Use ground lugs made of hot-dip zinc-coated flat steel with a
cross-sectional area of 40 mm x 4 mm, and the concrete platforms must be
300 mm above the ground.
Ground cable
Table 4-3 Ground cable description
No.
Cable
1
Ground
cable
The specifications of the ground cable are subject to this table or calculated
according to IEC 60364-5-54.
Copyright © Huawei Technologies Co., Ltd.
Type
Cross-
Sectional
Area
Single-
16–240
core
2
mm
outdoor
copper
cable and
M12
OT/DT
terminals
4 Installation
Outer
Source
Diameter
10–32 mm
Prepared
by the
customer
78