Bosch rexroth CytroBox Operating Instructions Manual page 93

Hydraulic power unit
Table of Contents

Advertisement

Selection of the operating point in fixed command value mode
The selection of the operating point for p and n can be specified cyclically via the
parameters. The function is selected in the 1-ms task. For pressure, the operating
point can be selected using P-0-1394, while the operating point for speed can be
selected using P-0-1395. The assignment to the operating point is provided in the
following table:
Table 47: Selection of the operating point
Value for the selection of the operating point
P-0-1394/P-0-1395
0
1
2
3
ELSE
The operating points for pressure p and speed n can be configured in the
following parameters:
Table 48: Configuration of the operating points
Operating point index
0
1
2
3
3. Configuration of the hydraulic power unit (HPU)
The configuration of the HPU is pre-set at the factory and usually does not need to
be adjusted. Any changes that are necessary nonetheless can be made via parameter
P-0-1380. Moreover, the threshold values can be adjusted, if necessary.
Only carry out changes if they are absolutely necessary and you have agreed them
with Bosch Rexroth.
Commissioning 93/128
Operating point
No new operating point is assigned. The last
valid value in the command value presetting
remains active.
Operating point
Pressure p
P-0-1311[100]
P-0-1311[101]
P-0-1311[102]
P-0-1311[103]
CytroBox, RE 51057-B/11.19, Bosch Rexroth AG
0
1
2
3
Speed n
P-0-1311[110]
P-0-1311[111]
P-0-1311[112]
P-0-1311[113]