– Vlow: 0 Vdc
– Vhigh: 15-24 Vdc
– Driving current: 13 mA @ 24 Vdc (Rint = 1.88 kΩ)
The digital inputs have free of potential contacts (opto-isolated).
By default, the digital inputs are disabled.
In a master-master filter arrangement, only the master that has the control over the complete system will monitor its
digital outputs. For full redundant functionality, it is recommended to cable the digital inputs of all the units in the filter
system.
70
Digital Outputs 1 to 6
With each digital output different filter conditions can be associated. The association between the filter condition and
the digital outputs is done with the PQF-Manager.
Remarks:
– In order to set up this function, navigate to [/Welcome/Settings/Customer set./Digital Outputs]
– Different programmable warnings and alarms can be defined
The default set-up for the digital contacts is given in
Digital output number
1
2
3
4
5
6
The customer can change the default output settings by means of the PQF-Manager.
The digital outputs contacts have a common point and are of the NO-type (normal open). The contact ratings are:
Maximum continuous ac rating: 440 Vac/1.5 A;
Maximum continuous dc rating: 110 Vdc/0.3 A;
The common is rated at 9A/terminal, giving a total of 18 A.
Information on cabling the digital output contacts and on setting up the digital outputs with the PQF-Manager is given
in the detailed manuals.
71
Alarm outputs and fan outputs
STATUS
Approved
Table 11.
Table 11: Default set-up for the digital output contacts
Icons
SECURITY LEVEL
Public
Default function
Auxil. ON
PQF running
Full Load
Armed
Unit miss.
T Limit
DOCUMENT ID
9AKK107045A4703
Q UICK STA RT-UP G UI DE
REV.
LANG.
PAGE
D
en
18/41
© 2022 Hitachi Energy. All rights reserved.

Advertisement

Table of Contents
loading

Table of Contents